The 1734-IT2I takes two thermocouples, each individually isolated, and linearises nine standard types - B, C, E, J, K, N, R, S and T - with cold junction compensation built into the 1734-TBCJC base it mounts on.
Individually isolated inputs are the reason to buy it: two thermocouples bonded to different pieces of earthed metal no longer fight each other through a common ground, which is the failure mode that makes non-isolated thermocouple cards read nonsense on real machines.
| 1734-IR2 | 2-channel RTD input, 0...600 ohm, 16 bits | IN STOCK |
| 1734-IR2E | 2-channel high resolution RTD input, 0.006 deg C per count | IN STOCK |
| 1734-IT2I | 2-channel isolated thermocouple input, types B/C/E/J/K/N/R/S/T | IN STOCK |
Number of inputs |
2 differential, individually isolated |
Resolution |
15 bits plus sign |
Thermocouple types |
B, C, E, J, K, N, R, S, T |
Type K range and resolution |
-270...1372 °C, 13 counts/°C |
Type J range and resolution |
-210...1200 °C, 21 counts/°C |
Type B range and resolution |
30...1820 °C, 3 counts/°C |
Cold junction compensation range |
0...70 °C |
Input impedance |
100 kohm |
Absolute accuracy |
0.1% full scale @ 25 °C |
Input update rate |
20 ms @ 50 Hz notch, 17 ms @ 60 Hz (default), 10 ms @ 100 Hz, 8 ms @ 120 Hz, 5 ms @ 200 Hz, 4 ms @ 240 Hz, 3 ms @ 300 Hz, 3 ms @ 400 Hz, 2 ms @ 480 Hz (per module) |
Step response |
60 ms @ 50 Hz, 50 ms @ 60 Hz, 30 ms @ 100 Hz, 25 ms @ 120 Hz, 15 ms @ 200 Hz, 13 ms @ 240 Hz, 10 ms @ 300 Hz, 8 ms @ 400 Hz, 6 ms @ 480 Hz (per channel) |
Common mode rejection |
120 dB |
Normal mode rejection |
-60 dB |
Terminal base |
1734-TBCJC cold junction compensation base |
Keyswitch position |
6 |
POINTBus current, max |
175 mA @ 5V DC |
Power dissipation, max |
1.0 W |
Isolation voltage |
50V continuous, Basic insulation, type tested 1600V AC for 60 s |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Weight, approx |
36 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN011-EN-E (module specifications) and 1734-UM004 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Each channel is separately isolated from the other and from the system, tested at 1600V AC for 60 s at 50V continuous basic rating. On a furnace with two earthed thermowells, that isolation is what stops a ground loop between the wells from appearing as a temperature offset. A differential input without isolation would still see the loop.
Type K spans -270 to 1372 deg C at 13 counts per degree, type J -210 to 1200 at 21 counts, type T -270 to 400 at 15, and type B only 3 counts per degree across 30 to 1820 deg C. Choosing type B for a 1500 deg C furnace therefore gives a coarse reading by design; if the process needs 1 deg C resolution up there, the module is the limitation, not the sensor.
The 1734-TBCJC base carries the cold junction sensor, and the specification only guarantees compensation from 0 to 70 deg C. A panel whose internal temperature sits below freezing, or above 70 deg C beside a heat source, is outside that window and the reading drifts with panel temperature. It is a base requirement, not an option: a plain TB base cannot be substituted.
20 ms at a 50 Hz notch, 17 ms at 60 Hz, down to 2 ms at 480 Hz - but the per-channel step response is 60 ms at 50 Hz. The difference matters: a thermocouple in a thermowell already has a time constant measured in seconds, so the module is never the bottleneck, and the notch setting should be chosen for mains rejection rather than for speed.
A 100 kohm input impedance is high enough that thermocouple lead resistance barely affects the reading, but it also means an open thermocouple produces a large, believable-looking number rather than an obvious fault. Use the channel status bits, not the value, to detect a broken sensor; a drifting reading that climbs steadily is the classic open-circuit signature.
175 mA at 5V DC, 1.0 W dissipation, 3.3 BTU/hr, 36 g, 56.6 x 12.1 x 77.5 mm, no external supply. Two thermocouple channels per 175 mA is a favourable ratio against the 220 mA of an RTD module, which is what lets a multi-zone furnace run 12 zones off one adapter inside the 1 A POINTBus limit.
Which thermocouple types does 1734-IT2I support?
B, C, E, J, K, N, R, S and T, with 15 bits plus sign resolution and 0.1% of full scale accuracy at 25 deg C.
Are the two inputs isolated from each other?
Yes - two differential, individually isolated inputs, 50V continuous basic insulation, type tested at 1600V AC for 60 s.
Which base does it require?
1734-TBCJC, which contains the cold junction compensation. A plain TB, TBS, TOP or TOPS base cannot be substituted.
What is the cold junction compensation range?
0 to 70 deg C. Panel temperatures outside that window are not compensated.
How fast does the module update?
17 ms per module at a 60 Hz notch, 20 ms at 50 Hz, down to 2 ms at 480 Hz; step response per channel is 50 ms at 60 Hz.
The table reproduces the sibling list this page publishes, with each catalog number put in the class of module it is; the paragraph after it places this part in that ladder, and the arithmetic at the end uses this page's own POINTBus figure against the 1.0 A budget the adapters print.
| Catalog number | What the published line says | Class of module |
| 1734-IR2 | 2-channel RTD input, 0...600 ohm, 16 bits | Temperature input |
| 1734-IR2E | 2-channel high resolution RTD input, 0.006 deg C per count | Temperature input |
| 1734-IT2I | 2-channel isolated thermocouple input, types B/C/E/J/K/N/R/S/T | Temperature input |
1734-IT2I is the thermocouple member and the only isolated one in the trio: two differential inputs, each individually isolated, 15 bits plus sign. Nine thermocouple types are printed, and the counts per degree differ by a factor of seven across them - 13 for type K against 3 for type B.
At the 175 mA this module prints, the 1.0 A POINTBus carries 5 modules with nothing left over. A full 63-module rack of this module would be 11025 mA, 11.0 times the 1.0 A budget, so the 63-module figure is a slot count and the current is what decides how many expansion supplies go into the rack.
Read the sibling list by the numbers in the description rather than by the catalog order: channel count, per-channel rating and per-module rating are three separate published figures, and on this page they do not scale together.
What the printed data does not carry: this page prints the sibling descriptions but not their POINTBus currents, so the 175 mA is the only draw in the table that can be used; and no page in this family states a maximum number of modules between two power supplies.
Source: Rockwell publication 1734-IN001 (POINT I/O module and adapter installation instructions) and the module specification tables published on these pages; the class column and the module count are read off the printed lines, not assumed.
The Allen-Bradley POINT I/O 1734 modules category lists the related catalog numbers, options and accessories for this range.