Product Details:
Payment & Shipping Terms:
|
The 1794-TB3GT is a grounded cage clamp base whose I/O terminals are rated 2 A while its V/COM terminals stay at 10 A.
That split rating is the whole point: power distribution can still carry 10 A, but a point-level circuit is limited to what a small field device or a signal wiring run should see.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O grounded terminal base with reduced I/O current |
Cat Num |
1794-TB3GT |
Brand Name |
Rockwell |
Termination |
Cage clamp, grounded |
Current capacity |
V/COM terminals 10 A; I/O terminals 2 A |
Wire size |
0.34...3.3 mm2 (22...12 AWG), 75 deg C or greater |
Dimensions |
94 x 94 x 69 mm |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
V/COM terminals 10 A, I/O terminals 2 A — the one specification that separates this base from the rest of the grounded family.
Cage clamp termination, grounded construction, 94 x 94 x 69 mm.
22...12 AWG wire window, the same as the other grounded bases.
-20...70 deg C operating range of the grounded family.
Signal-level wiring gets a 2 A ceiling sorted by termination rather than by a fuse downstream.
Distribution stays at 10 A on V and COM, so a group supply is not restricted.
Do not use it for contactor or lamp loads above 2 A per point; that belongs on a standard base.
Check the module's per-point rating too; the base does not raise the module limit.
Analog and specialty modules where per-point current is small and grounding matters.
Panels standardising on cage clamp with a grounded pattern.
Not for 3-wire digital inputs; 2 common and 2 +V do not cover 16 points.
Not a substitute for the 1794-TB3T; no CJC sets here.
35 x 7.5 mm DIN rail with 25 mm air space around the system.
Zinc-plated, yellow-chromated steel rail for the chassis ground path.
1794-NM1 panel kit and 1492-EA35 rail locks as needed.
One end cap per system.
1794-TB3G: 10 A across the board, grounded screw clamp.
1794-TB3GT: 10 A V/COM but 2 A on I/O terminals, grounded cage clamp.
1794-TB3GS: grounded spring clamp, 10 A.
Choose the GT when per-point current must stay low by construction, not when a standard base is enough.
What is the special rating on the 1794-TB3GT?
The I/O terminals are rated 2 A while the V/COM terminals remain 10 A.
Is it screw or spring terminated?
Cage clamp, in the grounded construction.
What wire size does it accept?
0.34...3.3 mm2 (22...12 AWG).
Can it drive a contactor?
Not above 2 A per I/O point; that load belongs on a standard base.
Does it carry CJC sets?
No; that is the 1794-TB3T.
What is the operating temperature?
-20...70 deg C.
1794-TB3GT is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is Cage clamp, grounded with 10 A on V and COM terminals, 2 A on I/O terminals.
| Attribute | Value |
| Catalog number | 1794-TB3GT |
| Termination type | Cage clamp, grounded |
| Connections | 10 A on V and COM terminals, 2 A on I/O terminals |
| Current capacity, maximum | module dependent |
| Wiring category | module dependent |
| Field voltage | Per module |
| Operating temperature | -20...+70 C |
| Purpose in the range | A grounded cage clamp base whose I/O terminals carry 2 A while the voltage and common terminals carry 10 A. |
The conductor range for this base is 0.34 to 3.3 mm2 (22 to 12 AWG) solid or stranded copper rated 75 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of module dependent across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.
Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.
Conformal coated variants carry a K suffix and exist because the same base can be asked to survive washdown, condensate, or corrosive atmosphere. Ordering the uncoated base and treating it in the field is not equivalent and does not carry the same published rating.
One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.
Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.
On the 32 point bases the common and voltage terminals are grouped in eight pairs rather than eighteen, which is why the 32 point digital modules can mix sinking and sourcing groups in one slice and why the terminal numbering on the drawing does not follow the 16 point pattern.
Any FLEX I/O position is a pair on the purchase order: one base, one module. Stocking modules without bases, or bases without the matching modules, produces a slice that cannot be commissioned, and the two part numbers are never interchangeable across the 8, 16 and 32 point families.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
Related models, options and spare parts for this range are listed in the Allen-Bradley Flex I/O 1794 modules category.