Product Details:
Payment & Shipping Terms:
|
1747-L552 is the SLC 5/05 controller for the SLC 500 modular platform: 32 K instructions of program memory, 4096 discrete of local I/O addressing, and 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0).
It sits in the first slot of the first 1746 chassis and is powered from a 1746-P1…P7 supply. Rockwell lists the catalog number as discontinued on 2024-03-31 with replacement category Engineering Replacement.
| 1747-L511 | SLC 5/01 modular processor, 1 K instructions | IN STOCK |
| 1747-L514 | SLC 5/01 modular processor, 4 K instructions | IN STOCK |
| 1747-L524 | SLC 5/02 modular processor, 4 K instructions | IN STOCK |
| 1747-L531 | SLC 5/03 modular processor, 8 K instructions | IN STOCK |
| 1747-L533 | SLC 5/03 modular processor, 32 K instructions | IN STOCK |
| 1747-L542 | SLC 5/04 modular processor, 32 K instructions | IN STOCK |
| 1747-L543 | SLC 5/04 modular processor, 64 K instructions | IN STOCK |
| 1747-L551 | SLC 5/05 modular processor, 16 K instructions | IN STOCK |
| 1747-L552 | SLC 5/05 modular processor, 32 K instructions | IN STOCK |
| 1747-L553 | SLC 5/05 modular processor, 64 K instructions | IN STOCK |
Catalog number |
1747-L552 |
Series |
SLC 5/05 |
Program memory |
32 K instructions (words) |
Local I/O capacity |
4096 discrete |
Communication |
10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) |
Memory back-up |
1747-BA lithium, about 2 years |
Backplane current, 5V dc |
1 A |
Backplane current, 24V dc |
0 mA |
Chassis and slots |
Up to 3 chassis / 30 I/O slots |
Operating temperature |
0…60 °C (32…140 °F) |
Discontinued date |
2024-03-31 |
Replacement category |
Engineering Replacement |
Replacement product |
No direct 1747 successor published |
Publication |
1747-IN009 / 1747-UM011 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1747-IN009 (module specifications) and 1747-IN009 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The SLC 500 modular family runs from the 5/01 through the 5/05. Memory, I/O addressing and the communication channel change between series; the chassis, the I/O modules and the power supplies do not. A SLC 5/05 therefore drops into the same 1746 rack as any other modular processor, which is why mixed fleets of 5/01 to 5/05 controllers still share spare racks and I/O in the field.
This catalog number carries 32 K instructions of program memory and addresses 4096 discrete. Embedded web server from FRN 5, BOOTP, SNMP, Modbus RTU master, DF1 full/half duplex, ASCII I/O.
Program memory in this series is user configurable between program and data storage. Across the modular family Rockwell prints a typical program scan of 0.9…8.0 ms per K of instructions depending on the processor, and an I/O scan of 0.25…2.6 ms depending on the processor and the modules installed. The SLC 5/05 sits at the faster end of that range.
I/O addressing stops at 4096 discrete on this processor, and Rockwell caps a modular system at three chassis with 30 I/O slots in total. The limit that actually bites in a retrofit is usually the chassis count, not the point count.
10/100Base-T Ethernet (channel 1) and RS-232 (channel 0). Channel 0 is configured as DTE on the 5/03 and later, with the same pinout as a 9-pin personal computer port, so a 1747-CP3 cable reaches it directly. On the 5/01 and 5/02 the single DH-485 channel answers message commands but does not initiate them.
Programming is done with RSLogix 500 over the channel that the processor exposes. On a 5/05 the Ethernet channel also carries an embedded web server from FRN 5 onwards, which shows module information, TCP/IP configuration, diagnostics, the data table memory map and the data table monitor in a browser.
The processor draws 1 A at 5V dc and 0 mA at 24V dc from the backplane, so it has to be counted against the 1746 supply budget together with every I/O module in the rack. 1747-BA lithium, about 2 years keeps the RAM alive when the rack is off.
