The 1734-OW2 provides two Form A isolated normally open relay contacts from a POINT I/O slice. The contacts are dry and isolated from each other and from the system, so the module can switch a 120/240V AC circuit, a 5...30V DC circuit, or a signal that belongs to another panel.
Contact rating is 2.0 A at 120/240V AC with 1800 VA make and 180 VA break, or 2.0 A at 5...30V DC with pilot duty R150. Backplane draw is 80 mA at 5V DC and the module dissipates 0.5 W.
| 1734-OW2 | 2 Form A isolated relay contacts, 2.0 A at 120/240V AC, 39 g | IN STOCK |
| 1734-OW4 | 4 Form A isolated relay contacts, 2.0 A at 120/240V AC, 46.1 g | IN STOCK |
| 1734-OX2 | 2 Form C changeover relay contacts, 2.0 A at 240V AC, 1,000,000 resistive cycles | IN STOCK |
Outputs per module |
2 Form A isolated, normally open electromechanical relays |
Backplane power |
5V DC, 80 mA |
Relay type |
Form A, isolated, normally open, electromechanical |
Contact rating |
120/240V AC 2.0 A @ 50/60 Hz, 1800 VA make, 180 VA break; 5...30V DC 2.0 A, R150 |
Pilot duty rating |
R150 |
Off-state leakage, max |
1.2 mA @ 240V AC, with bleed resistor through snubber circuit |
Switching frequency, max |
1 operation every 3 s (0.3 Hz at rated load) |
Expected contact life, min |
100,000 operations at rated load |
Power consumption |
0.8 W |
Power dissipation, max |
0.5 W |
Isolation voltage |
250V, tested 2550V DC for 60 s, field side to system and between contact sets |
Module location |
1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS wiring base assembly |
Terminal base screw torque |
Determined by the installed terminal block |
Wire size |
0.25...2.5 mm2 (22...14 AWG) copper rated 85 °C or greater, 1.2 mm insulation max |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
1 - on signal ports |
Operating temperature |
-20...55 °C |
Weight, approx |
39 g |
Field wiring terminations |
0A/0B - Channel 0, 1A/1B - Channel 1, 2A/2B - Channel 2, 3A/3B - Channel 3 |
Indicators |
Output status, module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN055-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Two Form A contacts, isolated from each other, are the reason to choose a relay module over a solid-state output: one channel can switch a 240V AC solenoid while the other switches a 24V DC signal to another cabinet, and neither sees the other's circuit. Isolation is 250V tested at 2550V DC for 60 s, field side to system and between contact sets.
1800 VA make against 180 VA break is the number that matters for inductive AC loads: a contactor coil that draws a high inrush can be made at 2.0 A but must be broken at a much smaller current. The rated load is 120/240V AC 2.0 A at 50/60 Hz, and the pilot duty rating is R150 for the 5...30V DC case.
Maximum switching frequency is one operation every 3 s, 0.3 Hz at rated load, and expected contact life is 100,000 operations at rated load. A relay module is therefore not a solution for fast pulsing - if a load needs 10 Hz, this is the wrong device and a solid-state output belongs there instead.
Off-state leakage is 1.2 mA at 240V AC through the snubber circuit's bleed resistor. That figure applies when the contact is open, so a very sensitive load may still see a small current; the bleed resistor is there to keep the leakage from building a voltage across an open contact.
Conductors must be rated at least 85 °C for 1734-OW2, wire size 0.25 to 2.5 mm2 (22 to 14 AWG) copper with 1.2 mm maximum insulation, and the base options are 1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. Terminal base screw torque follows the installed terminal block.
Can a 1734-OW2 switch a 240V AC contactor coil directly?
Yes, within the contact rating: 120/240V AC 2.0 A at 50/60 Hz with 1800 VA make and 180 VA break. Fit a surge suppressor across the coil - Rockwell's wiring guidelines recommend it - because inductive kick is what erodes relay contacts.
Are the two contacts isolated from each other?
Yes. The module provides Form A isolated contacts, with 250V isolation tested at 2550V DC for 60 s both field-to-system and between contact sets, so the two channels may sit on different circuits.
How often can the relay operate?
One operation every 3 s, which is 0.3 Hz at rated load, with a minimum expected life of 100,000 operations at rated load. For faster switching use a solid-state output module.
Does the relay output need field power?
No. The contacts are dry, so the switched circuit supplies its own voltage; the module itself takes 80 mA at 5V DC from the backplane and consumes 0.8 W.
What wire temperature rating is required?
85 deg C or greater for 1734-OW2 conductors, with 0.25 to 2.5 mm2 (22 to 14 AWG) copper and 1.2 mm maximum insulation.
The table reproduces the sibling list this page publishes, with each catalog number put in the class of module it is; the paragraph after it places this part in that ladder, and the arithmetic at the end uses this page's own POINTBus figure against the 1.0 A budget the adapters print.
| Catalog number | What the published line says | Class of module |
| 1734-OW2 | 2 Form A isolated relay contacts, 2.0 A at 120/240V AC, 39 g | Relay output |
| 1734-OW4 | 4 Form A isolated relay contacts, 2.0 A at 120/240V AC, 46.1 g | Relay output |
| 1734-OX2 | 2 Form C changeover relay contacts, 2.0 A at 240V AC, 1,000,000 resistive cycles | Relay output |
1734-OW2 is the two-contact member of the relay trio and the lightest on the backplane at 80 mA. 1734-OW4 carries four Form A contacts at 90 mA and 1734-OX2 carries two Form C changeover contacts at 100 mA, so the ladder is 10 mA per step and the change to changeover contacts costs the most.
At the 80 mA this module prints, the 1.0 A POINTBus carries 12 modules with nothing left over. A full 63-module rack of this module would be 5040 mA, 5.0 times the 1.0 A budget, so the 63-module figure is a slot count and the current is what decides how many expansion supplies go into the rack.
Read the sibling list by the numbers in the description rather than by the catalog order: channel count, per-channel rating and per-module rating are three separate published figures, and on this page they do not scale together.
What the printed data does not carry: this page prints the sibling descriptions but not their POINTBus currents, so the 80 mA is the only draw in the table that can be used; and no page in this family states a maximum number of modules between two power supplies.
Source: Rockwell publication 1734-IN001 (POINT I/O module and adapter installation instructions) and the module specification tables published on these pages; the class column and the module count are read off the printed lines, not assumed.
Browse the Allen-Bradley POINT I/O 1734 modules category for the other models, options and spare parts that share this range.