The 1756-IF4FXOF2F (also written 1756IF4FXOF2F) is the ControlLogix analog module that carries both directions in one slot: four high-speed differential inputs and two high-speed outputs, backplane load 375 mA at 5.1 V DC and 100 mA at 24 V DC, power consumption 4.3 W (1756-TD002).
The inputs are the fast part. Module scan time is 300 µs minimum on a B-series module at firmware revision 3.x or greater, and 400 µs on the A-series at revision 1.x. Resolution is approximately 14 bits across ±10.5 V at 1.3 mV per bit, 13 bits across 0...10.5 V, 12 bits across 0...5.25 V, and approximately 12 bits across 21 mA at 5.25 µA per bit.
The outputs are two channels of ±10 V or 0...20 mA at 13 bits across 21 mA (2.8 µA per bit) and 14 bits across 21.8 V (1.3 mV per bit), with electronic short-circuit limiting at 21 mA or less and an update period of 1 ms minimum for all channels. Output settling is under 2 ms to 95 % of final value into a resistive load.
Isolation separates this module from the rest of the analog family: 250 V continuous reinforced insulation from inputs and outputs to the backplane, and no isolation between the individual inputs or between the individual outputs — the opposite arrangement to the 1756-IF6I, which isolates channels from one another but rates the barrier basic. Technical data 1756-TD002, user manual 1756-UM009, installation instructions 1756-IN063.
1756-IF4FXOF2F |
4 high-speed differential inputs + 2 outputs, 375 mA, reinforced isolation |
In stock |
1756-IF6CIS |
6 isolated current inputs with sourcing 24 V DC loop supply |
In stock |
1756-IF6I |
6 isolated inputs, 16-bit, 250 mA, channel-to-channel basic isolation |
In stock |
1756-IF8 |
8 single-ended / 4 differential inputs, 200 mA, 250 V basic to backplane |
In stock |
1756-IF8H |
8 differential HART current inputs, A and B series |
In stock |
1756-IF16 |
16 single-ended / 8 differential inputs, 200 mA, 15 Hz bandwidth |
In stock |
1756-IF16H |
16 differential HART current inputs, A and B series |
In stock |
1756-IRT8I |
8 isolated RTD and thermocouple inputs, 24-bit, 1756-CJC required |
In stock |
1756-IR6I |
6 isolated RTD inputs, 20-pin block, discontinued 2017 |
In stock |
1756-IT6I |
6 thermocouple inputs, two mV ranges, one CJC sensor |
In stock |
1756-IT6I2 |
6 isolated thermocouple inputs, 16-bit, two CJC sensors |
In stock |
Application |
Analog input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IF4FXOF2F |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
4 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Analog Input Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN063 (analog I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
This is the module for a control loop that has to close inside the rack rather than through a separate controller: a fast pressure or flow input driving a proportional valve or a variable-speed reference, where the output has to follow the measurement within milliseconds.
The 4-in / 2-out arrangement suits a skid with a handful of fast loops — two independent single-loop controllers, or one cascade — where a full 8-channel input module plus separate output module would waste slots and backplane current.
It does not replace an isolated input module. Inputs share a common reference and there is no channel-to-channel barrier, so thermocouples on grounded junctions or transmitters on different supplies belong on a 1756-IF6I or 1756-IF8I instead.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Reinforced to the backplane, not between channels | 250 V reinforced inputs and outputs to the backplane, no isolation between individual channels. Channels at different field potentials need separate modules. |
| Check 3 | Output load window | Voltage output drives more than 2000 Ω, current output 0...750 Ω. A 250 Ω loop resistor plus cable resistance stays inside; a second receiver in the loop may not. |
| Check 4 | Overvoltage limits differ by input type | Voltage inputs accept 30 V DC, current inputs 8 V AC/DC. A mis-wired 24 V source on a current channel exceeds the published protection. |
| Check 5 | Terminal block and torque | The module takes 1756-TBCH or 1756-TBS6H at 0.5 N·m. The block is a separate catalogue item. |
Specifications per Rockwell publication 1756-TD002 (ControlLogix I/O Modules Specifications); module behaviour per 1756-UM009 and 1756-IN050.
For measurement only, the 1756-IF8 provides 8 single-ended channels at 200 mA backplane current and 250 V basic isolation; the 1756-IF16 doubles the channel count at the same backplane figure.
For isolated channels, the 1756-IF6I isolates six inputs from one another at 250 mA; the 1756-IF8I provides eight isolated channels at 24-bit resolution.
For an output-only requirement, the 1756-OF4 and 1756-OF8 carry 4 and 8 analog outputs; the 1756-OF8I is the isolated version.
What is the 1756-IF4FXOF2F?
A ControlLogix analog module with four high-speed differential inputs and two high-speed outputs in one slot.
What is the backplane current?
375 mA at 5.1 V DC and 100 mA at 24 V DC, 4.3 W power consumption (1756-TD002).
How fast does it scan?
300 µs minimum on a B-series module at firmware 3.x or later; 400 µs minimum on the A-series at revision 1.x.
What resolution do the inputs have?
Approximately 14 bits across ±10.5 V (1.3 mV per bit), 13 bits across 0...10.5 V, 12 bits across 0...5.25 V, and approximately 12 bits across 21 mA (5.25 µA per bit).
What isolation does it provide?
250 V continuous reinforced insulation from inputs and outputs to the backplane, with no isolation between individual inputs or individual outputs.
Can the outputs drive a 250 Ω loop?
Yes — current output drive capability is 0...750 Ω, and voltage output is more than 2000 Ω, with electronic short-circuit limiting at 21 mA or less.
Which terminal blocks fit?
1756-TBCH or 1756-TBS6H, torqued to 0.5 N·m, ordered separately from the module.
What temperature code does it carry?
T4A in North America, T4 under ATEX and IECEx, with ATEX certificate DEMKO15ATEX1482X and IECEx UL 15.0053X.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IF4FXOF2F. Values re-checked 15 November 2026.