Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier Allen Bradley PLC 1734-OX2 / 1734OX2 supplier

Large Image :  Allen Bradley PLC 1734-OX2 / 1734OX2

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley POINT I/O 1734-OX2 / 1734OX2

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $51.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 30 PCS
Detailed Product Description

1734-OX2 technical data PDF download POINT I/O 1734-OX2 / 1734OX2 2-Point Form C Relay Output Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: POINT I/O Digital Output

The 1734-OX2 is the changeover version of the POINT I/O relay output: two Form C contacts with both normally open and normally closed terminals, so a circuit can be closed on one side and a second circuit opened at the same instant from one output bit.

The contact system is wider than the OW family - 240V AC and 125V DC at 2.0 A resistive, 48V DC at 0.5 A, 15 A make on AC inductive loads at PF 0.4 - and the resistive contact life is 1,000,000 cycles against 100,000 inductive.

1734-OW2 2 Form A isolated relay contacts, 2.0 A at 120/240V AC, 39 g IN STOCK
1734-OW4 4 Form A isolated relay contacts, 2.0 A at 120/240V AC, 46.1 g IN STOCK
1734-OX2 2 Form C changeover relay contacts, 2.0 A at 240V AC, 1,000,000 resistive cycles IN STOCK

Product Specifications 1734-OX2 (PDF)
 Outputs per module
 2 Form C isolated electromechanical relays, normally open and normally closed
 Output voltage range
 5...28.8V DC 2.0 A; 48V DC 0.5 A; 125V AC 2.0 A; 125V DC 0.25 A; 240V AC 2.0 A (resistive)
 Inductive rating
 2.0 A steady state, 15 A make at 125/240V AC, PF 0.4; 2.0 A at 5...28.8V DC, L/R 7 ms
 Power rating, steady state
 480W at 240V AC resistive, 250W at 125V AC resistive, 60W at 28.8V DC; 480VA / 250VA inductive
 Off-state leakage, max
 2.0 mA at 240V AC, with bleed resistor through snubber circuit
 Minimum contact load
 5 mA per point
 Initial contact resistance
 30 milliohm
 Output signal delay
 10 ms maximum, off-to-on and on-to-off
 Switching frequency, max
 1 operation every 3 s (0.3 Hz at rated load)
 Contact life, min
 1,000,000 cycles resistive; 100,000 cycles inductive
 POINTBus current, max
 100 mA at 5V DC
 Power dissipation, max
 0.5 W
 Thermal dissipation, max
 1.7 BTU/hr
 Isolation voltage
 250V continuous, tested 2550V DC for 1 s, between contact sets and customer load to logic
 Field power bus
 None required, 240V AC max, 2 A per channel / 4 A per module
 Module location
 1734-TB or 1734-TBS wiring base assembly
 Terminal base screw torque
 0.6 Nm (7 lb-in)
 Wire size
 0.25...2.5 mm2 (22...14 AWG) copper rated 75 °C or greater, 1.2 mm insulation max
 Dimensions, HxWxD
 56 x 12 x 75.5 mm
 Weight, approx
 36.9 g
 Field wiring terminations
 0/1 - output 0 NC/NO, 2/3 - output 1 NC/NO, 4/5 - relay common 0/1, 6/7 - +supply
 Operating temperature
 -20...55 °C

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN587B-EN-P (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1734-OX2 original product photograph, wide view 1734-OX2 original product photograph, label view 1734-OX2 original product photograph, second unit

Form C gives you both states

Terminals 0 and 1 are output 0 normally closed and normally open, 2 and 3 are output 1 NC and NO, 4 and 5 are the relay commons and 6 and 7 are the supply. A changeover contact is the reason to pick OX2 over OW2 when a single bit has to switch between two circuits - a forward/reverse pair or a run/standby selector.

Ratings by load type

Resistive: 2.0 A at 5...28.8V DC, 0.5 A at 48V DC, 0.25 A at 125V DC, 2.0 A at 125V AC and 240V AC. Inductive AC: 2.0 A steady state with 15 A make at PF 0.4, which is what a contactor coil needs at the instant it pulls in. 480W at 240V AC resistive, 24W at 48V DC - the DC rating falls away quickly with voltage.

