logo
Home ProductsAB MicroLogix 1400 1766

Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA

China Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA supplier
Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA supplier Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA supplier Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA supplier Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA supplier Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA supplier

Large Image :  Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1766-L32AWAA / 1766L32AWAA

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $398.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 25 PCS
Detailed Product Description

1766-L32AWAA technical data PDF download 1766-L32AWAA Rockwell MicroLogix 1400 Controller with Analog I/O

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: MicroLogix 1100 / 1763

1766-L32AWAA is one of the 32-point MicroLogix 1400 controllers — the last MicroLogix family, and the only one still listed as Active Mature with a published five day lead time.

It carries three communication ports as standard: an isolated RS-232/RS-485 channel, a 10/100 Ethernet channel and a second non-isolated RS-232 channel. For a plant that wants a small controller on the network without a gateway, that is the whole argument for the 1400.

1766-L32AWA Controller, 20 ac inputs, 12 relay outputs IN STOCK
1766-L32AWAA Controller, 20 ac inputs, 12 relay outputs, analog I/O IN STOCK
1766-L32BWA Controller, 12 fast + 8 standard dc inputs, 12 relay outputs IN STOCK
1766-MM1 Memory module, 384 KB back-up IN STOCK

Product Specifications 1766-L32AWAA (PDF)
 Catalog number
 1766-L32AWAA
 Description
 MicroLogix 1400, 20 digital 120V ac inputs, 12 relay outputs, 4 analog in, 2 analog out, 110/240V ac power
 I/O
 32 discrete points — 20 digital 120V ac inputs, 12 relay outputs
 Analog I/O
 4 analog inputs and 2 analog outputs, 12-bit, 0…10V dc
 Power supply
 100…240V ac, 47…63 Hz
 Power consumption
 100 VA (130 VA for Series C)
 Inrush current
 120V ac 25 A for 8 ms, 240V ac 40 A for 4 ms
 Dimensions
 90 mm high, 180 mm wide, 87 mm deep
 Shipping weight
 900 g
 Communication ports
 Channel 0 isolated RS-232/RS-485, Channel 1 Ethernet 10/100, Channel 2 RS-232
 Relay load limit
 1440 VA maximum controlled load
 Relay current
 2.5 A per channel, 8 A per group common (channels 8…11)
 Relay mechanical life
 20,000,000 cycles
 Terminal screw torque
 0.791 N·m
 Lifecycle status
 Active Mature
 Estimated lead time
 5 days
 UPC
 612598518128
 Publication
 1766-UM001

Same-family catalog numbers: 1766-L32AWAA, 1766-L32BWA. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1766 family.

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1766-UM001 (module specifications) and 1766-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1766-L32AWAA 1766-L32AWAA 1766-L32AWAA 1766-L32AWAA 1766-L32AWAA 1766-L32AWAA

I/O and analog

20 digital 120V ac inputs, 12 relay outputs.

4 analog inputs and 2 analog outputs, 12-bit, 0…10V dc

The Ethernet channel carries EtherNet/IP, Modbus TCP or DNP3 over IP, but only CIP explicit messaging — real-time I/O messaging over the network is not supported, so remote I/O is not an option here.

Communication detail

Channel 0 is an isolated combination RS-232/RS-485 port: DF1 full duplex and half duplex, DH-485, Modbus RTU master/slave, DNP3 slave and ASCII. A 1763-NC01 cable is what connects it to an RS-485 trunk without an AIC+.

Channel 1 is 10/100 Ethernet with an embedded web server for module information, TCP/IP configuration, diagnostics and a data table monitor. Channel 2 is a non-isolated RS-232 port for a second serial device.

Power and loading

100 VA (130 VA for Series C). Inrush is 25 A for 8 ms at 120V ac and 40 A for 4 ms at 240V ac.

Up to seven 1762 expansion modules can be connected, in any combination, within the controller's backplane supply budget — that limit is the practical ceiling on how far this controller can grow.

