Product Details:
Payment & Shipping Terms:
|
The 1734-IB2 is the two-channel member of the POINT I/O Series C sink input family. It puts two 24V DC sinking inputs into a 12 mm slice on a 1734-TB or 1734-TBS base, so a machine builder can pick up two limit switches or two proximity sensors at the point where the wiring already is instead of pulling them back to a 16-channel rack card.
Both inputs share one common group. The module produces one byte of input data and consumes nothing, and the published on-state window is 10...28.8V DC with 4 mA typical at 24V DC.
| 1734-IB2 | 2 sinking 24V DC inputs, one group of 2, 30.9 g | IN STOCK |
| 1734-IB4 | 4 sinking 24V DC inputs, one group of 4, 31.8 g | IN STOCK |
| 1734-IB8 | 8 sinking 24V DC inputs, one group of 8, 32.3 g | IN STOCK |
On-state voltage, min |
10V DC |
On-state voltage, nominal |
24V DC |
On-state voltage, max |
28.8V DC |
On-state current, min |
2 mA |
On-state current, nominal |
4 mA @ 24V DC |
On-state current, max |
5 mA |
Off-state voltage, max |
5V DC |
Off-state current, min |
1.5 mA |
Input impedance, nominal |
3.6 kΩ |
Input impedance, max |
4.7 kΩ |
Input filter time |
0.5 ms hardware plus 0...63 ms, user-selectable, both directions |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), Reinforced Insulation, tested 2500V DC for 60 s, field side to system |
Field power supply, nominal |
24V DC |
Field power voltage range |
10...28.8V DC |
Dimensions, HxWxD |
56 x 12 x 75.5 mm |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Mounting base |
1734-TB or 1734-TBS wiring base assembly |
Keyswitch position |
1 |
Temperature code |
T4A (North American), T4 (IEC) |
Operating temperature |
-20...55 °C |
Enclosure |
None (open style) |
Inputs per module |
2 (1 group of 2), sinking |
Power dissipation, max @ 28.8V DC |
0.7 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
2.4 BTU/hr @ 28.8V DC |
Input status indicators |
2, yellow, logic side |
Weight, approx |
30.9 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN051H-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Density is the whole argument. A 1734-IB2 occupies one slot and one base, and it costs less panel space than any 4- or 8-channel card when only two signals are needed at that spot. The trade-off is that each point carries the full per-module POINTBus and heat budget of a slice: 75 mA at 5V DC on the backplane and 0.7 W dissipation, which is the lowest of the three sink input modules.
Terminals 0 and 1 are inputs 0 and 1; terminals 2 and 3 are no connection; 4 and 5 are common; 6 and 7 are user supply. 12/24V DC is supplied through the internal power bus, so a 2-wire sinking device returns to the common terminals and a 3-wire device takes its supply from the auxiliary terminals. Keep the field power inside 10...28.8V DC.
Every input has 0.5 ms of hardware filtering plus an optional 0...63 ms software filter that you set per module. On a two-point slice the software filter matters more than on a dense card, because the two points usually belong to one guard door or one small fixture and a shared filter time keeps their timestamps comparable.
Module status and network status are the only LEDs besides the two yellow input indicators, so fault isolation is by LED pattern: flashing green on module status means the slice is waiting for configuration, flashing red means a recoverable fault, solid red means replace the module. There is no per-point diagnostic channel on a standard 1734-IB2.
Use 1734-IB2 when the count is two and the location is remote; step to 1734-IB4 or 1734-IB8 when the same cabinet needs more contacts, and to 1734-IB8S when the points must be safety-rated. All Series C sink inputs in this family share the same 50V isolation, T4A/T4 temperature code and -20...55 °C operating range, so mixing channel counts in one adapter is electrically consistent.
Does the 1734-IB2 consume output data from the scanner?
No. The module produces one byte of input data (scanner Rx) and consumes no I/O data (scanner Tx), so the adapter's output image is not used by this module.
What is the input filter time and can it be changed?
0.5 ms of hardware filtering applies in both directions, plus a user-selectable 0...63 ms software filter. The default configuration uses the hardware filter only, so set the software value in the module's configuration when contact bounce or noise is present.
Which terminal base does the 1734-IB2 need?
It mounts on a 1734-TB or 1734-TBS wiring base assembly with a removable terminal block. Terminal base screw torque is 0.8 Nm (7 lb-in).
Can I use 2-wire and 3-wire proximity switches?
Yes. Sink inputs accept 2-wire and 3-wire sinking devices; on 3-wire switches connect the common to terminal 4 (1734-IB2/IB4) and take 12/24V DC from the internal power bus or from terminals 6/7.
What field voltage range can the inputs tolerate?
Field power is 24V DC nominal and the published range is 10...28.8V DC. On-state voltage is 10V DC minimum, 24V DC nominal and 28.8V DC maximum; off-state voltage must stay at or below 5V DC.
How much current does a 1734-IB2 draw from the adapter?
75 mA at 5V DC maximum on POINTBus, plus whatever the field devices draw from the 24V auxiliary supply. Module dissipation is 0.7 W at 28.8V DC.
The Allen-Bradley POINT I/O 1734 modules category lists the related catalog numbers, options and accessories for this range.