|
Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 22A-A1P4N113, a PowerFlex 4 drive: 240 V AC single-phase, 1.4 A, 0.2 kW (0.25 HP), enclosure N, frame A. The decode and every figure below are taken from the drive family's published selection, terminal and installation tables.
| Field | Value |
| Catalog number | 22A-A1P4N113 |
| Family (characters 1-3) | 22A - PowerFlex 4 adjustable frequency AC drive |
| Voltage class (character 5) | A - 240 V AC single-phase |
| Input band as published | 180-265 V AC (200-240 V +-10%) |
| Output as published | 0-230 V three-phase |
| Rating code (characters 6-8) | 1P4 - 1.4 A, 0.2 kW (0.25 HP) |
| Frame size | A |
| Enclosure (character 9) | N - IP20, NEMA/UL Type Open (panel mount) |
| Interface (character 10) | 1 - this position is not translated into a module by the selection table |
| Emission class (character 11) | 1 - integral S-type EMC filter |
| Drive type (character 12) | 3 - the single-phase no-brake form, which the table lists at the lower of its two currents |
The 240 V single-phase class is the answer to a machine that has to run without a three-phase supply. Its output is a three-phase waveform the motor cannot distinguish from a three-phase feed, and the class spans 0.2 to 2.2 kW across 1.4 A to 9.6 A.
Single-phase input changes the wiring, not the motor: the rectifier draws from two conductors, so the supply cable and the upstream protection are sized single-phase while the motor cable stays a three-phase run. That asymmetry is where most installation mistakes on this class begin.
The drive is rated 0 to 240 Hz output, 97.5 percent efficiency typical, and the published overvoltage trip sits at 405 V DC bus for 120 V and 240 V input (equivalent to 150 V and 290 V AC incoming) and 810 V DC for 480 V input (equivalent to 575 V AC). A site with a soft supply trips on the undervoltage side first: 210 V DC bus for 120 V and 240 V input, 390 V DC for 480 V input.
The enclosure character reads N, which the family defines as IP20 and NEMA/UL Type Open: a panel-mount drive intended to sit inside an enclosure that provides the protection. Its rating describes what the drive survives, not what the installation survives.
The family publishes the ambient window with that rating: -10 to 40 degrees C for the IP20/Open drive in Mounting Option A, and up to 50 degrees C only in Mounting Option B, where the drives are spaced 120 mm above and below and 25 mm at the sides. A cabinet that runs hotter than the window does not make the drive hotter-rated; it makes the rating untrue.
The emission character reads 1. At 1 the string carries the integral S-type EMC filter the family lists for this rating, at 0 it does not, and the EMC obligation then moves to the installation. The two filter families are bounded by cable length rather than by drive current: an S-type filter is published for 10 m of motor cable in a Class A environment and 1 m in Class B, an L-type filter for 100 m in Class A and 5 m in Class B. On the 480 V ratings the external filters are 22-RF5P7-AS and 22-RF5P7-AL on frame A, 22-RF012-BS and 22-RF012-BL on frame B.
On frame A the published power terminal block accepts 3.3 mm2 (12 AWG) maximum and 0.8 mm2 (18 AWG) minimum at 1.7-2.2 N-m (16-19 lb-in), and the control block common to both frames accepts 1.3 mm2 (16 AWG) maximum and 0.13 mm2 (26 AWG) minimum at 0.5-0.8 N-m. The frame measures 80 x 185 x 136 mm and ships at 1.4 kg (3.1 lb).
Two mechanical facts belong with the frame. The IP20/Open drive needs 120 mm of clear space above and below the heatsink and no clearance between adjacent drives. The IP30/NEMA 1/UL Type 1 rating is not a factory variant but a field kit, 22-JBAA for frame A and 22-JBAB for frame B, which adds the conduit box and top panel and moves the installation to Mounting Option B.
Dynamic braking here is a resistor selection rather than a drive setting. The family publishes a 60 ohm minimum resistance, with AK-R2-091P500 listed for the single-phase ratings, rated for 5 percent duty cycle, with a DC fuse on the DC+/BR+ and DC- terminals when those terminals are used: PV-10A10F on the resistor branch and a 1000GH-016 or 1000GH-025 DC fuse depending on the rating. Parameter A082 [DB Resistor Sel] must be set to 1 "Normal RA Res" for the drive to calculate resistor overload protection, and at that setting the drive protects the resistor but not a brake IGBT failure.
Where the supply needs a line reactor, the family lists Bulletin 1321 three-phase reactors by drive rating at 3 percent impedance, open style, for example 1321-3R2-B at 0.4 kW on 480 V and 1321-3R4-C at 0.75 kW, with NEMA Type 1 and 5 percent impedance types available separately. The reactor follows the drive rating, not the motor.
The published motor protection is I2t overload at 150 percent for 60 seconds and 200 percent for 3 seconds, which the family states provides Class 10 protection, with a 200 percent hardware current limit and a 300 percent instantaneous fault limit. Upstream protection is not in the string: the manual recommends UL Class J, CC, T or BS88 fuses, or Bulletin 140M/140MT self-protected combination controllers that may be used ahead of the drive without fuses, and it publishes a minimum enclosure volume of 1655 cubic inches for that arrangement.
The family adds one harmonic note that belongs with the supply rather than with the drive: the 0.75 kW (1 HP) 240 V single-phase and three-phase drives and the 0.37 kW (0.5 HP) 240 V single-phase drive are stated to be suitable for a private low voltage power network, and installation on a public low voltage network may require additional external harmonic mitigation. A drive can be compliant on the bench and questioned on site over that one sentence.
The string settles voltage class, output current, enclosure, filter and drive type. It does not settle the motor, the cable, the upstream protection or the duty, and on a drive of this size those four decide whether the installation works. Two drives in this family can share a rating and differ in enclosure or filter, so a spare order quoting a rounded-off number can produce a unit that runs the motor and does not fit the panel.
Two characters are named rather than translated. The interface position reads 1, and the replacement-plate and some panel strings of this family carry 2 there while the rest carry 1; the selection table does not turn that character into a module, so this page does not either. Commissioning starts with the motor nameplate current, which the drive must be limited to, and the acceleration the machine actually needs.
Related catalog numbers in this family: 22A-A1P5N104.
No lifecycle statement and no price is implied. The rating rows, voltage bands, enclosure definitions, terminal and frame data, filter cable limits, braking resistor and reactor selections and the protection figures are quoted from the PowerFlex 4 family's published selection and installation tables.