Product Details:
Payment & Shipping Terms:
|
The 1734-TOP3S is a 12-terminal POINT I/O wiring base with a spring-clamp removable terminal block: the base mounts on the DIN rail, the I/O module snaps into it, and integrated one-piece block carries the field wiring.
Twelve spring-clamp terminals in one piece - the highest terminal count with the lowest assembly time, and the same 1492-N80 release tool as 1734-TOPS.
| 1734-TB | 8 terminal wiring base with removable screw-clamp RTB | IN STOCK |
| 1734-TB3 | 12 terminal wiring base with removable screw-clamp RTB3 | IN STOCK |
| 1734-TB3S | 12 terminal wiring base with removable spring-clamp RTB3S | IN STOCK |
| 1734-TOP | 8 terminal one-piece base, screw-clamp | IN STOCK |
| 1734-TOPS | 8 terminal one-piece base, spring-clamp | IN STOCK |
| 1734-TOP3 | 12 terminal one-piece base, screw-clamp | IN STOCK |
| 1734-TOP3S | 12 terminal one-piece base, spring-clamp | IN STOCK |
| 1734-CTM | Common terminal module, 2 A per point, 4 A per module | IN STOCK |
Number of terminations |
12 |
Termination type |
spring-clamp |
Wiring block |
integrated one-piece block |
Field power bus supply voltage |
28.8V DC, 120/240V AC |
Field power bus supply current, max |
10 A |
Signal terminal voltage, max |
28.8V DC, 120/240V AC |
Signal terminal current, max |
2 A |
Wire size |
0.25...2.5 mm2 (22...14 AWG), 75 deg C or greater, 1.2 mm insulation max |
Dimensions, HxWxD |
49 x 12 x 188 mm |
Weight, approx |
66.8 g |
Enclosure type rating |
None (open-style) |
Temperature, operating |
Dependent on the installed module, -20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN028 (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
0...3 channels, 4/5 common, 6/7 supply, 8/9 common, 10/11 supply. Four channels with no external jumpers, and no removable block to re-key when a slice is replaced.
A 3 mm blade at about 97 degrees releases each clamp; 66.8 g total. Spring-clamp saves 12.4 g over the screw version and removes the torque procedure, which is the reason this is the base most often specified for cabinets assembled by a contract house.
TB3 97.5 g two-piece screw, TB3S 87 g two-piece spring, TOP3 79.2 g one-piece screw, TOP3S 66.8 g one-piece spring. All four carry 10 A field bus, 2 A signal terminals and 250V-class isolation in the case of the two-piece pair. Pick by service model, not by weight.
Field power bus 10 A and signal terminals 2 A, at 28.8V DC or 120/240V AC. The 10 A figure is the bus capacity that the 1734-EP24DC and 1734-FPD modules are built around; the 2 A is per signal terminal, which is why an output slice rated 2 A per point uses the base at its limit rather than in the middle of its range. Isolation and voltage segregation come from the module that sits in the base, not from the base itself - the base is a passive wiring carrier.
Rockwell's removal sequence is explicit: remove the module in the base, then the module in the base to the right, then the RTB, then release the orange base locking screw and lift straight up. The base to the right has to come out because the interlocking side pieces and the POINTBus contacts overlap. Pulling a base with power applied interrupts the backplane and can cause unintended machine motion.
What tool is needed for 1734-TOP3S?
A 3 mm bladed screwdriver, catalog number 1492-N80, inserted at roughly 97 degrees to release the clamp.
How many terminals and what pinout?
Twelve: 0...3 channels, 4/5 and 8/9 common, 6/7 and 10/11 field supply.
How does it compare with 1734-TB3S?
Same 12 terminals and spring-clamp, but one-piece at 66.8 g and 49 mm height versus the two-piece TB3S at 87 g and 65 mm.
What are the rail dimensions?
49 x 12 x 188 mm.
What current can it carry?
10 A on the field power bus and 2 A per signal terminal.
1734-TOP3S is a POINT I/O terminal base assembly: a DIN-rail mounting base with a 12-terminal spring-clamp RTB, tall base profile. The base is ordered separately from the I/O module because the base and the RTB are the parts that carry the wiring, and the module is the part that is replaced on failure.
| Attribute | Value |
| Catalog number | 1734-TOP3S |
| Assembly type | 12-terminal spring-clamp RTB, tall base profile |
| Replacement RTB | 1734-RTB3S |
| Dimensions, H x W x D | 167.6 x 13.8 x 79.1 mm (6.60 x 0.54 x 3.11 in.) |
| Weight | 79.10 g (2.79 oz) |
| RTB function | All field terminations, removable without disturbing wiring |
| Terminal numbering | Marked on the bottom of the RTB |
| Related base | 1734-TBCJC adds cold junction compensation for 1734-IT2I |
Terminal count decides the base, not the module width: the eight-terminal bases suit modules with one termination per channel, and the twelve-terminal bases are needed where the module presents commons or shield returns in addition to the channel terminals. A two-point analog module needs a shield ground terminal point, which is why the analog side of the family runs on the wider bases.
The terminal base assembly is the part that makes POINT I/O modular: the base mounts on the DIN rail, the removable terminal block (RTB) carries every field termination, and the I/O module plugs onto both. The RTB is ordered with the base as one unit, and a spare RTB is a field-replaceable part rather than a whole new base.
Each terminal point is numbered on the bottom of the RTB, which is why a wiring fault can be traced from the drawing to a numbered terminal instead of to a wire colour. Once the RTB is wired, the block separates from the base and the module without disturbing the terminations, so a module swap does not require re-terminating a single field wire.
Every POINT I/O module mounts in a terminal base that is ordered separately, and the number of field terminals on the base has to match the module: eight terminals for single-point-per-channel digital modules, twelve where the module needs a common or a shield return per channel group.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
The system is rated for panel work rather than for a lab bench: modules plug onto bases that are already wired, the RTB stays on the wiring while the electronics come off, and the same base family accepts the next module of the same width. That is the reason a spare part for POINT I/O is usually an RTB or a base rather than a module, and why a maintenance stock built only from modules is incomplete.
The Allen-Bradley POINT I/O 1734 modules category groups the other catalog numbers, options and spare parts in the same range.