Product Details:
Payment & Shipping Terms:
|
1746-NI8 is the 8 Point Analog Input Module in the Allen-Bradley SLC 500 range: 1746 SLC System, (8) Analog Input For Programmable Controller.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-NI4 | 4 Point Analog Input Module | IN STOCK |
| 1746-NI8 | 8 Point Analog Input Module | IN STOCK |
| 1746-NI16I | 16 Point Analog Input Module | IN STOCK |
| 1746-NI16V | 16 Point Analog Voltage Input Module | IN STOCK |
Application |
1746 SLC System, (8) Analog Input For Programmable Controller |
Cat Num |
1746-NI8 |
Brand Name |
Rockwell |
Product Type |
8 Point Analog Input Module |
Channels |
8 single-ended, channel-to-channel configurable |
Input range |
±10V dc, 0...10V dc, 0...5V dc, 1...5V dc, ±20 mA, 0...20 mA, 4...20 mA, 0...1 mA |
Resolution |
16-bit |
Backplane current, 5V DC |
200 mA |
Backplane current, 24V DC |
100 mA |
Update time / filtering |
Filter 1...75 Hz, step response 0.75...730 ms at 99% |
Isolation |
500V ac and 710V dc for 60 s |
Lifecycle |
Discontinued |
Discontinued date |
September 30, 2024 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-UM020 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: 1746 SLC System, (8) Analog Input For Programmable Controller.
8 Point Analog Input Module with 8 single-ended, channel-to-channel configurable.
Application: 1746 SLC System, (8) Analog Input For Programmable Controller.
Cat Num: 1746-NI8.
Brand Name: Rockwell.
Product Type: 8 Point Analog Input Module.
Channels: 8 single-ended, channel-to-channel configurable.
Input range: ±10V dc, 0...10V dc, 0...5V dc, 1...5V dc, ±20 mA, 0...20 mA, 4...20 mA, 0...1 mA.
Resolution: 16-bit.
Backplane current, 5V DC: 200 mA.
Backplane current, 24V DC: 100 mA.
Update time / filtering: Filter 1...75 Hz, step response 0.75...730 ms at 99%.
Isolation: 500V ac and 710V dc for 60 s.
Lifecycle: Discontinued.
Discontinued date: September 30, 2024.
Replacement category: Engineering Replacement.
Every input channel is configured in the user program, not with jumpers: the NI4 uses four DIP switches for current or voltage selection, while the NI8 and NI16 are software configured and can be re-ranged without interrupting the processor.
A current input is a 249 Ω burden on the loop for the NI16I, so the transmitter needs enough compliance to drive the loop impedance plus the card; a voltage input is 20 MΩ on the NI16V and 760 kΩ on the NI4.
The module does not supply loop power. An unpowered 4...20 mA transmitter reads as a negative out-of-range value, which is the diagnostic that tells an open loop from a failed sensor.
Rockwell lists 1746-NI8 as Discontinued, discontinued date September 30, 2024, replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V ac and 710V dc for 60 s between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-NI8?
1746 SLC System, (8) Analog Input For Programmable Controller. 8 Point Analog Input Module.
How many channels does 1746-NI8 have?
8 single-ended, channel-to-channel configurable.
What ranges does 1746-NI8 accept?
Inputs: ±10V dc, 0...10V dc, 0...5V dc, 1...5V dc, ±20 mA, 0...20 mA, 4...20 mA, 0...1 mA.
How much backplane current does 1746-NI8 draw?
200 mA at 5V dc and 100 mA at 24V dc.
Is 1746-NI8 still available?
Rockwell lists it as Discontinued, discontinued date September 30, 2024, replacement category Engineering Replacement.
Analog modules are the expensive ones on an SLC backplane: one 8-channel input can draw more 5 V current than six digital modules. The table below prints channels, range, resolution and both backplane currents for the modules of the same analog group, so a rack can be sized on current rather than on the channel count in a quotation.
| Catalog | Channels | Range printed | Resolution | 5 V backplane | 24 V backplane | Update |
| 1746-NI4 | 4 differential, voltage or current selectable per channel | ±10V dc, 0...10V dc, 0...5V dc, 1...5V dc, ±20 mA, 0...20 mA, 4...20 mA | 16-bit, 305.176 µV/LSB on ±10V, 1.22070 µA/LSB on ±20 mA | 35 mA | 85 mA | 512 µs for all channels in parallel |
| 1746-NI8 | 8 single-ended, channel-to-channel configurable | ±10V dc, 0...10V dc, 0...5V dc, 1...5V dc, ±20 mA, 0...20 mA, 4...20 mA, 0...1 mA | 16-bit | 200 mA | 100 mA | Filter 1...75 Hz, step response 0.75...730 ms at 99% |
| 1746-NI16I | 16 single-ended current inputs | 0...20 mA, 4...20 mA, ±20 mA, 0...1 mA | 16-bit, input resolution 640 nA | 125 mA | 75 mA | Sigma-Delta, filter 6/10/20/40/60/80/100/250 Hz |
| 1746-NI16V | 16 single-ended voltage inputs | ±10V dc, 0...10V dc, 0...5V dc, 1...5V dc | 16-bit, input resolution 312 µV | 125 mA | 75 mA | Sigma-Delta, filter 6/10/20/40/60/80/100/250 Hz |
Where this module sits: What the rack feels is the backplane current, not the channel count: 1746-NI8 is 200 mA at 5 V and 100 mA at 24 V. Added up, on the 5 A 1746-P2 the 5 V rail carries 25 and the 24 V rail carries 9, so the 24 V rail binds first at 9 modules, and that is below the thirteen slots of an A13.
Two things this block does not answer. It gives the module current, not the surge a rack sees at power-up, which is printed separately as inrush for the supply and not per module. And it says nothing about the 24 V field supply drawn by the loads themselves - the 24 V backplane figure is what the module takes from the rack, not what the sensors and coils take from the field supply.
Source: Rockwell 1746-IN027 digital I/O specification rows, 1746-IN008 and 1746-UM007 analog rows, 1746-IN016/IN004 chassis and supply rows. Backplane currents are quoted as printed; only the "how many fit" divisions are arithmetic, and they are integer divisions of the printed capacity.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.