The 1794-AENTRXT is the extended-temperature dual-port adapter: same two RJ45 ports and 8-module capacity, rated -25...70 deg C with conformal coating to ISA Class G3.
It draws less current and dissipates less heat than the standard dual-port adapter — 400 mA and 6.1 W against 500 mA and 7.1 W — which is part of how the wider range is achieved.
| 1794-AENT | EtherNet/IP adapter, single RJ45, 8 modules | IN STOCK |
| 1794-AENTR | dual-port EtherNet/IP adapter, redundancy capable | IN STOCK |
| 1794-AENTRXT | dual-port EtherNet/IP adapter, extended temperature | IN STOCK |
| 1794-ACN15 | ControlNet adapter, 5 Mbps, 8 modules | IN STOCK |
| 1794-ACN15K | ControlNet adapter, 5 Mbps, conformal coated | IN STOCK |
| 1794-ACNR | ControlNet adapter with redundant media | IN STOCK |
| 1794-ACNR15XT | ControlNet adapter, redundant media, extended temperature | IN STOCK |
| 1794-ACN | ControlNet adapter module, 8 modules | IN STOCK |
| 1794-ADN | DeviceNet adapter, 8 modules | IN STOCK |
| 1794-ADNK | DeviceNet adapter, conformal coated | IN STOCK |
| 1794-APB | Profibus DP adapter, 8 modules | IN STOCK |
| 1794-APBDPV1 | Profibus DP-V1 adapter, 8 modules | IN STOCK |
| 1794-ASB | Remote I/O adapter, 8 modules | IN STOCK |
| 1794-ASB2 | Remote I/O adapter, extended functionality | IN STOCK |
| 1794-ASBLT | Remote I/O adapter with built-in termination | IN STOCK |
Application |
FLEX I/O-XT dual-port EtherNet/IP adapter |
Cat Num |
1794-AENTRXT |
Brand Name |
Rockwell |
I/O module capacity |
8 modules |
Ethernet connectors |
2 x RJ45 Category 5 |
Communication rate |
10/100 Mbps |
Input voltage |
24V DC nom, 19.2...31.2V DC range |
Flexbus output |
640 mA at 5V DC |
Power consumption, max |
400 mA at 24V DC |
Coating |
ISA/ANSI-71.040 Class G3 |
Operating temperature |
-25...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
-25...70 deg C operating, 70 deg C maximum surrounding air, per 1794-IN131.
Conformal coating to ISA/ANSI-71.040-1985 Class G3, for noxious gas environments.
T4 temperature code for 1794-AENTRXT, with Ex ec IIC T4 Gc protection.
Same 8-module capacity and 640 mA Flexbus output as the standard adapter.
400 mA at 24V DC maximum consumption, 100 mA below the standard part.
6.1 W dissipation at 19.2V DC and 20.8 BTU/hr, the lowest of the three EtherNet/IP adapters.
18 A inrush for 2 ms, unchanged from the standard dual-port adapter.
19.2...31.2V DC input range with 5 percent ripple tolerance.
Two RJ45 Category 5 ports with link 1 and link 2 indicators, for redundant media.
10/100 Mbps, ODVA conformance tested to the EtherNet/IP specification.
50V continuous isolation, tested at 1000V AC for 60 s, power to Flexbus to EtherNet/IP.
87 x 94 x 92 mm and 227 g, the same envelope as the standard dual-port part.
Cold or hot enclosures where the standard 0...55 deg C part is out of range.
Corrosive or condensing atmospheres where the G3 coating matters.
Not for a single-cable star; the single-port 1794-AENT is simpler.
Not the ControlNet equivalent.
-XT islands built on coated bases and modules.
Outdoor cabinets and skids.
Not 16 modules; capacity stays at 8.
Not a safety adapter.
What is the operating range of the 1794-AENTRXT?
-25...70 deg C with Class G3 conformal coating.
How many modules can it carry?
8 FLEX I/O modules.
What is the power consumption?
400 mA at 24V DC maximum, 6.1 W dissipation.
Does it have two ports?
Yes, two RJ45 Category 5 ports for redundant media.
What protection method applies?
Ex ec IIC T4 Gc, T4 temperature code.
What is the Flexbus output?
640 mA at 5V DC.
