Product Details:
Payment & Shipping Terms:
|
The 1734-TOP3 is a 12-terminal POINT I/O wiring base with a screw-clamp removable terminal block: the base mounts on the DIN rail, the I/O module snaps into it, and integrated one-piece block carries the field wiring.
Twelve terminals in a one-piece base: the high density slice footprint without a removable block in the way.
| 1734-TB | 8 terminal wiring base with removable screw-clamp RTB | IN STOCK |
| 1734-TB3 | 12 terminal wiring base with removable screw-clamp RTB3 | IN STOCK |
| 1734-TB3S | 12 terminal wiring base with removable spring-clamp RTB3S | IN STOCK |
| 1734-TOP | 8 terminal one-piece base, screw-clamp | IN STOCK |
| 1734-TOPS | 8 terminal one-piece base, spring-clamp | IN STOCK |
| 1734-TOP3 | 12 terminal one-piece base, screw-clamp | IN STOCK |
| 1734-TOP3S | 12 terminal one-piece base, spring-clamp | IN STOCK |
| 1734-CTM | Common terminal module, 2 A per point, 4 A per module | IN STOCK |
Number of terminations |
12 |
Termination type |
screw-clamp |
Wiring block |
integrated one-piece block |
Field power bus supply voltage |
28.8V DC, 120/240V AC |
Field power bus supply current, max |
10 A |
Signal terminal voltage, max |
28.8V DC, 120/240V AC |
Signal terminal current, max |
2 A |
Wire size |
0.25...2.5 mm2 (22...14 AWG), 75 deg C or greater, 1.2 mm insulation max |
Dimensions, HxWxD |
49 x 12 x 188 mm |
Weight, approx |
79.2 g |
Enclosure type rating |
None (open-style) |
Temperature, operating |
Dependent on the installed module, -20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN028 (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
0...3 are channels 0 and 1, 4/5 common, 6/7 supply, 8/9 common again, 10/11 supply again. The layout repeats the common and supply pairs so four channels fit without external jumpers, exactly as on the 1734-TB3.
79.2 g and 49 x 12 x 188 mm - 44 mm longer than the 8-terminal TOP. In a 63-module rack that length adds up: 20 high density slices consume an extra 880 mm of rail, which is the argument for counting rail length before specifying density.
Panels that are built once and wired in place, with the same crew, on a rail that has room. If the cabinet will be serviced by someone else, the removable RTB3 on a 1734-TB3 is the safer choice for the same 12 terminals.
Field power bus 10 A and signal terminals 2 A, at 28.8V DC or 120/240V AC. The 10 A figure is the bus capacity that the 1734-EP24DC and 1734-FPD modules are built around; the 2 A is per signal terminal, which is why an output slice rated 2 A per point uses the base at its limit rather than in the middle of its range. Isolation and voltage segregation come from the module that sits in the base, not from the base itself - the base is a passive wiring carrier.
Rockwell's removal sequence is explicit: remove the module in the base, then the module in the base to the right, then the RTB, then release the orange base locking screw and lift straight up. The base to the right has to come out because the interlocking side pieces and the POINTBus contacts overlap. Pulling a base with power applied interrupts the backplane and can cause unintended machine motion.
How many terminals does 1734-TOP3 have?
Twelve: 0...3 channels, 4/5 common, 6/7 supply, 8/9 common, 10/11 supply.
How long is the base on the rail?
49 x 12 x 188 mm, 44 mm longer than the 8-terminal 1734-TOP.
What is the weight?
79.2 g.
Does it need a removable terminal block?
No - it is a one-piece base, so wiring is done on the installed unit.
What are the current ratings?
10 A field power bus, 2 A per signal terminal, 28.8V DC or 120/240V AC.
1734-TOP3 is a POINT I/O terminal base assembly: a DIN-rail mounting base with a 12-terminal RTB, tall base profile. The base is ordered separately from the I/O module because the base and the RTB are the parts that carry the wiring, and the module is the part that is replaced on failure.
| Attribute | Value |
| Catalog number | 1734-TOP3 |
| Assembly type | 12-terminal RTB, tall base profile |
| Replacement RTB | 1734-RTB3 |
| Dimensions, H x W x D | 167.6 x 13.8 x 79.1 mm (6.60 x 0.54 x 3.11 in.) |
| Weight | 79.10 g (2.79 oz) |
| RTB function | All field terminations, removable without disturbing wiring |
| Terminal numbering | Marked on the bottom of the RTB |
| Related base | 1734-TBCJC adds cold junction compensation for 1734-IT2I |
Terminal count decides the base, not the module width: the eight-terminal bases suit modules with one termination per channel, and the twelve-terminal bases are needed where the module presents commons or shield returns in addition to the channel terminals. A two-point analog module needs a shield ground terminal point, which is why the analog side of the family runs on the wider bases.
The terminal base assembly is the part that makes POINT I/O modular: the base mounts on the DIN rail, the removable terminal block (RTB) carries every field termination, and the I/O module plugs onto both. The RTB is ordered with the base as one unit, and a spare RTB is a field-replaceable part rather than a whole new base.
Each terminal point is numbered on the bottom of the RTB, which is why a wiring fault can be traced from the drawing to a numbered terminal instead of to a wire colour. Once the RTB is wired, the block separates from the base and the module without disturbing the terminations, so a module swap does not require re-terminating a single field wire.
Every POINT I/O module mounts in a terminal base that is ordered separately, and the number of field terminals on the base has to match the module: eight terminals for single-point-per-channel digital modules, twelve where the module needs a common or a shield return per channel group.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
Producer/consumer behaviour is what makes the slice worth wiring this way: input data and output status can be shared among several Logix controllers without a second physical input module per controller, so the I/O count is set by field devices rather than by the number of controllers that need to see them.
Browse the Allen-Bradley POINT I/O 1734 modules category for the other models, options and spare parts that share this range.