Product Details:
Payment & Shipping Terms:
|
The 1734-IB8 packs eight 24V DC sinking inputs into one 12 mm POINT I/O slice. It is the densest standard sink input in the family and the one most often specified when a remote station collects a full field device cluster - eight proximity switches on a conveyor zone, or the complete feedback set of an eight-position dial.
All eight points form one group with a shared common. The module produces one byte of input data (I0 to I7), consumes no output data, and uses the same 10...28.8V DC on-state and 5V DC maximum off-state limits as the rest of the Series C sink inputs.
| 1734-IB2 | 2 sinking 24V DC inputs, one group of 2, 30.9 g | IN STOCK |
| 1734-IB4 | 4 sinking 24V DC inputs, one group of 4, 31.8 g | IN STOCK |
| 1734-IB8 | 8 sinking 24V DC inputs, one group of 8, 32.3 g | IN STOCK |
On-state voltage, min |
10V DC |
On-state voltage, nominal |
24V DC |
On-state voltage, max |
28.8V DC |
On-state current, min |
2 mA |
On-state current, nominal |
4 mA @ 24V DC |
On-state current, max |
5 mA |
Off-state voltage, max |
5V DC |
Off-state current, min |
1.5 mA |
Input impedance, nominal |
3.6 kΩ |
Input impedance, max |
4.7 kΩ |
Input filter time |
0.5 ms hardware plus 0...63 ms, user-selectable, both directions |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), Reinforced Insulation, tested 2500V DC for 60 s, field side to system |
Field power supply, nominal |
24V DC |
Field power voltage range |
10...28.8V DC |
Dimensions, HxWxD |
56 x 12 x 75.5 mm |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Mounting base |
1734-TB or 1734-TBS wiring base assembly |
Keyswitch position |
1 |
Temperature code |
T4A (North American), T4 (IEC) |
Operating temperature |
-20...55 °C |
Enclosure |
None (open style) |
Inputs per module |
8 (1 group of 8), sinking |
Power dissipation, max @ 28.8V DC |
1.6 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
5.5 BTU/hr @ 28.8V DC |
Input status indicators |
8, yellow, logic side |
Weight, approx |
32.3 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN051H-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The default data map is a single byte with I0 in bit 0 through I7 in bit 7, 1 meaning on. Because the whole module is one group, all eight points share a common return, which keeps the terminal count low but requires the field devices to be referenced to the same supply. The module consumes nothing, so no configuration output image is needed beyond module parameters.
POINTBus current is 75 mA at 5V DC - identical to the two- and four-point versions, so adding points costs nothing on the adapter's 5V budget. The real cost is heat: 1.6 W and 5.5 BTU/hr at 28.8V DC, the highest of the three sink input modules, which matters in a sealed enclosure where slice count is decided by temperature rise rather than by point count.
Terminals 0 through 7 map one-to-one to inputs 0 through 7. Common and power are daisy-chained from the adapter, a 1734-FPD or a 1734-EP24DC, or from a user-supplied auxiliary terminal block; when two wires share a termination point they must be the same gauge and type. 12/24V DC for 3-wire devices comes from the internal power bus.
Hardware filtering is 0.5 ms in both directions. The 0...63 ms software filter is set per module, so on an eight-point slice every point shares the same filter time; that is convenient when all eight devices are similar, and a reason to split mixed device types across slices when they are not. Off-to-on and on-to-off times can be configured independently.
Standard 1734-IB8 suits general-purpose sensing. When the same eight points must be safety-rated, the equivalent is 1734-IB8S, which is a separate module with its own installation instructions. Both fit the same 1734-TB/1734-TBS base and the same -20...55 °C envelope, so the choice is by function, not by wiring.
Does the 1734-IB8 consume output data from the scanner?
No. The module produces one byte of input data (scanner Rx) and consumes no I/O data (scanner Tx), so the adapter's output image is not used by this module.
What is the input filter time and can it be changed?
0.5 ms of hardware filtering applies in both directions, plus a user-selectable 0...63 ms software filter. The default configuration uses the hardware filter only, so set the software value in the module's configuration when contact bounce or noise is present.
Which terminal base does the 1734-IB8 need?
It mounts on a 1734-TB or 1734-TBS wiring base assembly with a removable terminal block. Terminal base screw torque is 0.8 Nm (7 lb-in).
Can I use 2-wire and 3-wire proximity switches?
Yes. Sink inputs accept 2-wire and 3-wire sinking devices; on 3-wire switches connect the common to terminal 4 (1734-IB2/IB4) and take 12/24V DC from the internal power bus or from terminals 6/7.
What field voltage range can the inputs tolerate?
Field power is 24V DC nominal and the published range is 10...28.8V DC. On-state voltage is 10V DC minimum, 24V DC nominal and 28.8V DC maximum; off-state voltage must stay at or below 5V DC.
How many bytes does a 1734-IB8 send to the controller?
One byte. Bit 0 is input 0 through bit 7 is input 7, with 1 meaning on. There is no consumed data, so the scanner output image is not used by this module.
Browse the Allen-Bradley POINT I/O 1734 modules category for the other models, options and spare parts that share this range.