Product Details:
Payment & Shipping Terms:
|
The 1794-IF4IXT is the extended-temperature version of the isolated four-channel analog input, published -20...70 deg C with the same seven ranges and channel-to-channel isolation.
It is the card for an outdoor or unheated enclosure that still needs isolated analog measurement: the electronics are conformally coated and the temperature rating is widened.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O isolated analog input, 1794 terminal base |
Cat Num |
1794-IF4IXT |
Brand Name |
Rockwell |
Channels |
4, channel-to-channel isolated, individually configurable |
Input ranges |
4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V, 0...5V |
Resolution |
16 bits unipolar, 15 bits plus sign bipolar |
Input resistance |
<100 Ohm current, >10 MOhm voltage |
Conversion rate |
2.5, 5.0 or 7.5 ms, all channels |
Accuracy |
0.1% of full scale at 25 deg C |
External supply current |
55 mA at 24V DC |
Power dissipation |
2.0 W at 31.2V DC (6.8 BTU/hr) |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
-20...70 deg C operating range is the only functional difference from the 1794-IF4I, together with conformal coating on the assembly.
Seven input ranges and channel-to-channel isolation are carried over unchanged: 4...20 mA through 0...5V, each channel independent.
16-bit unipolar resolution and 0.1% of full scale accuracy at 25 deg C remain the published figures.
2.0 W at 31.2V DC (6.8 BTU/hr) is the module heat, marginally lower in the published table than the standard version.
Sigma-delta conversion at 2.5, 5.0 or 7.5 ms for all four channels, with the filter frequency selection setting both rejection and response.
150, 300, 600 and 1200 Hz filter settings give step responses from 26.7 ms down to 0.6 ms to 63% of full scale.
At the 300 Hz setting the card rejects 50 Hz by 80 dB, which is the figure to quote when a loop sits beside a drive.
1200 Hz is unaffected by the module-level parameters that apply to the other three filter settings.
Conformal coating protects the assembly from condensation during a cold start, which is the reason the XT line exists.
-40...85 deg C storage and 5...95% RH non-condensing are the general limits that apply outside the operating window.
Condensation is the risk, not the cold: a panel that cycles between a warm plant and a cold night accumulates moisture, and the coating is what tolerates it.
Isolation still requires a return at the module for each loop; the coating does not remove the need for a sensible ground reference.
55 mA at 24V DC is the module consumption; the loop supply belongs to the transmitter, not to the card.
Current input below 100 Ohm, voltage input above 10 MOhm — the burden figures that decide whether a two-wire transmitter can drive the loop.
One signal type per channel, with shielded twisted pair and the return at the module, is the wiring practice on this card as on the standard version.
Keying and the FlexBus insertion sequence are the same five steps as on every FLEX I/O module.
Outdoor cabinets, cold stores and unheated skids where -20 deg C start is a normal condition.
Mixed ground references that need per-channel isolation in the same panel.
Not for HART. The HART-enabled isolated card is the 1794-IF8IH with eight channels.
Not for temperature sensors. Thermocouples and RTDs need the 1794-IRT8, whose input stage and cold junction are designed for them.
How does the 1794-IF4IXT differ from the 1794-IF4I?
The extended version is rated -20...70 deg C and is conformally coated; ranges, resolution and isolation are the same.
What isolation does it have?
Channel-to-channel isolation on four channels, plus field-to-system isolation.
What conversion rates are available?
2.5, 5.0 or 7.5 ms for all channels, with 150/300/600/1200 Hz filter selections.
What ranges are supported?
4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V and 0...5V, per channel.
How much current does it draw?
55 mA at 24V DC for the module itself.
Is it factory calibrated?
Yes, and it can be recalibrated in the field when a documented trace is required.
| Catalog number | Channels | Input ranges | Resolution | Accuracy |
|---|---|---|---|---|
| 1794-IF4I | 4, channel-to-channel isolated, individually configurable | 4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V, 0...5V | 16 bits unipolar, 15 bits plus sign bipolar; 0.320/0.640 uA/cnt, 0.156/0.313 mV/cnt | 0.1% of full scale at 25 deg C |
| 1794-IF4IXT | 4, channel-to-channel isolated, individually configurable | 4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V, 0...5V | 16 bits unipolar, 15 bits plus sign bipolar | 0.1% of full scale at 25 deg C |
| 1794-IRT8 | 8, configurable per channel | -40...+100 mV DC thermocouple, 0...325 mV DC RTD, 0...500 Ohm | 14 bits | 0.05% of full range in mV mode with filtering |
| 1794-IF8IH | 8, isolated channel to channel, one HART device per channel | 4...20 mA, 0...20 mA (default 0...20 mA) | 16 bits unipolar, 15 bits plus sign bipolar; 0.320/0.640 uA per count | 0.1% of full scale at 25 deg C |
Reading the channel count first is misleading on this table: a four-channel module with a faster conversion can be the better choice for a loop that has to be sampled twice per second.
For 1794-IF4IXT the published row reads 4, channel-to-channel isolated, individually configurable channels over 4...20 mA, 0...20 mA, +/-20 mA, +/-10V, 0...10V, +/-5V, 0...5V, at 16 bits unipolar, 15 bits plus sign bipolar resolution and 0.1% of full scale at 25 deg C accuracy; the external supply draws 55 mA at 24V DC and the operating range is -20...70 deg C.
Common-mode rejection is the column that decides whether a thermocouple input survives next to a drive; the modules that print it are the ones built for that duty.
The source publication does not print a common-mode rejection figure for this module, so a thermocouple or millivolt input sharing a cabinet with a drive has to be screened by wiring practice rather than by a module specification.
Browse the Allen-Bradley Flex I/O 1794 modules category for the other models, options and spare parts that share this range.