logo
Home ProductsAB POINT I/O 1734

Allen Bradley PLC 1734-IB2 / 1734IB2

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1734-IB2 / 1734IB2

China Allen Bradley PLC 1734-IB2 / 1734IB2 supplier
Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier Allen Bradley PLC 1734-IB2 / 1734IB2 supplier

Large Image :  Allen Bradley PLC 1734-IB2 / 1734IB2

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1734-IB2 / 1734IB2

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $22.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

1734-IB2 technical data PDF download POINT I/O 1734-IB2 / 1734IB2 2-Point 24V DC Sink Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: POINT I/O Digital Input

The 1734-IB2 is the two-channel member of the POINT I/O Series C sink input family. It puts two 24V DC sinking inputs into a 12 mm slice on a 1734-TB or 1734-TBS base, so a machine builder can pick up two limit switches or two proximity sensors at the point where the wiring already is instead of pulling them back to a 16-channel rack card.

Both inputs share one common group. The module produces one byte of input data and consumes nothing, and the published on-state window is 10...28.8V DC with 4 mA typical at 24V DC.

1734-IB2 2 sinking 24V DC inputs, one group of 2, 30.9 g IN STOCK
1734-IB4 4 sinking 24V DC inputs, one group of 4, 31.8 g IN STOCK
1734-IB8 8 sinking 24V DC inputs, one group of 8, 32.3 g IN STOCK

Product Specifications 1734-IB2 (PDF)
 On-state voltage, min
 10V DC
 On-state voltage, nominal
 24V DC
 On-state voltage, max
 28.8V DC
 On-state current, min
 2 mA
 On-state current, nominal
 4 mA @ 24V DC
 On-state current, max
 5 mA
 Off-state voltage, max
 5V DC
 Off-state current, min
 1.5 mA
 Input impedance, nominal
 3.6 kΩ
 Input impedance, max
 4.7 kΩ
 Input filter time
 0.5 ms hardware plus 0...63 ms, user-selectable, both directions
 POINTBus current, max
 75 mA @ 5V DC
 Isolation voltage
 50V (continuous), Reinforced Insulation, tested 2500V DC for 60 s, field side to system
 Field power supply, nominal
 24V DC
 Field power voltage range
 10...28.8V DC
 Dimensions, HxWxD
 56 x 12 x 75.5 mm
 Terminal base screw torque
 0.8 Nm (7 lb-in)
 Mounting base
 1734-TB or 1734-TBS wiring base assembly
 Keyswitch position
 1
 Temperature code
 T4A (North American), T4 (IEC)
 Operating temperature
 -20...55 °C
 Enclosure
 None (open style)
 Inputs per module
 2 (1 group of 2), sinking
 Power dissipation, max @ 28.8V DC
 0.7 W @ 28.8V DC
 Thermal dissipation, max @ 28.8V DC
 2.4 BTU/hr @ 28.8V DC
 Input status indicators
 2, yellow, logic side
 Weight, approx
 30.9 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN051H-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1734-IB2 original product photograph, wide view 1734-IB2 original product photograph, label view 1734-IB2 original product photograph, second unit

Why a two-channel module exists

Density is the whole argument. A 1734-IB2 occupies one slot and one base, and it costs less panel space than any 4- or 8-channel card when only two signals are needed at that spot. The trade-off is that each point carries the full per-module POINTBus and heat budget of a slice: 75 mA at 5V DC on the backplane and 0.7 W dissipation, which is the lowest of the three sink input modules.

Wiring the two points

Terminals 0 and 1 are inputs 0 and 1; terminals 2 and 3 are no connection; 4 and 5 are common; 6 and 7 are user supply. 12/24V DC is supplied through the internal power bus, so a 2-wire sinking device returns to the common terminals and a 3-wire device takes its supply from the auxiliary terminals. Keep the field power inside 10...28.8V DC.

Filtering and response

Every input has 0.5 ms of hardware filtering plus an optional 0...63 ms software filter that you set per module. On a two-point slice the software filter matters more than on a dense card, because the two points usually belong to one guard door or one small fixture and a shared filter time keeps their timestamps comparable.

Diagnostics you actually get

Module status and network status are the only LEDs besides the two yellow input indicators, so fault isolation is by LED pattern: flashing green on module status means the slice is waiting for configuration, flashing red means a recoverable fault, solid red means replace the module. There is no per-point diagnostic channel on a standard 1734-IB2.

Where it fits in a POINT I/O line-up

Use 1734-IB2 when the count is two and the location is remote; step to 1734-IB4 or 1734-IB8 when the same cabinet needs more contacts, and to 1734-IB8S when the points must be safety-rated. All Series C sink inputs in this family share the same 50V isolation, T4A/T4 temperature code and -20...55 °C operating range, so mixing channel counts in one adapter is electrically consistent.

FAQ — 1734-IB2

Does the 1734-IB2 consume output data from the scanner?

No. The module produces one byte of input data (scanner Rx) and consumes no I/O data (scanner Tx), so the adapter's output image is not used by this module.

What is the input filter time and can it be changed?

0.5 ms of hardware filtering applies in both directions, plus a user-selectable 0...63 ms software filter. The default configuration uses the hardware filter only, so set the software value in the module's configuration when contact bounce or noise is present.

Which terminal base does the 1734-IB2 need?

It mounts on a 1734-TB or 1734-TBS wiring base assembly with a removable terminal block. Terminal base screw torque is 0.8 Nm (7 lb-in).

Can I use 2-wire and 3-wire proximity switches?

Yes. Sink inputs accept 2-wire and 3-wire sinking devices; on 3-wire switches connect the common to terminal 4 (1734-IB2/IB4) and take 12/24V DC from the internal power bus or from terminals 6/7.

What field voltage range can the inputs tolerate?

Field power is 24V DC nominal and the published range is 10...28.8V DC. On-state voltage is 10V DC minimum, 24V DC nominal and 28.8V DC maximum; off-state voltage must stay at or below 5V DC.

How much current does a 1734-IB2 draw from the adapter?

75 mA at 5V DC maximum on POINTBus, plus whatever the field devices draw from the 24V auxiliary supply. Module dissipation is 0.7 W at 28.8V DC.


Data sources. Technical values on this page come from Rockwell publication 1734-IN051H-EN-E (POINT I/O Input Modules, catalog numbers 1734-IB2, 1734-IB4, 1734-IB8, Series C) and 1734-UM001 (POINT I/O Digital and Analog Modules User Manual). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

The Allen-Bradley POINT I/O 1734 modules category lists the related catalog numbers, options and accessories for this range.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)