Allen Bradley PLC 1794-IT8 / 1794IT8 supplier Allen Bradley PLC 1794-IT8 / 1794IT8 supplier Allen Bradley PLC 1794-IT8 / 1794IT8 supplier Allen Bradley PLC 1794-IT8 / 1794IT8 supplier Allen Bradley PLC 1794-IT8 / 1794IT8 supplier Allen Bradley PLC 1794-IT8 / 1794IT8 supplier Allen Bradley PLC 1794-IT8 / 1794IT8 supplier

Large Image :  Allen Bradley PLC 1794-IT8 / 1794IT8

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1794-IT8 / 1794IT8

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $671.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1794-IT8 technical data PDF download FLEX I/O 1794-IT8 / 1794IT8 Thermocouple/mV Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1794-IT8 is the cost-effective thermocouple card: eight channels over +/-76.5 mV, 16-bit resolution at 2.384 uV, and 0.025% of full scale accuracy with the filter selected.

It is chosen where the update rate does not matter and the temperature does — kiln, furnace and heat-treat readings where a 325 ms channel scan is invisible to the process.

1794-IE8 8-channel analog input module IN STOCK
1794-IE8XT 8-channel analog input module, extended temperature IN STOCK
1794-IE8H 8-channel HART analog input module IN STOCK
1794-IE12 12-channel analog input module IN STOCK
1794-IE12K 12-channel analog input module, conformal coated IN STOCK
1794-IF4I 4-channel isolated analog input module IN STOCK
1794-IF4IXT 4-channel isolated analog input, extended temperature IN STOCK
1794-IF4ICFXT 4-channel isolated analog input, conformal coated IN STOCK
1794-IF8IH 8-channel HART isolated analog input module IN STOCK
1794-IR8 8-channel RTD input module IN STOCK
1794-IRT8 8-channel thermocouple/RTD input module IN STOCK
1794-IRT8XT 8-channel thermocouple/RTD input, extended temperature IN STOCK
1794-IT8 8-channel thermocouple/mV input module IN STOCK
1794-IE8XOE4 8-input, 4-output analog combination module IN STOCK
1794-IE4XOE2 4-input, 2-output analog combination module IN STOCK
1794-IF2XOF2I 2-input, 2-output isolated analog combination module IN STOCK
1794-OE4 4-channel analog output module IN STOCK
1794-OE12 12-channel analog output module IN STOCK

Product Specifications 1794-IT8 (PDF)
 Application
 FLEX I/O thermocouple and mV input, 1794 terminal base
 Cat Num
 1794-IT8
 Brand Name
 Rockwell
 Channels
 8, thermocouple or mV
 Input range
 +/-76.5 mV DC
 Resolution
 16 bits, 2.384 uV typical
 Throughput
 325 ms per channel, programmable to 28 ms
 Accuracy
 0.025% of full scale with filter, 0.05% without
 Common mode rejection
 -115 dB at 60 Hz, -100 dB at 50 Hz
 Common mode range
 +/-10V
 Overvoltage
 35V DC, 25V AC continuous; 250V peak transient
 External supply current
 150 mA at 24V DC
 Operating temperature
 -20...55 deg C

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1794-IT8 original product photograph, wide view 1794-IT8 original product photograph, wide view 1794-IT8 original product photograph, wide view

Millivolt measurement

+/-76.5 mV DC input span covers every standard thermocouple type with margin, and 16-bit resolution gives 2.384 uV typical per count.

0.025% of full scale with the filterand 0.05% without it — the filter is a configuration choice that changes the published accuracy, not just the noise.

Common mode rejection of -115 dB at 60 Hz and -100 dB at 50 Hz is the strongest in the FLEX I/O temperature line.

Input offset drift of +6 uV/deg C maximum and gain drift of 10 ppm/deg C are the two terms that dominate a cold-cabinet error budget.

Overall drift of 50 ppm/deg C of span is the published combined figure.

Throughput

325 ms per channel is 2.6 s for a full eight-channel scan, programmable down to 28 ms per channel.

Settling is to 100% of final value at the system throughput rate,so there is no separate settling spec to add.

Channel bandwidth of 0 to 2.62 Hz rejects everything faster than a process change, which is why the accuracy is high and the speed is not.

The card is not for a fast loop;a 2.6 s scan is the right answer for a furnace and the wrong one for an extrusion zone.

Thermocouple support

Ten types:B, C, E, J, K, N, R, S, T and TXK/SK(L), each with the published temperature range.

Grounded or ungrounded thermocouples are both accepted, with the +/-10V common mode range covering a grounded junction.

Cold junction compensation with the 1794-CJC2 kit,two compensators supplied with the module and additional ones orderable separately.

