The 1734-IB8S is a POINT Guard I/O safety input slice: eight channels rated SIL CL 3 and PLe Cat. 4, for GuardLogix, Compact GuardLogix and SmartGuard controllers.
It is a two-base module with eight 24V DC test outputs, and those test outputs - not the input readings alone - are what let the safety task prove a channel is live.
| 1734-IB8S | POINT Guard I/O 8-channel safety input, SIL CL 3 / PLe Cat. 4, two bases | IN STOCK |
Safety rating |
SIL CL 3, PLe, Cat. 4 per IEC 61508, IEC 61511, IEC 62061 and ISO 13849-1 |
Compatible controllers |
GuardLogix, Compact GuardLogix and SmartGuard |
Number of safety inputs |
8 |
Input voltage |
11...30V DC at 40 deg C; 11...28.8V DC at 55 deg C |
Input current |
3.5 mA |
Field power |
19.2...28.8V DC, 25 mA no load, SELV/PELV 150VA max |
Test outputs |
24V DC, 0.7 A max per output at 40 deg C; 0.5 A max at 55 deg C; 2.8 A max per module at 40 deg C |
Backplane current |
5V DC, 125 mA |
Isolation voltage |
50V (continuous), basic insulation, field side to system, no isolation between individual channels, tested per UL 61010-1 |
Terminal bases |
Two terminal bases per module |
Keyswitch |
8 (left key), 1 (right key) |
Temperature code |
T4 |
Indicators |
1 yellow lock status, 1 green/yellow power status, 8 I/O channel status |
Temperature, operating |
-20...55 deg C (-4...131 deg F) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN016 (module specifications) and 1734-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 1734-IB8S is a POINT Guard I/O module rated SIL CL 3, PLe, Cat. 4. It is not an input slice that happens to be in a safety rack: it only produces safety data when it is paired with a GuardLogix, Compact GuardLogix or SmartGuard controller over a safety network. Wired to a standard controller it is simply not a safety function.
The module occupies two terminal bases, with keyswitch 8 on the left base and 1 on the right. That double-wide footprint is the physical signature of the POINT Guard family and it is the first thing to check when laying out a rail that already carries 1734-IE4S analog safety slices.
Eight test outputs, 24V DC, 0.7 A per output at 40 deg C derating to 0.5 A at 55 deg C, 2.8 A per module at 40 deg C. Pulsing a test output and watching the input response is how the module proves a channel is live rather than stuck - dual-channel wiring with cross-monitoring is built on these pulses, not on the input reading alone.
Inputs read 11...30V DC at 3.5 mA up to 40 deg C, narrowing to 11...28.8V DC at 55 deg C. The 3.5 mA wetting current is what a safety-rated contact has to carry reliably, and it is the number to quote when a machine builder asks whether a light-guard OSSD output can drive the channel directly.
50V continuous, basic insulation, field side to system, with no isolation between channels and tested to UL 61010-1 rather than a type-test voltage. Temperature code T4. There is no reinforced 250V barrier here - a safety input slice in a 120V cabinet still needs the field wiring kept in its own segregation.
What safety rating does 1734-IB8S carry?
SIL CL 3 and PLe, Cat. 4 per IEC 61508, IEC 61511, IEC 62061 and ISO 13849-1, usable with GuardLogix, Compact GuardLogix and SmartGuard controllers.
How many terminal bases does it need?
Two, keyed 8 on the left base and 1 on the right - the same double-wide footprint as the other POINT Guard I/O modules.
What input voltage and current does it accept?
11...30V DC at 3.5 mA up to 40 deg C, and 11...28.8V DC at 3.5 mA at 55 deg C, with field power 19.2...28.8V DC at 25 mA no load.
What are the test outputs for?
Eight 24V DC test outputs, 0.7 A each at 40 deg C and 0.5 A at 55 deg C, used to pulse the field circuit so the module can detect a stuck-on or stuck-off safety channel.
Can it be used with a standard (non-safety) controller?
No. Safety data requires a safety controller and a safety network; on a standard controller the slice does not provide a safety function.
1734-IB8S is a 8-point safety DC input in the POINT I/O family. It mounts on a terminal base assembly that is ordered separately, connects to the POINTBus through the base, and presents its field wiring on the removable terminal block.
| Attribute | Value |
| Catalog number | 1734-IB8S |
| Module type | 8-point safety DC input |
| POINTBus current requirement | 75 mA |
| Module width | 12.1 mm (0.48 in.) standard, 24.1 mm (0.94 in.) for safety modules |
| Terminal base | Ordered separately: 1734-TB/TBS (8 terminal) or 1734-TB3/TB3S (12 terminal) |
| Module dimensions | 77.5 x 12.1 x 56.6 mm (3.05 x 0.48 x 2.23 in.), weight approx. 31-36 g |
| Output/input rating, 1734-OB8S reference | 1.0 A per point at 40 °C, 0.5 A at 55 °C; 8.0 A aggregate at 40 °C, 2.0 A at 55 °C |
| Field power limit, safety | One SELV/PELV supply limited to 150 VA |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Every POINT I/O module mounts in a terminal base that is ordered separately, and the number of field terminals on the base has to match the module: eight terminals for single-point-per-channel digital modules, twelve where the module needs a common or a shield return per channel group.
Safety and analog modules both spend panel width: a safety module occupies 24.1 mm rather than the standard 12.1 mm, and a slice that mixes safety and standard I/O has to be laid out from the width table rather than from the module count. The same table is what determines whether a slice still fits the rail after two safety modules are added.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
The system is rated for panel work rather than for a lab bench: modules plug onto bases that are already wired, the RTB stays on the wiring while the electronics come off, and the same base family accepts the next module of the same width. That is the reason a spare part for POINT I/O is usually an RTB or a base rather than a module, and why a maintenance stock built only from modules is incomplete.
This part sits in the Allen-Bradley POINT I/O 1734 modules category, with the other models and spare parts listed alongside it.