Product Details: |
The 1756-EN2T (also written 1756EN2T) is the single-port EtherNet/IP communication module for the Allen-Bradley ControlLogix 1756 platform: one copper RJ45 port at 10/100 Mbps, chassis mounted, one slot wide, bridging a ControlLogix controller to the plant Ethernet network.
Because it sits on the 1756 backplane, the module is also the network gateway for the whole chassis: ControlNet, DeviceNet, DH+/RIO, serial and motion modules in the same rack become reachable over one Ethernet drop, without an additional bridge. Its capacity is what separates it from the older 1756-ENBT — 128 TCP/IP connections, 256 CIP connections and 128 + 128 CIP unconnected messages, against 64 / 128 / 64 + 64 on the ENBT — so one module can carry explicit messaging (programming sessions, HMI, SCADA, MSG instructions) and implicit I/O at the same time.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
EtherNet/IP |
Brand Name |
Allen-Bradley (Rockwell Automation) |
Cat Num |
1756-EN2T |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1 Copper RJ45 (10/100 Mbps) |
Mounting |
Chassis |
Number Of Channels |
1 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Communication Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell Automation publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
I/O and drives. Remote 1756 I/O chassis, 1734 POINT I/O slices, 1794 FLEX I/O adapters and EtherNet/IP drives are reached through the single RJ45 port, so the drive cabinet can stand at the motor and the controller in the main panel, with no dedicated communication cable between them.
Supervision and data exchange. PanelView terminals, FactoryTalk View stations, scanners, vision systems and MSG / produced-consumed tag traffic share the same module, and the backplane bridge lets an Ethernet-only engineering workstation reach ControlNet, DeviceNet or DH+/RIO devices in the rack during a staged upgrade.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
Indicator |
State |
Meaning and action |
NET |
Off |
Not powered, or no valid IP address — check chassis power, seating, IP settings |
NET |
Flashing green |
IP address assigned, no CIP connection established — check the connection originator |
NET |
Solid green |
Normal operation — at least one CIP connection established |
NET |
Red |
Duplicate IP address in use — the display shows OK, the current IP and the duplicate MAC ID |
NET |
Flashing green / flashing red |
Power-up testing in progress — wait until the indicator settles |
LINK |
Off / green / flashing green |
Off: no link — check chassis power, cable and that the port is enabled; green: link up, no traffic; flashing green: traffic present |
OK |
Off / flashing green |
Off: no chassis power or the module is not fully seated in the backplane; flashing green: module not configured — the display scrolls BOOTP or DHCP with the MAC ID |
OK |
Solid green / flashing red |
Operating correctly / recoverable fault — usually cleared by re-downloading the configuration |
Indicator behaviour per Rockwell Automation publication 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and 1756-IN050.
Rockwell Automation declared the 1756-ENBT end of life on 1 November 2021 and names the 1756-EN2T as the engineered replacement (publication 1756-TD003). The swap keeps the panel design unchanged — same slot width, same chassis, same Studio 5000 workflow: record the existing IP address and connection list, fit the EN2T and set the same IP, install its EDS file and AOP profile on the engineering workstation, then change the catalogue number in the project and re-download.
One check is worth doing before ordering: backplane current rises from 700 mA to 1 A at 5.1 V DC per slot, i.e. 300 mA more per substituted module, so recalculate the 1756 power-supply budget when several slots are converted at once.
Q: What is the difference between 1756-EN2T and 1756EN2T?
A: They are the same module. 1756-EN2T is the catalogue number; 1756EN2T is the same number written without the hyphen, the form many search engines and ERP systems use.
Q: Can the 1756-EN2T be used in a device-level ring (DLR)?
A: No — it has one Ethernet port, so it cannot form a ring. For DLR redundancy use the dual-port 1756-EN2TR, for parallel redundancy (PRP) the 1756-EN2TP, and for extended temperature the 1756-EN2TXT.
Q: Which cable and connectors are required for the 1756-EN2T?
A: An RJ45 connector to IEC 60603-7 with 2- or 4-pair Category 5e minimum cable to TIA 568-B.1, or Category 5 to ISO/IEC 11801-3, shielded or unshielded. Standard copper Ethernet limits apply, so plan for a maximum 100 m run to the next switch.
Q: Can the 1756-EN2T be replaced with the rack powered on?
A: Yes — removal and insertion under power (RIUP) is supported, and the replacement must go into the same slot so the existing configuration and connections are kept. In a hazardous location, confirm the area is non-hazardous first: inserting or removing the module with backplane power applied can produce an arc.
Q: What are the environmental ratings and certifications of the 1756-EN2T?
A: Open-style and one slot wide, rated 0…60 °C (32…140 °F), 5…95 % RH non-condensing, 2 g vibration at 10…500 Hz, 30 g shock, temperature code T4. Certifications per publication 1756-TD003 Table 6: c-UL-us to UL File E65584, with UL Listing for Class I Division 2 Groups A–D under UL File E194810; CSA File LR54689C, Division 2 under CSA File LR69960C; CE to the 2014/30/EU EMC Directive (EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2); RCM; ATEX to 2014/34/EU, II 3 G Ex ec IIC T4 Gc, certificate UL 22 ATEX 2818X; UKEX UL22UKEX2604X; UKCA; FM Approval for Class I Division 2. EtherNet/IP is ODVA conformance tested. IECEx is not held by the single-port EN2T — that certificate (IECEx UL 22.0063X) applies to the dual-port 1756-EN2TR and 1756-EN3TR.