logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1769-OB16 / 1769OB16

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1769-OB16 / 1769OB16

China Allen Bradley PLC 1769-OB16 / 1769OB16 supplier
Allen Bradley PLC 1769-OB16 / 1769OB16 supplier Allen Bradley PLC 1769-OB16 / 1769OB16 supplier Allen Bradley PLC 1769-OB16 / 1769OB16 supplier Allen Bradley PLC 1769-OB16 / 1769OB16 supplier Allen Bradley PLC 1769-OB16 / 1769OB16 supplier

Large Image :  Allen Bradley PLC 1769-OB16 / 1769OB16

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-OB16 / 1769OB16

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $182.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1769-OB16 technical data PDF download CompactLogix 1769-OB16 / 1769OB16 16-Point 24V DC Output Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-OB16 (also written 1769OB16) is the sixteen-point 24V DC sourcing output of the Compact I/O 1769 range. All sixteen points switch to +VDC from one DC common, which is the wiring pattern most panels want when the loads are valve solenoids, interposing relays and 24V pilot lamps.

It is the fast slice of the DC output range — 0.1 ms on and 1.0 ms off — so it is also the one specified when a solid-state relay or a pneumatic valve has to follow a short pulse rather than a slow sequence.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-OB16 (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-OB16
 Brand Name
 Rockwell
 Outputs
 16 (16 points per group, one DC common)
 Voltage category
 24V DC source
 Operating voltage range
 20.4…26.4V DC
 Output delay, on / off
 0.1 ms / 1.0 ms
 Current draw @ 5.1V
 200 mA
 Heat dissipation, max
 2.11 W
 Off-state leakage, max
 1.0 mA @ 26.4V DC
 On-state current, min
 1.0 mA
 On-state voltage drop, max
 1.0V DC @ 1 A
 Current per point
 0.5 A @ 60 °C; 1.0 A @ 30 °C
 Current per module
 4.0 A @ 60 °C; 8.0 A @ 30 °C
 Surge current
 2.0 A for 10 ms, repeatable every 2 s
 Isolation
 1200V AC 1 s or 1697V DC 1 s, output point to bus; 75V DC working voltage
 Slot width / weight
 1 slot / 280 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-OB16 Compact I/O 16-point 24V DC source output module, factory packaging 1769-OB16 module, front view with terminal block 1769-OB16 label detail showing catalog number

Where the module sits in a CompactLogix system

Bank and supply. 200 mA at 5.1V, 2.11 W, one slot, eight-module distance rating, powered from the bank's 1769-PA2 / PB2 / PA4 / PB4. Sourcing only. Points switch the +DC rail to the load; the load returns to DC common. Every field device must therefore be a sinking-input type — a sinking (NPN-style) solenoid driven from this module will not work, and 1769-OV16 is the sink counterpart. Field supply window. 20.4…26.4V DC, a narrower window than the input modules' 10…30V DC: the output driver needs a proper 24V rail, and a supply sitting at 19V will not hold the load.

Load rules that decide the wiring

Derating with temperature. 1.0 A per point and 8.0 A per module at 30 °C fall to 0.5 A per point and 4.0 A per module at 60 °C. A warm cabinet designed on the 30 °C column is a real and repeatable failure mode. Minimum load 1.0 mA. Well below any real coil, but a solid-state input with a high internal resistance may need a loading resistor. Leakage. 1.0 mA at 26.4V DC off-state. That will not hold a solenoid, but it can hold a small relay or light an LED pilot; a 5.6 kΩ half-watt resistor across the load absorbs it. Inductive loads. A 1N4004 diode reverse-wired across a 24V DC coil is the published practice for this module, and it is what keeps the output driver inside its ratings over a long service life.

Commissioning in four checks

Confirm the field supply is 20.4…26.4V DC at the module terminals with all outputs energised, not just at the power supply terminals. Recompute per-point and per-module current on the cabinet's real internal temperature; 0.5 A per point at 60 °C is the working figure. Fit a 1N4004 across every 24V DC coil, and check that each load's return goes to the same DC common as the module. Torque terminals at 0.68 N·m (6 lb·in) with 22…14 AWG solid copper rated 90 °C, and pulse each output during commissioning against a known load.

Substituting or replacing a 1769-OB16

1769-OB16P — protected version, 160 mA at 5.1V, 0.5V maximum drop, 1.0 / 2.0 ms delays; slower but shorter-circuit tolerant. 1769-OB32 — 32 points, 1.5 slots, 300 mA at 5.1V, 4.5 W, six-module distance rating rather than eight. 1769-OV16 — the sinking (24V DC sink) counterpart when the load returns to +DC. 1769-OW16 — relay contacts for AC loads or DC loads up to 125V DC, at the cost of 10 ms switching.

Which Compact I/O DC output to specify

1769-OB16 — 16 sourcing points, 0.5 A per point at 60 °C, 200 mA, 2.11 W. 1769-OB32 — 32 sourcing points, 300 mA, 4.5 W, six-module distance rating. 1769-OB16P — protected output, 160 mA, 0.5V drop, for circuits exposed to short circuits. 1769-OV16 — sinking output when the load returns to +DC rather than to common. Source versus sink is fixed by how the existing panel returns its loads; the module cannot be rewired to the opposite convention.

FAQ — 1769-OB16

How many outputs does 1769-OB16 have?

Sixteen, all on one DC common, switching the +DC rail — a sourcing output, so the field devices must be sinking-input types.

What is the switching speed of 1769-OB16?

0.1 ms on and 1.0 ms off, the fastest of the standard 1769 DC output slices.

How much current can 1769-OB16 handle per point?

1.0 A at 30 °C and 0.5 A at 60 °C, with 8.0 A and 4.0 A per module. Design on the cabinet's real internal temperature.

What does 1769-OB16 draw from the backplane?

200 mA at 5.1V with 2.11 W maximum heat dissipation, one slot, 280 g, eight-module distance rating.

What field voltage does 1769-OB16 require?

20.4…26.4V DC. That is narrower than the input modules' 10…30V DC — the output driver needs a genuine 24V rail.

Why does a 1769-OB16 output stay on with the program false?

Off-state leakage can reach 1.0 mA at 26.4V DC. It will not hold a solenoid but can hold a small relay or light an LED. A 5.6 kΩ half-watt loading resistor across the load absorbs it.

What protection does 1769-OB16 need on inductive loads?

A 1N4004 diode reverse-wired across each 24V DC coil, which is the practice printed in the module specification.


Data sources. Technical values on 1769-OB16 come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current Rockwell Automation documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.