Product Details:
Payment & Shipping Terms:
|
The 1769-OA16 (also written 1769OA16) is the sixteen-point triac output of the Compact I/O 1769 range: eight points per group, two groups, switching 85…265V AC loads directly from the PLC without an interposing relay.
It is the highest 5.1V draw of the 1769 digital family at 225 mA, because a triac output has to hold gate drive on every conducting point. That number, not the field current, is what usually decides whether the bank supply has room for it.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-OA16 |
Brand Name |
Rockwell |
Outputs |
16 (8 points per group) |
Voltage category |
100/240V AC |
Operating voltage range |
85…265V AC, 47…63 Hz |
Output delay, on / off |
1/2 cycle / 1/2 cycle |
Current draw @ 5.1V |
225 mA |
Heat dissipation, max |
4.9 W |
Off-state leakage, max |
2.0 mA @ 132V AC; 2.5 mA @ 265V AC |
On-state current, min |
10 mA |
On-state voltage drop, max |
1.5V peak @ 2 A |
Current per point |
0.25 A @ 60 °C; 0.5 A @ 30 °C |
Current per module |
2 A @ 60 °C; 4 A @ 30 °C |
Surge current |
5 A for 25 ms, repeatable every 2 s |
Isolation |
1836V AC 1 s or 2596V DC 1 s, output point to bus; 265V AC working voltage |
Slot width / weight |
1.5 slot / 280 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
How many outputs does 1769-OA16 have?
Sixteen, in two groups of eight, each group with its own AC supply terminal and able to run on a different feed.
What is the minimum load for 1769-OA16?
10 mA. A triac output below that holding current may not latch — small contactor coils are the usual failure, and a loading resistor in parallel with the coil is the fix.
How much current can 1769-OA16 switch per point?
0.5 A at 30 °C and 0.25 A at 60 °C, with 4 A and 2 A per module respectively. Design on the temperature the cabinet actually reaches.
What does 1769-OA16 draw from the backplane?
225 mA at 5.1V with 4.9 W maximum heat dissipation — the highest 5.1V draw in the 1769 digital range, one and a half slots, 280 g.
What AC voltage range does 1769-OA16 switch?
85…265V AC at 47…63 Hz, rated 100/240V AC, with zero-cross switching so the delay is half a cycle on and half a cycle off.
Why does the indicator glow when 1769-OA16 output is off?
Off-state leakage is up to 2.0 mA at 132V AC and 2.5 mA at 265V AC. That is enough for a neon or LED pilot; a loading resistor in parallel with the load removes it.
What is the surge rating of 1769-OA16?
5 A for 25 ms, repeatable every 2 s — enough for incandescent lamp and small solenoid inrush, not for a motor starter coil without a suppressor.
This part sits in the Allen-Bradley CompactLogix 1769 controllers category, with the other models and spare parts listed alongside it.