Product Details:
Payment & Shipping Terms:
|
The 1794-IE8XT is the extended-temperature version of the eight-channel analog input module: 4...20 mA, 0...20 mA, +/-10V and 0...10V, configurable per channel, rated -20...70 deg C.
It is the general-purpose analog card of FLEX I/O — not isolated, not HART, but 256 us conversion across all eight channels and internal calibration that needs no user trim.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O analog input, 1794 terminal base |
Cat Num |
1794-IE8XT |
Brand Name |
Rockwell |
Channels |
8, single-ended, individually configurable |
Input ranges |
4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC |
Input impedance |
238 Ohm current, 100 kOhm voltage |
Resolution |
12 bits unipolar, 11 bits plus sign bipolar |
Conversion rate |
256 us, all channels |
Accuracy |
0.20% of full scale at 25 deg C |
Overload |
30V continuous, 32 mA continuous, single channel |
External supply current |
60 mA at 24V DC |
Power dissipation |
3 W at 31.2V DC (10.2 BTU/hr) |
Isolation |
Field to system, basic insulation; no channel isolation |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Four ranges per channel: 4...20 mA, 0...20 mA, +/-10V DC and 0...10V DC, selected individually in configuration rather than as a module-wide setting.
12-bit unipolar and 11-bit plus sign bipolar resolution, which is 5.13 uA or 2.56 mV per count in unipolar mode.
238 Ohm current input impedance and 100 kOhm voltage input impedance define the load the sensor sees and the burden the loop carries.
0.20% of full scale at 25 deg C includes offset, gain, non-linearity and repeatability, so it is the number to use in an accuracy budget, not a typical value.
30V and 32 mA overload tolerance on a single channel is what survives a miswired transmitter on commissioning day.
256 us conversion for all eight channels is a successive-approximation converter, not a sigma-delta, which is why the update is fast and the noise rejection is modest.
Normal mode rejection is -15.3 dB at 50 Hz and -16.8 dB at 60 Hz for current input, so line-frequency ripple does reach the data and the program has to average if it matters.
Step response to 63% is 18.2 ms on current input and 9.4 ms on voltage input, which sets the fastest loop this card can serve.
Internal calibration means no user trim; the factory calibration is maintained by the module rather than by a potentiometer.
60 mA at 24V DC from the external supply is the module's own consumption, separate from any loop current.
3 W at 31.2V DC (10.2 BTU/hr) is the heat the enclosure removes for eight channels.
The external supply is 24V DC nominal, shared with the rest of the island; the module does not source loop power for a 4...20 mA transmitter.
Two-wire, three-wire and four-wire sensors are all supported, so the same card serves a loop-powered transmitter and a four-wire analyser.
Keying, FlexBus connector fully left, pin inspection, alignment, latch — the five insertion steps in 1794-IN093 apply unchanged.
-20...70 deg C operating range is the reason to choose the XT suffix: a panel that starts cold or sits in an unheated enclosure.
Two-wire input on a single-ended card needs the return at the module common; a floating transmitter with a separate 24V supply introduces a ground loop that the non-isolated card cannot break.
One range per channel, not both: connecting a voltage source and a current loop to the same channel is a wiring error, not a configuration choice.
General process signals in a panel that already has a 24V rail and does not need channel isolation.
Fast scan applications where 256 us across eight channels is the reason to prefer it over a sigma-delta module.
Not for HART — the 1794-IE8H carries the HART modem; the IE8XT reads the analog value only.
Not for thermocouples or RTDs — those need the 1794-IRT8, 1794-IT8 or 1794-IR8, which have the cold-junction and excitation circuitry.
What input ranges does the 1794-IE8XT accept?
4...20 mA, 0...20 mA, +/-10V DC and 0...10V DC, configurable per channel.
What is its resolution?
12 bits unipolar and 11 bits plus sign bipolar, with 5.13 uA or 2.56 mV per count in unipolar mode.
How fast does it convert?
256 us for all eight channels, successive approximation.
How accurate is it?
0.20% of full scale at 25 deg C, including offset, gain, non-linearity and repeatability.
Does it supply loop power?
No. It draws 60 mA at 24V DC for itself; the transmitter needs its own loop supply.
What temperature range does the XT version accept?
-20...70 deg C, against -20...55 deg C for the standard 1794-IE8.
Related models, options and spare parts for this range are listed in the Allen-Bradley Flex I/O 1794 modules category.