Product Details:
Payment & Shipping Terms:
|
The 1734-ARM keeps a slot alive. When a POINT I/O module is pulled for repair and the machine has to keep running on the remaining slices, the ARM goes into that base and holds the address, so the controller's I/O image does not renumber.
That is the whole function: 75 mA of POINTBus current and a physical placeholder that tells the adapter the slot is still there and intentionally empty.
| 1734-AENT | EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus | IN STOCK |
| 1734-ADN | DeviceNet adapter, 125/250/500 kbit, 63 modules | IN STOCK |
| 1734-ADNX | DeviceNet adapter with Subnet scanner, node 0 on the subnet | IN STOCK |
| 1734-ACNR | ControlNet adapter, redundant coax A/B, node 01...99 | IN STOCK |
| 1734-APB | PROFIBUS DP adapter, 63 modules on one DP node | IN STOCK |
| 1734-PDN | DeviceNet communication interface, 24V DC 400 mA, 1.3 A POINTBus | IN STOCK |
| 1734-EP24DC | 24V DC expansion power supply, 1.3 A POINTBus at 19.2...28.8V input | IN STOCK |
| 1734-EPAC | 120/240V AC expansion power supply, 1.3 A POINTBus, 3250V DC isolation | IN STOCK |
| 1734-FPD | Field potential distributor, breaks the field power bus, no current draw | IN STOCK |
| 1734-ARM | Address reserve module, 75 mA POINTBus, keeps a slot addressed | IN STOCK |
Function |
Reserves an I/O slot address when a module is removed |
Module location |
1734-TB, TBS, TOP or TOPS wiring base assembly |
POINTBus current, max |
75 mA @ 5V DC |
Power dissipation, max |
0.375 W @ 5V DC |
Thermal dissipation, max |
1.3 BTU/hr @ 5V DC |
Status indicators |
1 green/red network status, 1 green/red module status, logic side |
Keyswitch position |
Use the keyswitch position of the removed module |
Field wiring terminals |
0 = no connection, 3 = protective earth ground, 4 = L2/N |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Weight, approx |
23.3 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN019 (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The ARM carries a network status and a module status indicator and nothing else - terminal 0 is explicitly no connection, 3 is protective earth ground and 4 is L2/N. It does not emulate the removed module's data; it keeps the slot from collapsing and shifting every module to its right down by one address.
Rockwell's instruction is to use the keyswitch position of the module that was removed. The mechanical keying on the base is what stops a wrong slice being fitted later, so matching the ARM to that position keeps the base's keying meaningful when the real module goes back in.
75 mA at 5V DC, 0.375 W dissipation, 1.3 BTU/hr. Small, but it counts against the 1.3 A POINTBus budget like any other slice - four ARMs in a rack is 300 mA of the budget spent on placeholders.
The same housing as an I/O module, so it occupies one slot and one base. Use it in a 1734-TB, TBS, TOP or TOPS base; the base stays wired and no field wiring is touched.
What is the 1734-ARM used for?
It reserves the I/O slot address when a module is removed, so the modules to the right keep their addresses in the controller's I/O image.
How much POINTBus current does it draw?
75 mA at 5V DC, with 0.375 W dissipation and 1.3 BTU/hr thermal dissipation.
Which keyswitch position should it use?
The keyswitch position of the module that was removed, so the base keying stays valid when the module is refitted.
What terminals does it have?
Terminal 0 is no connection, 3 is protective earth ground and 4 is L2/N; no I/O signal terminals are used.
What are its dimensions and weight?
56.6 x 12.1 x 77.5 mm and 23.3 g, the same housing as an I/O slice.
1734-ARM is a POINT I/O mounting and wiring accessory in the POINT I/O family. It mounts on a terminal base assembly that is ordered separately, connects to the POINTBus through the base, and presents its field wiring on the removable terminal block.
| Attribute | Value |
| Catalog number | 1734-ARM |
| Module type | POINT I/O mounting and wiring accessory |
| POINTBus current requirement | see module it serves |
| Module width | 12.1 mm (0.48 in.) standard, 24.1 mm (0.94 in.) for safety modules |
| Terminal base | Ordered separately: 1734-TB/TBS (8 terminal) or 1734-TB3/TB3S (12 terminal) |
| Module dimensions | 77.5 x 12.1 x 56.6 mm (3.05 x 0.48 x 2.23 in.), weight approx. 31-36 g |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Every POINT I/O module mounts in a terminal base that is ordered separately, and the number of field terminals on the base has to match the module: eight terminals for single-point-per-channel digital modules, twelve where the module needs a common or a shield return per channel group.
Sink/source and AC-input variants exist because the field device decides the wiring, not the module preference: a sinking input expects the field device to switch to the positive rail, a sourcing input expects it to switch to common, and an isolated AC input exists so that a shared common between channels does not create a path between two different field circuits.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
The system is rated for panel work rather than for a lab bench: modules plug onto bases that are already wired, the RTB stays on the wiring while the electronics come off, and the same base family accepts the next module of the same width. That is the reason a spare part for POINT I/O is usually an RTB or a base rather than a module, and why a maintenance stock built only from modules is incomplete.
This part sits in the Allen-Bradley POINT I/O 1734 modules category, with the other models and spare parts listed alongside it.