The 1794-IRT8 is the fast temperature card of FLEX I/O: thermocouples, 2/3/4-wire RTDs and millivolt sources on eight configurable channels, with 8–10 ms throughput and 14-bit resolution.
Speed and diagnostics are the point: wire-off, overrange and underrange are reported per channel, and Series B accepts grounded thermocouples at a plus/minus 15V common mode range.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O thermocouple, RTD and mV input, 1794 terminal base |
Cat Num |
1794-IRT8 |
Brand Name |
Rockwell |
Channels |
8, configurable per channel |
Input ranges |
-40...+100 mV DC thermocouple, 0...325 mV DC RTD, 0...500 Ohm |
Resolution |
14 bits |
Throughput |
7.4 ms mV, 8.0...10.8 ms RTD, 8.0...8.8 ms thermocouple |
Excitation current |
630 uA |
Accuracy |
0.05% of full range in mV mode with filtering |
Common mode rejection |
-80 dB at 5V peak-to-peak, 50...60 Hz |
Common mode range |
Series A +/-4V, Series B +/-15V |
External supply current |
85 mA at 24V DC |
Operating temperature |
-20...55 deg C, XT -20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
-40...+100 mV DC for thermocouples, 0...325 mV DC for RTDs and 0...500 Ohm for direct resistance, configurable per channel.
Eight thermocouple types:B, E, J, K, N, R, S and T, plus TXK/XK (L), each with its published temperature span.
RTD types:Pt100 (0.00385 and 0.003916), Pt200, Ni100, Ni120, Ni200 and Cu10, all with the published ranges.
2-wire, 3-wire and 4-wire RTDs are accepted; four-wire removes both lead and connection resistance from the measurement.
Cold junction compensation uses the 1794-CJC2 compensator;two are shipped with the module and they fit in the terminal base.
7.4 ms for mV, 8.0 to 10.8 ms for RTD and 8.0 to 8.8 ms for thermocouple is the published throughput, far faster than the 1794-IR8's 28...325 ms.
14-bit resolution is the trade for the speed: the RTD card publishes 16 bits across its span, this one 14.
0.05% of full range in mV mode with filtering selected,0.10% with hardware filtering only.
Overall drift of 150 ppm/deg C for Series A and 50 ppm/deg C for Series B is a series difference worth checking against the module label.
Common mode rejection of -80 dB at 5V peak-to-peak,50 to 60 Hz, is what allows long thermocouple runs in a noisy cabinet.
Wire-off, overrange and underrange detection per channel, with alarm bits the program can read instead of comparing values.
Series A defaults to the maximum value on an open input in both RTD and TC modes; Series B defaults to maximum in RTD mode and minimum in TC mode.
Open input detection is immediate (within two scans)on Series A revision E or later and on all Series B modules; earlier Series A revisions take up to 3.8 s.
Series B extends the common mode range to +/-15V and that is what allows grounded thermocouples to be used directly.
Cold junction compensation range is -20...+100 deg C on revision E and later, which matters if the terminal base sits in a warm cabinet.
Shielded thermocouple wire, shield at the module,is the practice that matches the -80 dB common mode rejection.
Unused channels should be shorted for maximum throughput, which is stated in the publication rather than inferred.
630 uA excitation on the RTD modes is low enough that self-heating stays out of the error budget.
-20...55 deg C standard, -20...70 deg C with the XT suffix,with the XT version conformally coated.
Fast temperature loops — extruder zones, fast ovens, anywhere an 8 ms update is wanted.
Mixed temperature points on one card: four thermocouples and four RTDs is a normal configuration.
Grounded thermocouples where Series B and its +/-15V common mode are required.
Not the accuracy choice.Where 0.01% of full scale matters, the 1794-IR8 in enhanced mode is the card to specify.
What inputs does the 1794-IRT8 accept?
Thermocouples, 2/3/4-wire RTDs and millivolt sources, configurable per channel across eight channels.
Which thermocouple types are supported?
B, E, J, K, N, R, S, T and TXK/XK (L).
How fast is the update?
7.4 ms in mV mode, 8.0...10.8 ms for RTDs and 8.0...8.8 ms for thermocouples.
What is the resolution?
14 bits.
How is cold junction compensation done?
With the 1794-CJC2 compensator; two are supplied with the module.
Can it read grounded thermocouples?
Yes, with Series B modules, whose common mode range is +/-15V.
| Catalog number | Channels | Input ranges | Resolution | Accuracy |
|---|---|---|---|---|
| 1794-IF4I | 4, channel-to-channel isolated, individually configurable | 4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V, 0...5V | 16 bits unipolar, 15 bits plus sign bipolar; 0.320/0.640 uA/cnt, 0.156/0.313 mV/cnt | 0.1% of full scale at 25 deg C |
| 1794-IF4IXT | 4, channel-to-channel isolated, individually configurable | 4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V, 0...5V | 16 bits unipolar, 15 bits plus sign bipolar | 0.1% of full scale at 25 deg C |
| 1794-IRT8 | 8, configurable per channel | -40...+100 mV DC thermocouple, 0...325 mV DC RTD, 0...500 Ohm | 14 bits | 0.05% of full range in mV mode with filtering |
| 1794-IF8IH | 8, isolated channel to channel, one HART device per channel | 4...20 mA, 0...20 mA (default 0...20 mA) | 16 bits unipolar, 15 bits plus sign bipolar; 0.320/0.640 uA per count | 0.1% of full scale at 25 deg C |
Reading the channel count first is misleading on this table: a four-channel module with a faster conversion can be the better choice for a loop that has to be sampled twice per second.
For 1794-IRT8 the published row reads 8, configurable per channel channels over -40...+100 mV DC thermocouple, 0...325 mV DC RTD, 0...500 Ohm, at 14 bits resolution and 0.05% of full range in mV mode with filtering accuracy; the external supply draws 85 mA at 24V DC and the operating range is -20...55 deg C, XT -20...70 deg C.
Common-mode rejection is the column that decides whether a thermocouple input survives next to a drive; the modules that print it are the ones built for that duty.
Common-mode rejection on this module is published as -80 dB at 5V peak-to-peak, 50...60 Hz over a common-mode range of Series A +/-4V, Series B +/-15V, which is the figure to quote when the input shares a cabinet with a drive.
Related models, options and spare parts for this range are listed in the Allen-Bradley Flex I/O 1794 modules category.