The 1794-OB16D is the diagnostic sixteen-point output module. It detects open field wiring, shorted outputs and reverse polarity of the external supply, and sets the corresponding error bit in its data table.
Each channel carries a bicolour LED and the module has one red module status indicator; both are driven from the customer's field-side power, so the indication survives a logic-side failure.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O diagnostic digital output |
Cat Num |
1794-OB16D |
Brand Name |
Rockwell |
Outputs |
16, sourcing, with diagnostics |
On-state voltage |
10V DC min, 24V DC nom, 31.2V DC max |
Output current |
500 mA per channel, 8 A per module |
On-state voltage drop |
0.5V DC max at 0.5 A |
Off-state leakage |
0.5 mA max |
Surge current |
2 A for 50 ms, repeatable every 2 s |
Short circuit protection |
Thermal shutdown, auto reset |
Open wire detection |
0.1 mA off-state leakage threshold |
External supply current |
56...78 mA |
Isolation |
50V continuous; tested 2121V DC for 1 s |
Power dissipation |
4.8 W max at 31.2V DC (16.4 BTU/hr) |
Terminal base |
1794-TB3, -TB3S, -TB3K, -TB3SK |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Open wire is found by monitoring the off-state leakage path, with a 0.1 mA threshold when external power is active and the output is inactive.
Short circuit is declared when external power is active, the output is on, and the port voltage stays below 2V; the channel then thermal-shuts down and resets automatically.
Reverse polarity of the external supply is detected above 10V, which catches a swapped field supply before it damages the load.
Open-wire detection on an off channel relies on a small leakage path, so a load with a parallel indicator lamp can mask the open circuit.
The diagnostic bits are a maintenance tool, not a safety signal; they carry no functional-safety certification as an output circuit.
Bicolour LEDs show on state and fault separately, which lets a commissioning engineer read the channel without opening the program.
Reverse polarity is reported above 10V; below that threshold the module simply behaves as if the field supply were absent.
The 8 A module limit still applies: diagnostics do not raise the output rating, only the information about it.
Error bits in the data table carry open wire, short circuit and reverse power separately, so the program can distinguish a wiring fault from a device failure.
Indication is field-side powered — bicolour per channel plus a module fault LED — which is what makes the module usable without a laptop at the panel.
<The module does not replace a fuse. Short circuit protection is thermal shutdown inside the output stage; the load circuit still needs its own protection.
500 mA per channel, 8 A per module, 0.5V DC maximum drop at 0.5 A over 10...31.2V DC, with a 2 A surge for 50 ms every 2 s.
<56...78 mA from the external supply — the highest of the 16-point output modules, because the diagnostic circuitry is continuously active.
4.8 W maximum dissipation (16.4 BTU/hr) at 31.2V DC, and 0...55 °C operating range.
1794-TB3, -TB3S, -TB3K or -TB3SK only; the diagnostic module is not listed on the TB2 base.
<2121V DC for 1 s tested at 50V continuous basic insulation, field side to system, no channel-to-channel isolation.
Field supply 10...31.2V DC with 5% ripple — the same range as the rest of the 24V DC family.
<Remote islands. An open wire on a valve 200 m from the panel is a maintenance call; a reported bit is a work order with the right terminal number.
<Commissioning. Reverse-polarity detection catches a miswired field supply on first power-up instead of at the first output command.
Not a safety function. The diagnostics report faults; they do not make the output a safety-rated circuit.
What faults does the 1794-OB16D detect?
Open field wiring, shorted output circuits and reverse polarity of the external supply, reported as bits in the data table.
How is a short circuit handled?
Thermal shutdown with automatic reset, declared when the output is on and the port voltage stays below 2V.
What is the output rating?
500 mA per channel and 8 A per module, sourcing, 10...31.2V DC.
Which terminal base does it need?
1794-TB3, 1794-TB3S, 1794-TB3K or 1794-TB3SK.
Does it provide channel indication?
Yes, one bicolour LED per channel plus a red module status indicator, both field-side powered.
What is its supply current?
56...78 mA from the 10...31.2V DC external supply, with 4.8 W maximum dissipation.
| Catalog number | Outputs | Per-channel current | Module ceiling | Terminal base |
|---|---|---|---|---|
| 1794-OB8 | 8, current, sourcing | 500 mA per channel | 4 A per module | 1794-TB2, -TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OV16 | 16, current, sinking | 500 mA per channel | 8 A per module | 1794-TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OV16P | 16, current, sinking, protected | 500 mA per channel | 8 A per module | 1794-TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OB16 | 16, current, sourcing | 500 mA per channel | 8 A per module | 1794-TB2, -TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OB16D | 16, sourcing, with diagnostics | 500 mA per channel | 8 A per module | 1794-TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OV32 | 32, current, sinking | 500 mA per channel | 8 A per module | 1794-TB32, 1794-TB32S |
| 1794-OB32P | 32, sourcing, protected, two groups of 16 | 500 mA per channel | Not published | 1794-TB32, 1794-TB32S |
A FLEX I/O island usually settles between this module and a neighbour in the same table: the point count decides the base width, and the per-channel current decides whether the load can stay on one supply.
For 1794-OB16D the published row reads 16, sourcing, with diagnostics, at 500 mA per channel with a module ceiling of 8 A per module; the supply window is 10V DC min, 24V DC nom, 31.2V DC max, and it mounts on 1794-TB3, -TB3S, -TB3K, -TB3SK.
The module ceiling is what stops a sixteen-point module from behaving like sixteen independent channels at the per-channel rating: the sum is capped, so a panel that loads every channel near the top has to count the total before it counts the points.
Off-state leakage is the number that decides whether a two-wire sensor sharing the field supply reads an output as off: 0.5 mA max on this module.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.