The 1734-OB2E is the protected two-point 24V DC sourcing output for POINT I/O Series C. Electrically it matches 1734-OB2 - 1.0 A per channel, 2.0 A per module, 0.2V DC maximum drop - but each channel carries its own red fault indicator, so a shorted valve coil is visible at the slice instead of only at the adapter.
The module takes 8 mA from the external 24V DC supply for its output stage, dissipates 0.8 W at 28.8V DC, and mounts on the full range of two-point bases including the three-row TB3 family.
| 1734-OB2E | 2 protected sourcing outputs, red fault LED per channel, 2.0 A per module | IN STOCK |
| 1734-OB4E | 4 protected sourcing outputs, red fault LED per channel, 3.0 A per module | IN STOCK |
| 1734-OB8E | 8 protected sourcing outputs, red fault LED per channel, 3.0 A per module | IN STOCK |
Number of outputs |
2 (1 group of 2), non-isolated, sourcing |
Output current rating, per output |
1.0 A |
Output current rating, max, per module |
2.0 A |
External DC supply current |
8 mA |
On-state voltage, min |
10V DC |
On-state voltage, nominal |
24V DC |
On-state voltage, max |
28.8V DC |
On-state voltage drop, max |
0.2V DC |
On-state current, min per channel |
1.0 mA |
Off-state leakage, max |
0.5 mA @ 28.8V DC |
Surge current |
2 A for 10 ms, repeatable every 3 s |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), reinforced insulation type, tested 2500V DC for 60 s, field side to system |
External DC supply, nominal |
24V DC |
External DC supply range |
10...28.8V DC |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
2 - on signal ports |
Operating temperature |
-20...55 °C |
Enclosure |
None (open style) |
Power dissipation, max @ 28.8V DC |
0.8 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
2.7 BTU/hr @ 28.8V DC |
Weight, approx |
32.60 g |
Module location |
1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS, 1734-TB3, 1734-TB3S, 1734-TOP3, 1734-TOP3S |
Field wiring terminations |
0/2 - Output 0, 1/3 - Output 1, 4/5 - Common, 6/7 - Supply |
Indicators |
2 yellow output status, 2 red output fault, 2 green/red module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN056-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The indicator set is the reason to buy this module: two yellow output status LEDs, two red output fault LEDs and the two green/red module and network LEDs. The fault LEDs are field side, logic-driven, so they report a real channel condition rather than a configuration state. In a panel with two solenoid valves, that is the difference between a five-minute and a thirty-minute fault find.
Current is limited per channel and the fault is latched until the channel is re-energised with the cause removed. Surge capability is 2 A for 10 ms repeatable every 3 s, which covers lamp inrush and small DC motor starts but not a repetitive capacitive load. Off-state leakage stays at or below 0.5 mA at 28.8V DC.
Terminals 0 and 2 are output 0, 1 and 3 are output 1, 4 and 5 are common and 6 and 7 are supply, the same layout as the unprotected 1734-OB2, so a like-for-like swap keeps the field wiring. The external supply must stay in 10...28.8V DC and the module consumes 8 mA of it.
Because this is a two-point module, it accepts 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS as well as 1734-TB3, 1734-TB3S, 1734-TOP3 and 1734-TOP3S. That matters in retrofit work where the three-row base already exists and only the module is being replaced.
Long field cables, wet or washdown areas and loads that fail short - solenoid coils and small DC motors - are the cases where a per-channel fault LED pays for itself. For a dry cabinet driving interposing relays on short wiring, the standard 1734-OB2 is electrically equivalent and cheaper.
What does the extra red LED on a protected output give me?
One red output-fault indicator per channel, driven from the logic side. When a channel trips on short circuit or thermal overload its yellow status LED goes off and its red fault LED comes on, so the electrician knows which of the eight loads to look at without pulling the module.
Does a protected module limit current or latch off?
The module limits the channel current and reports the fault; the published rating is 1.0 A per output with a module maximum of 2.0 A for 1734-OB2E and 3.0 A for 1734-OB4E and 1734-OB8E. Clearing the fault is by removing the cause and re-energising the channel - there is no manual reset button.
What is the difference between 1734-OB8 and 1734-OB8E?
The output stage, voltage window and current ratings are identical; the difference is per-channel electronic protection with a dedicated fault indicator instead of module-level reporting only. Both use the same 1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS base.
Are the outputs isolated from the backplane?
Outputs are non-isolated from the external 24V DC field supply and isolated from the system side by 50V continuous reinforced insulation, tested at 2500V DC for 60 s field side to system.
Which bases fit a 1734-OB8E?
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. The two-point 1734-OB2E also accepts 1734-TB3, 1734-TB3S, 1734-TOP3 and 1734-TOP3S, so a TB3 position can only take the two-point protected module.
How do I size the field supply?
The module itself draws 8 mA (1734-OB2E), 16 mA (1734-OB4E) or 32 mA (1734-OB8E) from the external 24V DC supply, and the load current passes through the same supply. Add the simultaneous load current to that figure when selecting the 1734-FPD or 1734-EP24DC.
Related models, options and spare parts for this range are listed in the Allen-Bradley POINT I/O 1734 modules category.