The 1734-OW4 provides four Form A isolated normally open relay contacts in one 12 mm POINT I/O slice. Contact rating is 120/240V AC 2.0 A at 50/60 Hz with 1800 VA make and 180 VA break, or 2.0 A at 5...30V DC with pilot duty R150.
Unlike 1734-OW2, the four-point module cannot take load power from the internal power bus. Load power must come from an external supply wired to the base - this is the single difference that catches people out when they substitute OW4 for OW2 in an existing panel.
| 1734-OW2 | 2 Form A isolated relay contacts, 2.0 A at 120/240V AC, 39 g | IN STOCK |
| 1734-OW4 | 4 Form A isolated relay contacts, 2.0 A at 120/240V AC, 46.1 g | IN STOCK |
| 1734-OX2 | 2 Form C changeover relay contacts, 2.0 A at 240V AC, 1,000,000 resistive cycles | IN STOCK |
Outputs per module |
4 Form A isolated, normally open electromechanical relays |
Backplane power |
5V DC, 90 mA |
Relay type |
Form A, isolated, normally open, electromechanical |
Contact rating |
120/240V AC 2.0 A @ 50/60 Hz, 1800 VA make, 180 VA break; 5...30V DC 2.0 A, R150 |
Pilot duty rating |
R150 |
Off-state leakage, max |
1.2 mA @ 240V AC, with bleed resistor through snubber circuit |
Switching frequency, max |
1 operation every 3 s (0.3 Hz at rated load) |
Expected contact life, min |
100,000 operations at rated load |
Power consumption |
0.8 W |
Power dissipation, max |
0.5 W |
Isolation voltage |
250V, tested 2550V DC for 60 s, field side to system and between contact sets |
Module location |
1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS wiring base assembly |
Terminal base screw torque |
Determined by the installed terminal block |
Wire size |
0.25...2.5 mm2 (22...14 AWG) copper rated 85 °C or greater, 1.2 mm insulation max |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
1 - on signal ports |
Operating temperature |
-20...55 °C |
Weight, approx |
46.1 g |
Field wiring terminations |
0A/0B, 1A/1B, 2A/2B, 3A/3B - four contact pairs; 1734-IN055-EN-E numbers the terminals 0, 2, 1, 3, 4, 6, 5, 7 |
Indicators |
4 output status, module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN055-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Rockwell states it directly: load power must be provided by an external power source for 1734-OW4 and 1734-OW4K, and the module cannot be powered from the internal power bus. Pins 6 and 7 are V supply and pins 4 and 5 are V common on 1734-OW2; on OW4 the load circuit has to be fed from the panel's own supply. The relay contacts themselves remain isolated.
The default data map consumes four bits - Ch0 to Ch3 - with bits 4 to 7 not used, so the controller sees a compact 4-bit output image regardless of how the field circuits are arranged. Contacts are isolated from each other at 250V, tested 2550V DC for 60 s, field side to system and between contact sets.
120/240V AC 2.0 A at 50/60 Hz, 1800 VA make, 180 VA break; 5...30V DC 2.0 A, pilot duty R150. With four relays on one slice the aggregate load current through the base terminals is what to check, not only the per-contact figure.
One operation every 3 s at rated load and a minimum of 100,000 operations at rated load. Energising four contactor coils from one slice does not change those limits - if the machine cycles faster, use solid-state outputs.
Wire size 0.25 to 2.5 mm2 (22 to 14 AWG) copper rated at least 85 °C, 1.2 mm maximum insulation; bases 1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. Terminal base screw torque follows the installed terminal block, and the module draws 90 mA at 5V DC from the backplane while dissipating 0.5 W.
Can 1734-OW4 replace 1734-OW2 directly?
Not without rewiring. OW2 can power its load circuit from the internal power bus through pins 6 and 7 with 4 and 5 as common; OW4 cannot - load power must come from an external supply. The base footprint is the same and the contact rating is identical.
How many output bits does the module use?
Four. The default data map consumes Ch0 to Ch3 and leaves the upper bits unused, so a four-point relay slice costs four output bits in the controller image.
Does a relay output need a surge suppressor?
Yes for inductive loads. Rockwell's wiring guidelines recommend a suppressor across the coil; without it the inductive kick erodes contacts well before the 100,000-operation rating.
What is the maximum switching frequency?
One operation every 3 s, 0.3 Hz at rated load, with a minimum expected contact life of 100,000 operations at rated load.
Which bases accept 1734-OW4?
1734-TB, 1734-TBS, 1734-TOP and 1734-TOPS wiring base assemblies, the same set as the rest of the 1734 relay and output family.
The table reproduces the sibling list this page publishes, with each catalog number put in the class of module it is; the paragraph after it places this part in that ladder, and the arithmetic at the end uses this page's own POINTBus figure against the 1.0 A budget the adapters print.
| Catalog number | What the published line says | Class of module |
| 1734-OW2 | 2 Form A isolated relay contacts, 2.0 A at 120/240V AC, 39 g | Relay output |
| 1734-OW4 | 4 Form A isolated relay contacts, 2.0 A at 120/240V AC, 46.1 g | Relay output |
| 1734-OX2 | 2 Form C changeover relay contacts, 2.0 A at 240V AC, 1,000,000 resistive cycles | Relay output |
1734-OW4 is the four-contact member of the relay trio: 90 mA on the backplane, 10 mA above the two-contact 1734-OW2 and 46.1 g against 39 g. The contact rating is identical on both - 2.0 A at 120/240 V AC, 1800 VA make and 180 VA break - so the 10 mA buys two more contacts and nothing else.
At the 90 mA this module prints, the 1.0 A POINTBus carries 11 modules with nothing left over. A full 63-module rack of this module would be 5670 mA, 5.7 times the 1.0 A budget, so the 63-module figure is a slot count and the current is what decides how many expansion supplies go into the rack.
Read the sibling list by the numbers in the description rather than by the catalog order: channel count, per-channel rating and per-module rating are three separate published figures, and on this page they do not scale together.
What the printed data does not carry: this page prints the sibling descriptions but not their POINTBus currents, so the 90 mA is the only draw in the table that can be used; and no page in this family states a maximum number of modules between two power supplies.
Source: Rockwell publication 1734-IN001 (POINT I/O module and adapter installation instructions) and the module specification tables published on these pages; the class column and the module count are read off the printed lines, not assumed.
This part sits in the Allen-Bradley POINT I/O 1734 modules category, with the other models and spare parts listed alongside it.