Product Details:
Payment & Shipping Terms:
|
1746-OW16 is the 16 Point Relay Output Module in the Allen-Bradley SLC 500 range: 1746 SLC System, 16 ch-Relay Output Module For Programmable Controller.
It sits in an SLC 500 chassis slot and exchanges data with the processor through the backplane image table; the points, voltage category and backplane current below are what decide whether it fits the slot and the power budget.
| 1746-OW4 | 4 Point Relay Output Module | IN STOCK |
| 1746-OW8 | 8 Point Relay Output Module | IN STOCK |
| 1746-OW16 | 16 Point Relay Output Module | IN STOCK |
| 1746-OX8 | 8 Point Isolated Relay Output Module | IN STOCK |
Application |
1746 SLC System, 16 ch-Relay Output Module For Programmable Controller |
Cat Num |
1746-OW16 |
Brand Name |
Rockwell |
Product Type |
16 Point Relay Output Module |
Points |
16 outputs |
Points per common |
8 |
Voltage category |
AC/DC relay contact output |
Operating voltage |
5...265V AC or 5...125V DC |
Backplane current, 5V DC |
0.090 A |
Backplane current, 24V DC |
0.070 A |
Signal delay, max |
Relay contact, 10 ms typical |
Isolation |
1500V, electro-optical to control logic |
Lifecycle |
Discontinued |
Discontinued date |
November 24, 2022 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN027 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: 1746 SLC System, 16 ch-Relay Output Module For Programmable Controller.
16 Point Relay Output Module, with 16 outputs and 8 per common terminal.
Application: 1746 SLC System, 16 ch-Relay Output Module For Programmable Controller.
Cat Num: 1746-OW16.
Brand Name: Rockwell.
Product Type: 16 Point Relay Output Module.
Points: 16 outputs.
Points per common: 8.
Voltage category: AC/DC relay contact output.
Operating voltage: 5...265V AC or 5...125V DC.
Backplane current, 5V DC: 0.090 A.
Backplane current, 24V DC: 0.070 A.
Signal delay, max: Relay contact, 10 ms typical.
Isolation: 1500V, electro-optical to control logic.
Lifecycle: Discontinued.
Discontinued date: November 24, 2022.
Replacement category: Engineering Replacement.
A relay output is a dry contact, so one card can switch a 120V AC coil and a 24V DC solenoid within the published per-point and per-module current.
A relay contact has a finite electrical life at rated load; a point that switches often is better served by an interposing relay than by the card itself.
The isolated version, 1746-OX8, gives each of the eight contacts its own common, which is what a circuit with separate supplies needs.
Rockwell lists 1746-OW16 as Discontinued, with the discontinued date November 24, 2022 and the replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution rather than a direct part-for-part swap.
Rockwell's own migration guidance for Bulletin 1746 I/O points to the Compact 5000 I/O platform with a Logix controller; a machine that stays on SLC 500 is served from the secondary market.
The enclosure, the terminal armature and the address assignment are unchanged when a card is replaced by the same catalog number, which is why the original number keeps a value after the end of sale.
A modular SLC 500 chassis reserves slot 0 for the processor or the adapter, so this card goes in any other I/O slot; a fixed controller chassis has a published power limit instead of a slot rule.
The backplane current above is added to the draw of every other card in the chassis and compared with the chassis supply before a card is added, which is the check that prevents an intermittent chassis fault after a retrofit.
Electro-optical isolation between the field terminals and the control logic is 1500V, and the operating range of the whole family is 0...60 °C with 5...95% noncondensing humidity and NEMA ICS 2-230 noise immunity.
The card in red in the table at the top is the one on this page.
What is 1746-OW16?
1746 SLC System, 16 ch-Relay Output Module For Programmable Controller. 16 Point Relay Output Module.
How many points does 1746-OW16 have?
16 outputs, 8 per common.
What voltage does 1746-OW16 work at?
AC/DC relay contact output, operating range 5...265V AC or 5...125V DC.
Is 1746-OW16 still available?
Rockwell lists it as Discontinued with the discontinued date November 24, 2022, replacement category Engineering Replacement.
What has to be checked before fitting 1746-OW16?
The backplane current against the chassis supply, the sinking or sourcing convention of the field devices, and the terminal block, which is removable and often missing on a used card.
Every 1746 digital module is one slot wide, so slot count is never the constraint in an SLC rack - the 5 V and 24 V backplane currents are. This table is the printed current for each module in the same functional group, taken from the 1746-IN027 specification rows, so the budget can be added up before the rack is ordered instead of after it browns out.
| Catalog | Points | Signal | 5 V backplane | 24 V backplane | Signal delay |
| 1746-OW4 | 4 outputs | AC/DC relay contact output | 0.030 A | 0.025 A | Relay contact, 10 ms typical |
| 1746-OW8 | 8 outputs | AC/DC relay contact output | 0.060 A | 0.045 A | Relay contact, 10 ms typical |
| 1746-OW16 | 16 outputs | AC/DC relay contact output | 0.090 A | 0.070 A | Relay contact, 10 ms typical |
| 1746-OX8 | 8 outputs | AC/DC relay contact output | 0.060 A | 0.045 A | Relay contact, 10 ms typical |
Where this module sits: Read the backplane column before the point count: 1746-OW16 takes 0.090 A at 5 V and 0.070 A at 24 V. Added up, on the 5 A 1746-P2 even the tighter rail (the 24 V one) carries 13 of them, more than the thirteen slots of the longest 1746 chassis, so slot count and not current decides.
Two things this block does not answer. It gives the module current, not the surge a rack sees at power-up, which is printed separately as inrush for the supply and not per module. And it says nothing about the 24 V field supply drawn by the loads themselves - the 24 V backplane figure is what the module takes from the rack, not what the sensors and coils take from the field supply.
Source: Rockwell 1746-IN027 digital I/O specification rows, 1746-IN008 and 1746-UM007 analog rows, 1746-IN016/IN004 chassis and supply rows. Backplane currents are quoted as printed; only the "how many fit" divisions are arithmetic, and they are integer divisions of the printed capacity.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.