Rockwell prints 0…60 °C operating, -40…85 °C storage, 5…95% humidity without condensation, 2.5 g vibration at 5…2000 Hz, and 1500V ac dielectric withstand for the system. Communication circuits are isolated at 500V dc.
Rockwell discontinued the catalog number on 2024-03-31. The replacement category on record is Engineering Replacement, with No direct 1747 successor published listed as the replacement product. For a plant that already runs SLC 500, the practical route is either to hold tested spares of the exact catalog number or to plan a migration to a current controller family; a like-for-like 1747 processor cannot be bought new from Rockwell any more.
When buying on the secondary market, check three things before the module goes into a rack: the series letter on the label, the firmware revision reported by the programming software once the processor is online, and the battery date code on the 1747-BA inside. A processor with a flat battery loses its program on the next power cycle.
Is 1747-L552 still available new from Rockwell?
No. Rockwell lists it as discontinued as of 2024-03-31, with replacement category Engineering Replacement.
What replaces 1747-L552?
Rockwell records No direct 1747 successor published as the replacement product for this catalog number.
How much program memory does 1747-L552 have?
32 K instructions of program memory, addressing up to 4096 discrete of local I/O.
Which battery does 1747-L552 use?
1747-BA lithium, about 2 years. The battery is a field-replaceable item on the processor front.
Can 1747-L552 run in a 1746 chassis with a standard 1746 power supply?
Yes. It occupies the first slot of the first chassis and draws 1 A at 5V dc and 0 mA at 24V dc from a 1746-P1…P7 supply.
Ten SLC 500 processors share one chassis family and differ in three numbers: program memory, the discrete I/O ceiling, and how much 5 V backplane current the processor itself takes before any I/O module is added. The last one matters because the processor and the I/O hang on the same supply, so a 1 A processor leaves less room than a 90 mA one in the same rack.
| Processor | Series | Memory | Discrete I/O | Communication channels | 5 V backplane |
| 1747-L511 | SLC 5/01 | 1 K instructions | 3940 discrete | DH-485 (channel 0) | 90 mA |
| 1747-L514 | SLC 5/01 | 4 K instructions | 3940 discrete | DH-485 (channel 0) | 90 mA |
| 1747-L524 | SLC 5/02 | 4 K instructions | 4096 discrete | DH-485 (channel 0) | 500 mA |
| 1747-L531 | SLC 5/03 | 8 K instructions | 4096 discrete | DH-485 (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L533 | SLC 5/03 | 32 K instructions | 4096 discrete | DH-485 (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L542 | SLC 5/04 | 32 K instructions | 4096 discrete | Data Highway Plus (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L543 | SLC 5/04 | 64 K instructions | 4096 discrete | Data Highway Plus (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L551 | SLC 5/05 | 16 K instructions | 4096 discrete | 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L552 | SLC 5/05 | 32 K instructions | 4096 discrete | 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) | 1 A |
| 1747-L553 | SLC 5/05 | 64 K instructions | 4096 discrete | 10/100Base-T Ethernet (channel 1) and RS-232 (channel 0) | 1 A |
Where this processor sits: Read the ladder by column: at SLC 5/05 the draw is 1 A, the ceiling is 4096 discrete, and its 32 K is one step above 16 K and one below 64 K. 3940 is printed only on the two 5/01 processors; from the 5/02 up the ceiling reads 4096.
What this ladder does not carry is timing: instruction execution times and scan times are printed per instruction class in 1747-RM001 and are not reproduced here, so the memory column tells you how much program fits and not how fast it runs. The discrete I/O figure is the addressable ceiling, not a slot count - the chassis still decides how many modules can physically be fitted.
Source: Rockwell 1747-IN009, 1747-IN007, 1747-IN019, 1747-IN062, 1747-UM011 and 1747-RM001 as recorded per catalog number, plus the Rockwell product page for each number. Every figure is quoted as printed; no value is calculated.
The Allen-Bradley SLC 500 1747 processors and chassis category lists the related catalog numbers, options and accessories for this range.