Cold junction range 0...70 deg C is the published figure, so a cabinet hotter than that is outside the compensation specification.

Open input detection reads upscale — an out-of-range value rather than a plausible temperature.

Electrical and mechanical

35V DC or 25V AC continuous and 250V peak transient overvoltage capability protects the input against a miswired supply or a surge.

150 mA at 24V DC is the module consumption, the highest of the three temperature cards because of the eight-channel multiplexer and reference.

-20...55 deg C operating range, 46 x 94 x 53 mm body, 94 x 94 x 69 mm installed on the base.

RFI immunity is under 1% of range error at 10 V/m from 27 to 1000 MHz.

Where it fits

Slow thermal processes — kilns, furnaces, heat-treat, annealing — where a 2.6 s scan is irrelevant.

Cost-sensitive temperature panels that still need better than 0.1% accuracy.

Not for fast temperature or for mixed RTD work; the 1794-IRT8 covers both with 8–10 ms throughput at 14 bits.

Not for direct resistance measurement.The IT8 reads millivolts; RTD elements need excitation, which the IR8 and IRT8 provide.

FAQ — 1794-IT8

What input range has the 1794-IT8?

+/-76.5 mV DC, for thermocouple and millivolt sources.

What resolution and accuracy does it offer?

16 bits at 2.384 uV typical, with 0.025% of full scale accuracy when the filter is selected.

How fast does it scan?

325 ms per channel, programmable to 28 ms, or 2.6 s for eight channels.

Which thermocouple types are supported?

B, C, E, J, K, N, R, S, T and TXK/SK(L).

Does it need a cold junction compensator?

Yes, the 1794-CJC2; two are supplied with the module.

Can it read an RTD directly?

No. RTDs need excitation current, which the 1794-IR8 and 1794-IRT8 provide.


Data sources. Technical values on this page come from Rockwell publication 1794-SG002 (FLEX I/O Selection Guide, Table 19 and Table 28) and 1794-IN093. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

The thermocouple module against the RTD module beside it

This page is the thermocouple and millivolt module, and the RTD module beside it on this site covers the same eight channels from a different front end. The table sets the two against each other, because the choice between them is made on resolution, throughput and common mode rejection rather than on channel count.

Row1794-IT8, this page1794-IRT8 on this site
ApplicationFLEX I/O thermocouple and mV inputFLEX I/O thermocouple, RTD and mV input
Channels8, thermocouple or mV8, configurable per channel
Input ranges+/-76.5 mV DC-40...+100 mV DC thermocouple, 0...325 mV DC RTD, 0...500 Ohm
Resolution16 bits, 2.384 uV typical14 bits
Throughput325 ms per channel, programmable to 28 ms7.4 ms mV, 8.0...10.8 ms RTD, 8.0...8.8 ms thermocouple
Accuracy0.025% of full scale with filter, 0.05% without0.05% of full range in mV mode with filtering
Common mode rejection-115 dB at 60 Hz, -100 dB at 50 Hz-80 dB at 5 V peak to peak, 50...60 Hz
Common mode range+/-10 VSeries A +/-4 V, Series B +/-15 V
Excitation currentnot printed630 uA
External supply150 mA at 24 V DC85 mA at 24 V DC
Operating temperature-20...55 deg C-20...55 deg C, XT -20...70 deg C

Resolution and speed trade against each other across these two records and the numbers are not close: 16 bits with 2.384 uV at 325 ms per channel on this page, against 14 bits at 7.4 ms in mV mode on the RTD module. A furnace survey that needs 4 uV resolution waits 44 times longer for a reading, and the programmable 28 ms rate still leaves it four times slower. The common mode rejection is the other row: -115 dB at 60 Hz here against -80 dB there, which is what decides whether a module can sit beside a drive.

The XT row exists on the RTD record and not on this one. 1794-IRT8 is published to 70 °C in the XT form while this module stops at 55 °C, so an extended temperature panel has one thermal input module to choose from and it is not this one.

What this record does not settle: the thermocouple types accepted, the cold junction compensation method, the open thermocouple detection, the input resistance, the isolation between input and backplane, the terminal base part numbers, and any lifecycle field.

The module is a precision front end and not a fast one: 16 bits and 2.384 uV on a 325 ms default conversion, programmable to 28 ms, which suits a furnace or a kiln scan and not a control loop. The -115 dB rejection at 60 Hz is why it can live in the same enclosure as a drive, and the 150 mA supply draw is why it cannot live there many times over.

Source: the printed attribute rows of 1794-IT8 on this page and of 1794-IRT8 on this site, quoted row by row, including resolution, throughput, rejection, supply and temperature rows.