All values on this page are taken from Rockwell Automation publications 1794-TD014A-EN-E (FLEX I/O Communication Adapters Specifications), 1794-IN131 (installation instructions) and 1794-SG002D-EN-P (FLEX I/O Platform Configuration Guide).
The 1794-AENTRXT is the dual-port EtherNet/IP adapter catalogued for extended temperatures. It shares the two RJ45 ports, the eight-module backplane, the 10/100 Mbps rate and the embedded switch behaviour of the 1794-AENTR; what changes is the environment it is rated for and, slightly, the power it draws.
The temperature band published for the XT part is -25...70 °C operating with 70 °C maximum surrounding air, the same as the standard dual-port adapter, and the temperature code is T4A rather than T5. Anyone who selects XT expecting a wider window than AENTR should read the table: the difference between the two dual-port parts is not the temperature range, it is the dissipation and the coating story attached to the FLEX I/O XT platform.
That distinction matters because the XT platform carries its own I/O modules, and mixing an XT adapter with standard bases is a decision about the whole slice rather than about the adapter. The job of the adapter in an XT slice is the same as in a standard one: hold the IP address, host the embedded switch, and drive eight bases over the FlexBus at 640 mA maximum.
Power numbers for this part are the lowest of the three EtherNet/IP adapters: 6.1 W dissipation at 19.2 V DC, 20.8 BTU/hr, 500 mA maximum current load with 400 mA at 24 V DC, 18 A inrush for 2 ms. In a dense cabinet the 1.0 W saved against the standard dual-port part is not the reason to choose it; heat tolerance is.
Lifecycle context is relevant here too: Rockwell names this part as the replacement for the conformally coated 1794-AENTK, which is why an AENTK bill of materials usually resolves to this catalog number rather than to the standard dual-port adapter.
Field wiring and mechanics are shared with the AENTR: 0.8 N*m (7 lb-in) terminal torque, 22...12 AWG power conductors at 75 °C minimum, 227 g in a 87 x 94 x 92 mm body, 35 x 7.5 mm DIN rail, and the 1794-NM1 kit when panel mounted.
| Attribute | 1794-AENT / AENTR / AENTRXT |
| I/O module capacity | 8 FLEX I/O modules |
| Communication rate | 10/100 Mbps, half or full duplex |
| Input voltage | 24 V DC nominal, 19.2...31.2 V DC (includes 5% AC ripple) |
| Current load at 24 V DC | 550 mA maximum (1794-AENT) / 440 mA (1794-AENTR) / 500 mA maximum (1794-AENTRXT), 400 mA at 24 V DC |
| Inrush current | 23 A for 2 ms (1794-AENT) / 18 A for 2 ms (dual-port adapters) |
| FlexBus output current | 640 mA maximum |
| Isolation | 50 V continuous, basic insulation; type tested at 1000 V AC for 60 s, power to FlexBus to EtherNet |
| Power dissipation, max | 7.3 W at 19.2 V DC (AENT) / 7.1 W (AENTR) / 6.1 W (AENTRXT) |
| Thermal dissipation | 24.9 BTU/hr at 24 V DC (AENT) / 24.2 (AENTR) / 20.8 (AENTRXT) |
| Ethernet connector | 1 x RJ45 Category 5 (AENT) / 2 x RJ45 Category 5 (AENTR and AENTRXT) |
| Temperature code | T4A for AENT and AENTRXT; T5 for AENTR |
| Terminal screw torque | 0.8 N*m (7 lb-in) |
| Wire size, power conductors | 0.33...3.31 mm2 (22...12 AWG) stranded copper, 75 °C or greater, 1.2 mm insulation maximum |
| Dimensions (H x W x D) | 87 x 94 x 69 mm (3.4 x 3.7 x 2.7 in.) AENT / 87 x 94 x 92 mm (3.4 x 3.7 x 3.6 in.) AENTR and AENTRXT |
| Weight | 180 g (6.34 oz) AENT / 227 g (8.01 oz) AENTR and AENTRXT |
| Operating temperature | 0...55 °C (32...131 °F) AENT / -25...70 °C (-13...158 °F) AENTR and AENTRXT; surrounding air max 55 °C / 70 °C |
An island that runs out of backplane power is a supply problem, not an adapter problem: the adapter passes 640 mA at 5 V to the bases and takes its own 24 V from the terminals, so the arithmetic is total module current against the supply, not against the adapter rating.