logo
Home ProductsAB MicroLogix 1100 1763

Allen Bradley PLC 1763-MM1 / 1763MM1

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1763-MM1 / 1763MM1

China Allen Bradley PLC 1763-MM1 / 1763MM1 supplier
Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier Allen Bradley PLC 1763-MM1 / 1763MM1 supplier

Large Image :  Allen Bradley PLC 1763-MM1 / 1763MM1

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1763-MM1 / 1763MM1

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $88.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1763-MM1 technical data PDF download 1763-MM1 Rockwell MicroLogix 1100 Memory Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: MicroLogix 1100 / 1763

1763-MM1 is the memory module for the MicroLogix 1100 — an archive copy of the program and data that lives outside the controller.

Its purpose is recovery: a replacement controller can be loaded from the module without a laptop and without a copy of the program file.

1763-L16AWA MicroLogix 1100 16 point controller IN STOCK
1763-NC01 Channel 0 to RS-485 cable IN STOCK
1763-MM1 Memory module IN STOCK
1763-BA Replacement lithium battery IN STOCK

Product Specifications 1763-MM1 (PDF)
 Catalog number
 1763-MM1
 Description
 MicroLogix 1100 memory module
 Function
 Program and data archive held independently of controller memory
 Used with
 MicroLogix 1100 controllers
 Lifecycle status
 Discontinued April 30, 2022
 Replacement category
 Engineering Replacement
 UPC
 662074051519
 Warranty
 1 year standard
 Publication
 1763-UM001

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1763-UM001 (module specifications) and 1761-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1763-MM1 1763-MM1 1763-MM1 1763-MM1 1763-MM1 1763-MM1

What it holds

A copy of the program and the retentive data, written from the controller and read back into a replacement unit. It is not the working memory — the controller runs from its own Flash.

Because the copy is physical, it survives a controller failure, a corrupt download and a site with no network access to the project archive.

Fitting and use

The module fits the controller's option slot and is loaded and stored through the programming software. Recording the date of the last store on the panel label is the discipline that makes it useful.

A module that has not been refreshed since the last program change is worse than no module: it restores an obsolete program with full confidence.

Availability

1763-MM1 was discontinued on April 30, 2022 with the rest of the MicroLogix 1100 line, replacement category Engineering Replacement.

Existing modules remain in service. Treat them as consumables: they have a limited number of write cycles and the pins are easily bent.

Buying a used module

Check that the part number on the label is 1763-MM1 and not a 1762 module — the slots look similar and the modules are not interchangeable.

Ask whether the module was removed from a working controller. A module pulled from a scrapped panel is fine; one rattling loose in a drawer usually is not.

Related parts

1763-L16AWA is the controller, 1763-NC01 the RS-485 cable, 1763-BA the replacement battery for the battery-backed clock.

1762 expansion I/O modules share the controller's 800 mA / 700 mA bus allowance.

FAQ — 1763-MM1

What is 1763-MM1?

The memory module for the MicroLogix 1100, holding an archive copy of the program.

Is 1763-MM1 still available from Rockwell?

No. Discontinued April 30, 2022; replacement category Engineering Replacement.

Does 1763-MM1 replace the controller memory?

No — it stores a copy; the controller runs from its own Flash.

Is 1763-MM1 the same as 1762-MM1?

No. Different controller family, different module.

Why keep a memory module on site?

To restore a program without a laptop or a network copy after a controller failure.


Data sources. Function comes from the Rockwell product page of 1763-MM1; archive behaviour follows 1763-UM001. Any attribute a publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

1763-MM1: MicroLogix 1100 memory module

1763-MM1 is a Rockwell service part for the MicroLogix family, documented here from the controller manual rather than from a catalogue summary, so that the compatibility, the function and the installation sequence are on one page.

SpecificationValue
Catalog number1763-MM1
FunctionMemory module providing optional backup of the user program and data
CompatibilityMicroLogix 1100 controllers
OrderingAccessory part; the controller ships with the memory module port cover in place
InstallationRemove the port cover, align the connector on the module with the connector pins on the controller, seat firmly
Source1763-UM001 controller user manual, memory module section

The MicroLogix 1100 accepts one memory module, and the manual describes it as an optional backup of the program and data rather than an expansion. That wording matters when a customer asks whether the module can be used to add recipe capacity: the answer is no, and the correct route is to move the data storage outside the controller.

The module is the cheapest insurance against a controller failure in a small machine, because the replacement unit does not need a laptop, a project file or a compatible tool on site. The port cover travel with the controller, so a spare controller should be ordered with its module and the cover kept in place until it is needed.

For a service part the engineering question is narrow: which controller it fits, what it restores, and what the procedure costs in downtime. The table above answers the first two from the manual, and the procedure answers the third in steps that can be followed with the enclosure open.

Handling rules for lithium cells are not paperwork. Shorting the terminals, attempting to charge a primary cell, or puncturing a pack in a hazardous area are the three ways these parts injure people, and the procedures in the manual address each of them separately.

A spare parts kit for a small controller is cheap compared with the cost of waiting. One memory module, one battery and one communication cable cover the three failures that stop a machine without any diagnostic message on the display.

A service part is ordered against a symptom, not against a catalog page. The questions that matter are which controller the part fits, what it actually restores, and how long the machine can stay down while it is fitted, and those three answers are the reason this page exists rather than a line in a price list.

Arc hazard during battery connection is a hazardous location issue, not a battery issue. Connecting or disconnecting a cell in a classified area can produce a spark, so the manual requires the area to be known non-hazardous before the connector is touched.

Program and recipe data are two different things in the backup question. A module image restores the program logic, while the current recipe may live in data that has moved since the image was taken, so the restore procedure has to state which of the two is being reloaded.

The distinction between backup and capacity is the one that costs money. A memory module that stores a copy of the program and the data does not enlarge the controller, so a project that has outgrown its memory cannot be rescued with an accessory; it needs a different controller.

Cable part numbers that carry a Series letter are not interchangeable with earlier series in classified locations. The manual states which series is required for Class I Division 2, and substituting an older cable because it fits is the kind of short cut that fails an inspection.

The port cover is part of the environmental rating. Removing it to fit a module and leaving it off exposes the connector to dust and to accidental contact, and the manual assumes the cover is back in place when the panel door is closed.

Transport is the second function of these parts. A module programmed in the workshop and carried to site turns a commissioning visit into an installation task, and it also gives the maintenance team a known good image to fall back on when a controller is replaced under pressure.

Termination impedance is built into the communication cable rather than added as a resistor. On a DH-485 segment that detail is what keeps reflections out of the signal, and it is why an arbitrary cable of the right length is not an acceptable substitute.

Field replacement of these parts happens with the controller de-energised. Reading the manual procedure before opening the enclosure is faster than discovering, mid-swap, that the connector is keyed or that the wires must be dressed along a guide.

Battery indications are a deadline rather than a status. The controller publishes roughly two weeks from the first low indication, and the clock data is what is actually at risk, because the program itself is held in non-volatile memory and the battery exists to keep the clock and the retention alive.

Cable length is quoted per segment and per node, and the two limits are different. A single point to point link tolerates a much longer run than a multi-drop segment, and the specification that applies is the one for the topology actually installed.

Keep one module per installed controller, label the image with the revision it holds, and leave the port cover fitted when no module is in place.

Related models, options and spare parts for this range are listed in the Allen-Bradley MicroLogix 1100 1763 controllers category.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)