Product Details:
Payment & Shipping Terms:
|
The 1794-TB3GSK combines the two features that are hardest to retrofit: spring termination and conformal coating, on the grounded analog base.
36 I/O terminals with 10 chassis ground connections, for an analog island that has to keep its shield path while sitting in a condensing cabinet.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O grounded terminal base for analog modules |
Cat Num |
1794-TB3GSK |
Brand Name |
Rockwell |
Termination |
Grounded spring clamp, 36 I/O, 2 common, 2 +V, 10 chassis ground |
Wire size |
0.34...3.3 mm2 (22...12 AWG), 75 deg C or greater |
Current capacity |
10 A maximum |
Wiring category |
2 |
Dimensions |
94 x 94 x 69 mm |
Operating temperature |
-20...70 deg C |
Coating |
Conformal |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
36 I/O, 2 common, 2 +V and 10 chassis ground — the grounded pattern, spring terminated.
10 A current capacity and the 22...12 AWG wire window.
-20...70 deg C with the coating applied to the assembly.
94 x 94 x 69 mm — identical footprint to the uncoated base, so a swap needs no rail change.
The K suffix is the coated catalog in the guide's conventions, intended to pair with -XT modules.
Coating does not remove the grounding requirement; the 10 chassis terminals still need a low-impedance path.
Zinc-plated, yellow-chromated steel rail for the chassis connection through the rail.
Star-washer screws on the mounting holes when the base is panel mounted without rail.
Outdoor or unheated analog cabinets where condensation is the failure mode.
High-vibration locations that favour spring over screw termination.
Not a discrete base; 2 common and 2 +V are for analog channel patterns.
Not a temperature base; thermocouple CJC sets are on the 1794-TB3TSK.
35 x 7.5 mm DIN rail with 25 mm air space.
1794-NM1 panel kit where no rail exists.
1492-EA35 rail locks for vertical mounting or vibration.
One end cap per system, bases plugging together for the backplane.
Coated analog islands with -XT analog modules.
Cold-start conditions where a coated base avoids a cabinet heater.
Not a general purpose base; the 1794-TB3GS is cheaper indoors.
Not for 32 points; the 1794-TB32SK carries 32 I/O in the same size.
What does the K suffix add?
Conformal coating on the grounded spring base.
How many grounding terminals does it have?
10 chassis ground terminals.
Is it spring or screw terminated?
Spring clamp.
What is the operating temperature?
-20...70 deg C.
What wire size does it accept?
0.34...3.3 mm2 (22...12 AWG).
Which modules pair with it?
The -XT family; the coating on the base is only half of the protection.
1794-TB3GSK is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is Grounded spring clamp with 36 I/O, 2 common, 2 +V, 10 chassis ground.
| Attribute | Value |
| Catalog number | 1794-TB3GSK |
| Termination type | Grounded spring clamp |
| Connections | 36 I/O, 2 common, 2 +V, 10 chassis ground |
| Current capacity, maximum | module dependent |
| Wiring category | 2 |
| Field voltage | Per module |
| Operating temperature | -20...+70 C |
| Purpose in the range | The conformal coated version of the 1794-TB3GS. |
The conductor range for this base is 0.34 to 3.3 mm2 (22 to 12 AWG) solid or stranded copper rated 75 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of module dependent across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.
Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.
The wiring category matters as much as the gauge: category 2 bases are the general field wiring class, while grounded bases in the 1794-TB3G family carry 10 chassis ground terminals for analog and temperature modules where a separate signal common is needed.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.
Conformal coating on a K suffix base is applied to the assembled board and not to the terminals, so the coating protects the electronics against condensation while the field terminals remain serviceable. That is the point of ordering the coated base instead of sealing the whole enclosure.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.