1747-L524 is the SLC 5/02 controller for the SLC 500 modular platform: 4 K instructions of program memory, 4096 discrete of local I/O addressing, and DH-485 (channel 0).
It sits in the first slot of the first 1746 chassis and is powered from a 1746-P1…P7 supply. Rockwell lists the catalog number as discontinued on 2017-01-31 with replacement category Functional Replacement.
| 1747-L511 | SLC 5/01 modular processor, 1 K instructions | IN STOCK |
| 1747-L514 | SLC 5/01 modular processor, 4 K instructions | IN STOCK |
| 1747-L524 | SLC 5/02 modular processor, 4 K instructions | IN STOCK |
| 1747-L531 | SLC 5/03 modular processor, 8 K instructions | IN STOCK |
| 1747-L533 | SLC 5/03 modular processor, 32 K instructions | IN STOCK |
| 1747-L542 | SLC 5/04 modular processor, 32 K instructions | IN STOCK |
| 1747-L543 | SLC 5/04 modular processor, 64 K instructions | IN STOCK |
| 1747-L551 | SLC 5/05 modular processor, 16 K instructions | IN STOCK |
| 1747-L552 | SLC 5/05 modular processor, 32 K instructions | IN STOCK |
| 1747-L553 | SLC 5/05 modular processor, 64 K instructions | IN STOCK |
Catalog number |
1747-L524 |
Series |
SLC 5/02 |
Program memory |
4 K instructions (words) |
Local I/O capacity |
4096 discrete |
Communication |
DH-485 (channel 0) |
Memory back-up |
1747-BA lithium, about 2 years |
Backplane current, 5V dc |
500 mA |
Backplane current, 24V dc |
175 mA |
Chassis and slots |
Up to 3 chassis / 30 I/O slots |
Operating temperature |
0…60 °C (32…140 °F) |
Discontinued date |
2017-01-31 |
Replacement category |
Functional Replacement |
Replacement product |
No same-series successor published |
Publication |
1747-IN009 / 1747-UM011 |
Same-family catalog numbers: 1747-L511, 1747-L514, 1747-L531, 1747-L533. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1747 family.
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1747-IN009 (module specifications) and 1747-IN009 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The SLC 500 modular family runs from the 5/01 through the 5/05. Memory, I/O addressing and the communication channel change between series; the chassis, the I/O modules and the power supplies do not. A SLC 5/02 therefore drops into the same 1746 rack as any other modular processor, which is why mixed fleets of 5/01 to 5/05 controllers still share spare racks and I/O in the field.
This catalog number carries 4 K instructions of program memory and addresses 4096 discrete. PID, indexed addressing, interrupts, user fault routines, 32-bit signed math, DH-485 initiator.
Program memory in this series is user configurable between program and data storage. Across the modular family Rockwell prints a typical program scan of 0.9…8.0 ms per K of instructions depending on the processor, and an I/O scan of 0.25…2.6 ms depending on the processor and the modules installed. The SLC 5/02 sits at the slower end of that range.
I/O addressing stops at 4096 discrete on this processor, and Rockwell caps a modular system at three chassis with 30 I/O slots in total. The limit that actually bites in a retrofit is usually the chassis count, not the point count.
DH-485 (channel 0). Channel 0 is configured as DTE on the 5/03 and later, with the same pinout as a 9-pin personal computer port, so a 1747-CP3 cable reaches it directly. On the 5/01 and 5/02 the single DH-485 channel answers message commands but does not initiate them.
Programming is done with RSLogix 500 over DH-485, either through a 1747-UIC USB converter or, on the 5/03 and later, through the RS-232 channel 0 with a 1747-CP3 cable.
The processor draws 500 mA at 5V dc and 175 mA at 24V dc from the backplane, so it has to be counted against the 1746 supply budget together with every I/O module in the rack. 1747-BA lithium, about 2 years keeps the RAM alive when the rack is off.
Rockwell prints 0…60 °C operating, -40…85 °C storage, 5…95% humidity without condensation, 2.5 g vibration at 5…2000 Hz, and 1500V ac dielectric withstand for the system. Communication circuits are isolated at 500V dc.
Rockwell discontinued the catalog number on 2017-01-31. The replacement category on record is Functional Replacement, with No same-series successor published listed as the replacement product. For a plant that already runs SLC 500, the practical route is either to hold tested spares of the exact catalog number or to plan a migration to a current controller family; a like-for-like 1747 processor cannot be bought new from Rockwell any more.
When buying on the secondary market, check three things before the module goes into a rack: the series letter on the label, the firmware revision reported by the programming software once the processor is online, and the battery date code on the 1747-BA inside. A processor with a flat battery loses its program on the next power cycle.
Is 1747-L524 still available new from Rockwell?
No. Rockwell lists it as discontinued as of 2017-01-31, with replacement category Functional Replacement.
What replaces 1747-L524?
Rockwell records No same-series successor published as the replacement product for this catalog number.
How much program memory does 1747-L524 have?
4 K instructions of program memory, addressing up to 4096 discrete of local I/O.
Which battery does 1747-L524 use?
1747-BA lithium, about 2 years. The battery is a field-replaceable item on the processor front.
Can 1747-L524 run in a 1746 chassis with a standard 1746 power supply?
Yes. It occupies the first slot of the first chassis and draws 500 mA at 5V dc and 175 mA at 24V dc from a 1746-P1…P7 supply.
Ten SLC 500 processors share one chassis family and differ in three numbers: program memory, the discrete I/O ceiling, and how much 5 V backplane current the processor itself takes before any I/O module is added. The last one matters because the processor and the I/O hang on the same supply, so a 1 A processor leaves less room than a 90 mA one in the same rack.
| Processor | Series | Memory | Discrete I/O | Communication channels | 5 V backplane |
| 1747-L511 | SLC 5/01 | 1 K instructions | 3940 discrete | DH-485 (channel 0) | 90 mA |
| 1747-L514 | SLC 5/01 | 4 K instructions | 3940 discrete | DH-485 (channel 0) | 90 mA |
| 1747-L524 | SLC 5/02 | 4 K instructions | 4096 discrete | DH-485 (channel 0) | 500 mA |
| 1747-L531 | SLC 5/03 | 8 K instructions | 4096 discrete | DH-485 (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L533 | SLC 5/03 | 32 K instructions | 4096 discrete | DH-485 (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L542 | SLC 5/04 | 32 K instructions | 4096 discrete | Data Highway Plus (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L543 | SLC 5/04 | 64 K instructions | 4096 discrete | Data Highway Plus (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L551 | SLC 5/05 | 16 K instructions | 4096 discrete | 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L552 | SLC 5/05 | 32 K instructions | 4096 discrete | 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L553 | SLC 5/05 | 64 K instructions | 4096 discrete | 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) | 1 A |
Where this processor sits: Read the ladder by column: at SLC 5/02 the draw is 500 mA, the ceiling is 4096 discrete, and its 4 K is one step above 1 K and one below 8 K. 3940 is printed only on the two 5/01 processors; from the 5/02 up the ceiling reads 4096.
What this ladder does not carry is timing: instruction execution times and scan times are printed per instruction class in 1747-RM001 and are not reproduced here, so the memory column tells you how much program fits and not how fast it runs. The discrete I/O figure is the addressable ceiling, not a slot count - the chassis still decides how many modules can physically be fitted.
Source: Rockwell 1747-IN009, 1747-IN007, 1747-IN019, 1747-IN062, 1747-UM011 and 1747-RM001 as recorded per catalog number, plus the Rockwell product page for each number. Every figure is quoted as printed; no value is calculated.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1747 processors and chassis category.