Product Details:
Payment & Shipping Terms:
|
The 1769-ECL is the left end cap: the passive terminator fitted at the far end of a 1769 I/O bank, on the left side of the first module.
A bank that ends without a cap does not close the backplane bus, and the controller will not see the modules beyond the gap. That is the whole job — 5 mA at 5.1V, 130 g, one position, no I/O. The point of knowing its weight and current is that the cap is still a module position in the bank count and still draws from the power supply budget.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-ECL |
Brand Name |
Rockwell |
Function |
Terminates the bus at the far end of an I/O bank |
Location |
Left end of a bank |
Positions |
1 |
Current draw @ 5.1V |
5 mA |
Current draw @ 24V |
0 mA |
Weight, approx |
130 g |
North American temperature code |
T3C |
IEC temperature code |
N/A |
Enclosure type rating |
None (open-style) |
Dimensions (H * W * D), approx |
118 * 15 * 87 mm |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
What is 1769-ECL used for?
It terminates a Compact I/O bank at the left end where there is no expansion cable, closing the backplane so the controller can see the modules in that bank.
Does 1769-ECL draw power?
5 mA at 5.1V and 0 mA at 24V; it is a passive terminator that still counts against the bank's power supply budget.
How much does 1769-ECL weigh?
Approximately 130 g, with drawing dimensions of 118 * 15 * 87 mm, one position in the bank.
Is 1769-ECL certified for hazardous locations?
It carries the North American T3C temperature code and no IEC temperature code, so it is not the variant certified for Zone 2; 1769-ECRK is the extended variant.
What is the difference between 1769-ECL and 1769-ECR?
Position: the ECL terminates the left end of a bank and the ECR the right end. Both draw 5 mA at 5.1V and weigh 130 g.
Do I need an end cap on every bank?
Yes. Every bank needs a cap at the end without an expansion cable; without it the bus is open and downstream modules are not recognised.
The Allen-Bradley CompactLogix 1769 controllers category groups the other catalog numbers, options and spare parts in the same range.