Product Details:
Payment & Shipping Terms:
|
The 1769-IM12 (also written 1769IM12) is the 200/240V AC input of the Compact I/O 1769 range: twelve points on one internally connected common, reading 230V control circuits directly — European and Asian panels where the control voltage is phase-to-neutral mains rather than 120V.
Twelve points, not sixteen, is the detail that catches people: the 1769-IM12 physically has sixteen terminal positions but four are marked NC and must not be used as a connection. A panel wired on the assumption of a full sixteen gets four dead terminals.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-IM12 |
Brand Name |
Rockwell |
Inputs |
12 (12 points per group, commons connected internally) |
Voltage category |
200/240V AC |
Operating voltage range |
159…265V AC, 47…63 Hz |
Input delay, on / off |
20 ms / 20 ms |
Current draw @ 5.1V |
100 mA |
Heat dissipation, max |
3.65 W |
Off-state voltage / current |
40V AC max / 2.5 mA max |
On-state voltage / current |
159V AC min / 5 mA @ 74V AC min, 12 mA @ 120V AC max |
Inrush current, max |
250 mA |
Input impedance, max |
27 kΩ @ 50 Hz; 23 kΩ @ 60 Hz |
Isolation |
1836V AC 1 s or 2596V DC 1 s, point to bus; 132V AC working voltage |
Slot width / weight |
1 slot / 300 g |
Power supply distance |
8 modules |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
How many inputs does 1769-IM12 have?
Twelve live points on one internally connected common. The module has sixteen terminal positions but four are marked NC and must not be used as connections.
What AC voltage range does 1769-IM12 accept?
159…265V AC at 47…63 Hz, rated 200/240V AC, with a fixed 20 ms on and 20 ms off delay.
What does 1769-IM12 draw from the backplane?
100 mA at 5.1V with 3.65 W maximum heat dissipation, one slot, 300 g, eight-module power-supply distance rating.
Why are four terminals marked NC on 1769-IM12?
The module is built on a sixteen-terminal block but only twelve channels are fitted. The specification states the NC terminals must not be used as a connection.
What is the off-state voltage of 1769-IM12?
40V AC, with 2.5 mA maximum off-state current — twice the voltage limit of the 120V input modules, matched to the 230V line.
Can 1769-IM12 read a 120V AC signal?
No. The minimum on-state voltage is 159V AC, so a 120V circuit never reaches the guaranteed on-state level.