Product Details:
Payment & Shipping Terms:
|
1746-P1 is the rack mounting power supply for the SLC 500 modular system: 1746 SLC System, Power Supply - Rack Mount, 120/240 VAC, 2A.
It converts the panel supply into the two backplane rails the cards draw from, 5V dc and 24V dc, and on most versions into a small isolated 24V dc source for sensors.
| 1746-P1 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P2 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P3 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P4 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P5 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P6 | SLC Rack Mounting Power Supply | IN STOCK |
| 1746-P7 | SLC Rack Mounting Power Supply | IN STOCK |
Application |
1746 SLC System, Power Supply - Rack Mount, 120/240 VAC, 2A |
Cat Num |
1746-P1 |
Brand Name |
Rockwell |
Product Type |
SLC 500 rack mounting power supply |
Line voltage |
85...132 / 170...265V ac, 47...63 Hz |
Typical line power requirement |
135 VA typical |
Inrush current, max |
20 A max |
Internal capacity, 5V dc |
2 A at 5V dc |
Internal capacity, 24V dc |
0.46 A at 24V dc |
24V dc user-power output |
200 mA at 18...30V dc |
Isolation |
1800V ac RMS for 1 s |
Fuse protection |
1746-F1 or equivalent, replaceable |
Dimensions, W x D x H |
65 x 140 x 140 mm |
Temperature, ambient operating |
0...60 °C (32...140 °F) |
Lifecycle |
Discontinued |
Discontinued date |
September 30, 2020 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN004 (module specifications) and 1746-IN004 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Rockwell description: 1746 SLC System, Power Supply - Rack Mount, 120/240 VAC, 2A.
The supply bolts to the left end of the chassis and feeds the backplane; it is not a slot card and it does not consume a slot address.
Application: 1746 SLC System, Power Supply - Rack Mount, 120/240 VAC, 2A.
Cat Num: 1746-P1.
Brand Name: Rockwell.
Product Type: SLC 500 rack mounting power supply.
Line voltage: 85...132 / 170...265V ac, 47...63 Hz.
Typical line power requirement: 135 VA typical.
Inrush current, max: 20 A max.
Internal capacity, 5V dc: 2 A at 5V dc.
Internal capacity, 24V dc: 0.46 A at 24V dc.
24V dc user-power output: 200 mA at 18...30V dc.
Isolation: 1800V ac RMS for 1 s.
Fuse protection: 1746-F1 or equivalent, replaceable.
Dimensions, W x D x H: 65 x 140 x 140 mm.
Temperature, ambient operating: 0...60 °C (32...140 °F).
Lifecycle: Discontinued.
Discontinued date: September 30, 2020.
Replacement category: Engineering Replacement.
The 5V dc and 24V dc figures above are the supply's internal capacity. Every card in the rack draws from them, and the sum has to stay inside both rails at the same time, not just inside the larger one.
The 24V dc user output is a separate, isolated source for field devices. On the 1746-P4 the total of backplane and user power cannot exceed 70 W, so a fully loaded 10 A rack leaves little for sensors.
Capacity is derated 5 percent above 55 °C on the P1, P2, P4, P5 and P6, which matters in a sealed panel where the internal temperature runs above the ambient figure.
The P1, P2 and P4 have an input voltage jumper that has to be set before power is applied; the P3, P5, P6 and P7 have no jumper. Setting the jumper with the supply energised exposes line voltage on the pins.
The ground screw goes to the nearest ground bus with 1.68 mm² (#14 AWG) 75 °C copper, and the incoming terminals take the same wire, tightened to 0.8 N·m (7 lb-in).
Hold-up time is what the controller keeps scanning after the line drops. The P5 holds the CPU for 20 ms at full load, the P6 for 5 ms, and the P7 for 40 ms at 24V dc input and full load; the P7 also latches off if the input sits between 4V and 9V until it is raised to 11V dc.
Rockwell lists 1746-P1 as discontinued, date September 30, 2020, replacement category Engineering Replacement.
Rockwell prints no replacement catalog number on the product page, so a failed supply is replaced from stock or the rack is migrated.
A power supply is the part that decides how much I/O a rack can hold, so a spare is normally kept at the same current rating rather than at the same physical size.
What is 1746-P1?
1746 SLC System, Power Supply - Rack Mount, 120/240 VAC, 2A. Rack mounting power supply for the SLC 500 modular system.
What input voltage does 1746-P1 accept?
85...132 / 170...265V ac, 47...63 Hz.
How much current does 1746-P1 give the backplane?
2 A at 5V dc at 5V dc and 0.46 A at 24V dc at 24V dc.
Can 1746-P1 power field sensors?
200 mA at 18...30V dc.
Is 1746-P1 still available?
Rockwell lists it as discontinued, date September 30, 2020, replacement category Engineering Replacement.
1746-P1 is a chassis power supply for SLC 500 modular systems. It mounts on the left end of the 1746 chassis and supplies both backplane rails; the processor and the I/O modules draw from it, and the two rails are budgeted separately.
Remote I/O changes the data path, not the module: with a 1747-ASB adapter in the remote chassis, analog and thermocouple modules require block transfers, and a program written as direct I/O in a local chassis does not simply move to a remote one. The 1746-NO4I and 1746-NO4V analog outputs also accept a user-supplied 24V DC source, and that source must be 24V plus or minus 10 percent; the 1746-P1, P2, P5 and P6 user supplies do not meet that tolerance.
Power supply selection is a two-rail comparison, not a wattage comparison: 1746-P1 gives 2.0 A at 5V and 0.46 A at 24V, 1746-P2 gives 5.0 A and 0.96 A, 1746-P3 gives 3.6 A and 0.87 A from a 19.2 to 28.8V DC input, and 1746-P4 gives 10.0 A and 2.88 A with a 70 W total limit across all outputs. Choosing by input voltage alone and ignoring the 24V allowance is how a chassis ends up short on analog capacity.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
The processor or the I/O adapter occupies the left-most slot of a 1746 chassis, and the power supply is a separate unit mounted on the left end of the chassis rather than a module inside it. That is why a spare chassis is not a spare system: chassis, power supply and processor are three catalog numbers, and the interconnect cable is a fourth.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
The Allen-Bradley SLC 500 1746 I/O modules category lists the related catalog numbers, options and accessories for this range.