Product Details:
Payment & Shipping Terms:
|
1763-NC01 is the breakout cable that takes the MicroLogix 1100 channel 0 port from its 8-pin mini-DIN connector to a 6-pin Phoenix RS-485 terminal block.
It is the part that lets a 1100 join an existing DH-485 or Modbus RTU trunk without cutting the factory connector off the controller.
| 1763-L16AWA | MicroLogix 1100 16 point controller | IN STOCK |
| 1763-NC01 | Channel 0 to RS-485 cable | IN STOCK |
| 1763-MM1 | Memory module | IN STOCK |
| 1763-BA | Replacement lithium battery | IN STOCK |
Catalog number |
1763-NC01 |
Description |
Cable, MicroLogix 1100 channel 0 (8-pin DIN) to RS-485 (6-pin Phoenix) |
Connector A |
8-pin mini-DIN, controller channel 0 |
Connector B |
6-pin Phoenix, RS-485 terminal block |
Used with |
MicroLogix 1100 channel 0 |
Lifecycle status |
Active Mature |
UPC |
662074051632 |
Estimated lead time |
5 days |
Warranty |
1 year standard |
Publication |
1763-UM001 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1763-UM001 (module specifications) and 1761-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Controller side: the 8-pin mini-DIN channel 0 connector. Field side: a 6-pin Phoenix terminal block carrying RS-485 data lines and signal common.
The cable is passive — no electronics, no isolation, no termination. It is a wiring adapter, which is why it survives as an active catalog number while the controller it plugs into does not.
Whenever channel 0 has to talk DH-485, Modbus RTU or ASCII RS-485 to a drive, a weigh scale or another controller over a two-wire trunk.
For point-to-point DF1 to a programming laptop the ordinary 1761-CBL-PM02 cable is the correct part; NC01 is for the RS-485 side.
RS-485 needs a terminating resistor at each end of the trunk and bias resistors somewhere in the segment. The Phoenix end gives access to those terminals; the values come from the network documentation, not from the cable.
Keep the segment within the DH-485 distance and node limits, and give every node a unique address before power-up.
Lifecycle status on the Rockwell product page: Active Mature, with a published lead time of 5 days and a 1 year warranty.
Because the connector is moulded, a damaged cable cannot be repaired in the field — it has to be replaced, which is why a spare belongs in the panel cabinet.
1763-L16AWA is the controller this cable serves. Other MicroLogix 1100 accessories: 1763-MM1 memory module and 1763-BA replacement battery.
The rest of the 1762 expansion I/O range plugs into the same controller and shares its bus power budget.
What does 1763-NC01 connect?
MicroLogix 1100 channel 0, 8-pin DIN, to an RS-485 6-pin Phoenix terminal block.
Is 1763-NC01 an active product?
Yes — lifecycle status Active Mature, 5 day published lead time.
Does 1763-NC01 provide isolation?
No. It is a passive wiring adapter.
Can 1763-NC01 be used for DF1 to a laptop?
No — point-to-point DF1 uses a 1761-CBL-PM02 cable.
Where is 1763-NC01 used?
Where a MicroLogix 1100 must join a DH-485, Modbus RTU or ASCII RS-485 trunk.
1763-NC01 is a Rockwell service part for the MicroLogix family, documented here from the controller manual rather than from a catalogue summary, so that the compatibility, the function and the installation sequence are on one page.
| Specification | Value |
|---|---|
| Catalog number | 1763-NC01, Series A or later |
| Length | 30 cm (11.8 in.) |
| Use | Communication cable for the MicroLogix 1100; required series for Class I Division 2 applications |
| Termination | The cable includes the 120 ohm termination impedance required by the DH-485 specification, so no external resistor is fitted |
| Segment limit | DH-485 segment total length 1219 m (4000 ft) from first to last node |
| Other supported cables | 1761-CBL-AM00 and 1761-CBL-AP00 at 45 cm, 1761-CBL-PM02/HM02/PH02/AH02 at 2 m, 2707-NC9 at 15 m, all with stated series requirements |
| Modem link | When port 0 is connected to a modem over RS-232, the cable may be extended to a maximum of 15.24 m (50 ft) |
| Source | 1763-UM001 controller user manual, communication cable tables |
Thirty centimetres sounds like a trivial part, and it is the one that decides whether a DH-485 segment works. The 120 ohm termination is inside the cable, so a longer general purpose cable with the same connector will fit and will not terminate the bus, which shows up as intermittent communication rather than as a clean failure.
The series letter is the second detail. For Class I Division 2 installations the manual names the series that is acceptable, and an older cable with the correct length and connector does not qualify, which is a finding that surfaces during inspection rather than during commissioning.
For a service part the engineering question is narrow: which controller it fits, what it restores, and what the procedure costs in downtime. The table above answers the first two from the manual, and the procedure answers the third in steps that can be followed with the enclosure open.
Cable part numbers that carry a Series letter are not interchangeable with earlier series in classified locations. The manual states which series is required for Class I Division 2, and substituting an older cable because it fits is the kind of short cut that fails an inspection.
The port cover is part of the environmental rating. Removing it to fit a module and leaving it off exposes the connector to dust and to accidental contact, and the manual assumes the cover is back in place when the panel door is closed.
Transport is the second function of these parts. A module programmed in the workshop and carried to site turns a commissioning visit into an installation task, and it also gives the maintenance team a known good image to fall back on when a controller is replaced under pressure.
Termination impedance is built into the communication cable rather than added as a resistor. On a DH-485 segment that detail is what keeps reflections out of the signal, and it is why an arbitrary cable of the right length is not an acceptable substitute.
Field replacement of these parts happens with the controller de-energised. Reading the manual procedure before opening the enclosure is faster than discovering, mid-swap, that the connector is keyed or that the wires must be dressed along a guide.
Battery indications are a deadline rather than a status. The controller publishes roughly two weeks from the first low indication, and the clock data is what is actually at risk, because the program itself is held in non-volatile memory and the battery exists to keep the clock and the retention alive.
Cable length is quoted per segment and per node, and the two limits are different. A single point to point link tolerates a much longer run than a multi-drop segment, and the specification that applies is the one for the topology actually installed.
Documentation for accessories is a page in the controller manual rather than a separate publication, which is why the figures here are quoted from that manual. When a customer asks for the source, the manual section is the reference, and the catalog number is only the ordering key.
Handling rules for lithium cells are not paperwork. Shorting the terminals, attempting to charge a primary cell, or puncturing a pack in a hazardous area are the three ways these parts injure people, and the procedures in the manual address each of them separately.
A spare parts kit for a small controller is cheap compared with the cost of waiting. One memory module, one battery and one communication cable cover the three failures that stop a machine without any diagnostic message on the display.
A service part is ordered against a symptom, not against a catalog page. The questions that matter are which controller the part fits, what it actually restores, and how long the machine can stay down while it is fitted, and those three answers are the reason this page exists rather than a line in a price list.
Arc hazard during battery connection is a hazardous location issue, not a battery issue. Connecting or disconnecting a cell in a classified area can produce a spark, so the manual requires the area to be known non-hazardous before the connector is touched.
Program and recipe data are two different things in the backup question. A module image restores the program logic, while the current recipe may live in data that has moved since the image was taken, so the restore procedure has to state which of the two is being reloaded.
Use the listed series for classified areas, do not substitute a general purpose cable for the terminated one, and keep the segment inside the published length.
The Allen-Bradley MicroLogix 1100 1763 controllers category groups the other catalog numbers, options and spare parts in the same range.