Contact life depends on the load

1,000,000 cycles resistive but only 100,000 cycles inductive, and 5 mA minimum per point so the contact wipes clean. Switching a dry signal below 5 mA may give unreliable contact resistance - 30 milliohm initial, and oxide builds up when nothing breaks it down.

Isolation, note the test duration

250V continuous between contact sets and from customer load to logic, tested at 2550V DC for 1 s - one second, not the 60 s used by the OW modules. That is a specification detail worth recording, because a panel builder comparing the two data sheets will see different numbers for what looks like the same isolation.

Base, torque and wiring

Bases are 1734-TB or 1734-TBS only - the OX2 does not list the TOP/TOPS option. Terminal base torque is 0.6 Nm, wire 0.25 to 2.5 mm2 (22 to 14 AWG) rated at least 75 °C with 1.2 mm insulation, and the module draws 100 mA at 5V DC with 0.5 W dissipation.

FAQ — 1734-OX2

What is the difference between 1734-OX2 and 1734-OW2?

OX2 has two Form C changeover contacts with both NO and NC terminals, a 125V DC and 48V DC range, 15 A make on AC inductive loads and 1,000,000 resistive contact cycles. OW2 has two Form A normally open contacts rated 120/240V AC 2.0 A with 1800 VA make and 180 VA break. OX2 suits changeover circuits, OW2 suits simple on/off loads.

What load can 1734-OX2 switch at 240V AC?

2.0 A resistive, 480W maximum steady state; 2.0 A steady state inductive with 15 A make at PF 0.4, 480VA maximum. Off-state leakage is 2.0 mA at 240V AC through the snubber bleed resistor.

How long do the contacts last?

1,000,000 cycles minimum with resistive loads and 100,000 cycles with inductive loads. Adding a surge suppressor across an inductive load is what keeps the inductive figure from being consumed early.

Does 1734-OX2 need external load power?

No. The field power bus entry reads none required up to 240V AC, 2 A per channel and 4 A per module, so the relay circuit is fed through the base supply terminals 6 and 7.

Which terminal base fits 1734-OX2?

1734-TB or 1734-TBS only. Torque is 0.6 Nm and conductors are 0.25 to 2.5 mm2 (22 to 14 AWG) rated at least 75 deg C.


Data sources. Technical values on this page come from Rockwell publication 1734-IN587B-EN-P (POINT I/O 2 Relay Output Module, catalog number 1734-OX2, Series C, March 2002) and 1734-UM001 (POINT I/O Digital and Analog Modules User Manual). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Where 1734-OX2 sits in the POINT I/O line

The table reproduces the sibling list this page publishes, with each catalog number put in the class of module it is; the paragraph after it places this part in that ladder, and the arithmetic at the end uses this page's own POINTBus figure against the 1.0 A budget the adapters print.

Catalog numberWhat the published line saysClass of module
1734-OW22 Form A isolated relay contacts, 2.0 A at 120/240V AC, 39 gRelay output
1734-OW44 Form A isolated relay contacts, 2.0 A at 120/240V AC, 46.1 gRelay output
1734-OX22 Form C changeover relay contacts, 2.0 A at 240V AC, 1,000,000 resistive cyclesRelay output

1734-OX2 is the only changeover module in this list and the dearest on the backplane at 100 mA. Form C contacts bring a normally closed path, 240 V AC at 2.0 A resistive, and a printed minimum contact load of 5 mA per point, which is the number that decides whether a low-current pilot circuit can use it at all.

At the 100 mA this module prints, the 1.0 A POINTBus carries 10 modules with nothing left over. A full 63-module rack of this module would be 6300 mA, 6.3 times the 1.0 A budget, so the 63-module figure is a slot count and the current is what decides how many expansion supplies go into the rack.

The class column is the useful filter: within one page the list holds modules that look alike in a catalog and behave completely differently on a backplane, and the printed one-line description is the only place the difference appears.

What the printed data does not carry: this page prints the sibling descriptions but not their POINTBus currents, so the 100 mA is the only draw in the table that can be used; and no page in this family states a maximum number of modules between two power supplies.

Source: Rockwell publication 1734-IN001 (POINT I/O module and adapter installation instructions) and the module specification tables published on these pages; the class column and the module count are read off the printed lines, not assumed.

Related numbers

Other catalog numbers and accessories for the same range are collected in the Allen-Bradley POINT I/O 1734 modules category.