logo
Home ProductsAB FlexLogix I/O 1794

Allen Bradley PLC 1794-IE8XT / 1794IE8XT

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1794-IE8XT / 1794IE8XT

China Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier
Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier Allen Bradley PLC 1794-IE8XT / 1794IE8XT supplier

Large Image :  Allen Bradley PLC 1794-IE8XT / 1794IE8XT

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1794-IE8XT / 1794IE8XT

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $514.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1794-IE8XT technical data PDF download FLEX I/O 1794-IE8XT / 1794IE8XT 8-Channel Analog Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1794-IE8XT is the extended-temperature version of the eight-channel analog input module: 4...20 mA, 0...20 mA, +/-10V and 0...10V, configurable per channel, rated -20...70 deg C.

It is the general-purpose analog card of FLEX I/O — not isolated, not HART, but 256 us conversion across all eight channels and internal calibration that needs no user trim.

1794-IE8 8-channel analog input module IN STOCK
1794-IE8XT 8-channel analog input module, extended temperature IN STOCK
1794-IE8H 8-channel HART analog input module IN STOCK
1794-IE12 12-channel analog input module IN STOCK
1794-IE12K 12-channel analog input module, conformal coated IN STOCK
1794-IF4I 4-channel isolated analog input module IN STOCK
1794-IF4IXT 4-channel isolated analog input, extended temperature IN STOCK
1794-IF4ICFXT 4-channel isolated analog input, conformal coated IN STOCK
1794-IF8IH 8-channel HART isolated analog input module IN STOCK
1794-IR8 8-channel RTD input module IN STOCK
1794-IRT8 8-channel thermocouple/RTD input module IN STOCK
1794-IRT8XT 8-channel thermocouple/RTD input, extended temperature IN STOCK
1794-IT8 8-channel thermocouple/mV input module IN STOCK
1794-IE8XOE4 8-input, 4-output analog combination module IN STOCK
1794-IE4XOE2 4-input, 2-output analog combination module IN STOCK
1794-IF2XOF2I 2-input, 2-output isolated analog combination module IN STOCK
1794-OE4 4-channel analog output module IN STOCK
1794-OE12 12-channel analog output module IN STOCK

Product Specifications 1794-IE8XT (PDF)
 Application
 FLEX I/O analog input, 1794 terminal base
 Cat Num
 1794-IE8XT
 Brand Name
 Rockwell
 Channels
 8, single-ended, individually configurable
 Input ranges
 4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC
 Input impedance
 238 Ohm current, 100 kOhm voltage
 Resolution
 12 bits unipolar, 11 bits plus sign bipolar
 Conversion rate
 256 us, all channels
 Accuracy
 0.20% of full scale at 25 deg C
 Overload
 30V continuous, 32 mA continuous, single channel
 External supply current
 60 mA at 24V DC
 Power dissipation
 3 W at 31.2V DC (10.2 BTU/hr)
 Isolation
 Field to system, basic insulation; no channel isolation
 Operating temperature
 -20...70 deg C

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1794-IE8XT original product photograph, wide view 1794-IE8XT original product photograph, wide view 1794-IE8XT original product photograph, wide view

Signal ranges and resolution

Four ranges per channel: 4...20 mA, 0...20 mA, +/-10V DC and 0...10V DC, selected individually in configuration rather than as a module-wide setting.

12-bit unipolar and 11-bit plus sign bipolar resolution, which is 5.13 uA or 2.56 mV per count in unipolar mode.

238 Ohm current input impedance and 100 kOhm voltage input impedance define the load the sensor sees and the burden the loop carries.

0.20% of full scale at 25 deg C includes offset, gain, non-linearity and repeatability, so it is the number to use in an accuracy budget, not a typical value.

30V and 32 mA overload tolerance on a single channel is what survives a miswired transmitter on commissioning day.

Conversion and filtering

256 us conversion for all eight channels is a successive-approximation converter, not a sigma-delta, which is why the update is fast and the noise rejection is modest.

Normal mode rejection is -15.3 dB at 50 Hz and -16.8 dB at 60 Hz for current input, so line-frequency ripple does reach the data and the program has to average if it matters.

Step response to 63% is 18.2 ms on current input and 9.4 ms on voltage input, which sets the fastest loop this card can serve.

Internal calibration means no user trim; the factory calibration is maintained by the module rather than by a potentiometer.

Supply and dissipation

60 mA at 24V DC from the external supply is the module's own consumption, separate from any loop current.

3 W at 31.2V DC (10.2 BTU/hr) is the heat the enclosure removes for eight channels.

The external supply is 24V DC nominal, shared with the rest of the island; the module does not source loop power for a 4...20 mA transmitter.

Two-wire, three-wire and four-wire sensors are all supported, so the same card serves a loop-powered transmitter and a four-wire analyser.

Installation

Keying, FlexBus connector fully left, pin inspection, alignment, latch — the five insertion steps in 1794-IN093 apply unchanged.

-20...70 deg C operating range is the reason to choose the XT suffix: a panel that starts cold or sits in an unheated enclosure.

Two-wire input on a single-ended card needs the return at the module common; a floating transmitter with a separate 24V supply introduces a ground loop that the non-isolated card cannot break.

One range per channel, not both: connecting a voltage source and a current loop to the same channel is a wiring error, not a configuration choice.

Where it fits

General process signals in a panel that already has a 24V rail and does not need channel isolation.

Fast scan applications where 256 us across eight channels is the reason to prefer it over a sigma-delta module.

Not for HART — the 1794-IE8H carries the HART modem; the IE8XT reads the analog value only.

Not for thermocouples or RTDs — those need the 1794-IRT8, 1794-IT8 or 1794-IR8, which have the cold-junction and excitation circuitry.

FAQ — 1794-IE8XT

What input ranges does the 1794-IE8XT accept?

4...20 mA, 0...20 mA, +/-10V DC and 0...10V DC, configurable per channel.

What is its resolution?

12 bits unipolar and 11 bits plus sign bipolar, with 5.13 uA or 2.56 mV per count in unipolar mode.

How fast does it convert?

256 us for all eight channels, successive approximation.

How accurate is it?

0.20% of full scale at 25 deg C, including offset, gain, non-linearity and repeatability.

Does it supply loop power?

No. It draws 60 mA at 24V DC for itself; the transmitter needs its own loop supply.

What temperature range does the XT version accept?

-20...70 deg C, against -20...55 deg C for the standard 1794-IE8.


Data sources. Technical values on this page come from Rockwell publication 1794-SG002 (FLEX I/O Selection Guide, Table 19 and Table 20) and 1794-IN093. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

Related models, options and spare parts for this range are listed in the Allen-Bradley Flex I/O 1794 modules category.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)