Relays

Relay contacts handle a maximum controlled load of 1440 VA, 2.5 A per channel and 8 A per group common on channels 8…11. Mechanical life is 20,000,000 cycles.

That is pilot duty, not motor duty. A contactor coil is fine; a motor directly is not, whatever the VA figure suggests.

Lifecycle

Active Mature with a published five day lead time — the controller can still be ordered new, which is why it makes sense to standardise on it for spares rather than chase used MicroLogix 1100 or 1500 hardware.

It has a built-in real-time clock, so time-stamped fault records work without an add-on module. The optional 1766-MM1 memory module adds a separate program back-up, not more memory.

FAQ — 1766-L32AWAA

What I/O does 1766-L32AWAA have?

20 digital 120V ac inputs, 12 relay outputs.

Does 1766-L32AWAA have Ethernet?

Yes — a 10/100 Ethernet channel supporting EtherNet/IP, Modbus TCP and DNP3 over IP.

Is 1766-L32AWAA still available from Rockwell?

Yes. Lifecycle status Active Mature, published lead time 5 days.

How many expansion modules fit on 1766-L32AWAA?

Up to seven 1762 modules, within the backplane supply budget.

Does 1766-L32AWAA have a real-time clock?

Yes, built into the controller.


Data sources. Input and output combination, dimensions, weight, power consumption, inrush, relay limits and analog ratings come from the 1766-UM001 general specifications table; lifecycle and lead time come from the Rockwell product page, which lists the model as Active Mature. Any attribute a publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

1766-L32AWAA: MicroLogix 1400 controller with analog I/O

1766-L32AWAA is a MicroLogix controller, a self contained unit that combines the power supply, the processor, embedded I/O and the communication ports, so the figures below describe the whole assembly rather than a single card in a chassis. All values are taken from the Rockwell controller manual for this bulletin.

SpecificationValue
Catalog number1766-L32AWAA
Input power100 to 240V AC at 47 to 63 Hz
Total I/O24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog)
Embedded discrete inputs20 at 120V AC
Embedded analog inputs4 voltage inputs, 0 to 10V DC
Embedded discrete outputs12 relay
Embedded analog outputs2 voltage outputs
Communication portsPort 0 RS-232/RS-485 mini-DIN, port 1 Ethernet RJ45, port 2 RS-232 9-pin D-shell
Dimensions H x W x D90 x 180 x 87 mm (3.5 x 7.08 x 3.43 in.)
Shipping weight900 g (31.74 oz.)
Power supply inrush120V AC: 25 A for 8 ms; 240V AC: 40 A for 4 ms
Power consumption100 VA, 130 VA on Series C
Terminal screw torque0.791 N m (7.0 lb in.) rated
Source1766-UM001 controller user manual, general specifications

This is the variant that closes the loop without an expansion module: four 0 to 10V analog inputs and two analog outputs sit on the same controller as the twenty 120V AC inputs and twelve relay outputs. For a skid with a pressure transducer, a level probe and a proportional valve, it means one part number instead of a controller plus two analog cards.

The analog channels are voltage only, 0 to 10V DC. A 4 to 20 mA transmitter needs a shunt resistor or a signal conditioner, and that is a wiring decision made at the drawing stage rather than at commissioning, because the terminals are shared with the discrete field wiring.

Three numbers decide most of the engineering on a controller like this: the input power and its inrush, because that sizes the supply and the protective device; the embedded point count and type, because that decides how many field devices are wired directly; and the clearance envelope, because that decides whether the unit fits the panel that already exists.

Panel builders treat these units as a component with a fixed footprint, so the drawing set carries the dimensions and the clearance envelope rather than the mounting hole pattern alone. Getting that envelope wrong is discovered when the door will not close.

Inrush current is the number that trips a breaker on a cold morning. An AC powered controller that draws tens of amperes for a few milliseconds needs a supply and a protective device sized for that pulse, not for the steady state VA figure on the nameplate.

Mounting clearance is part of the thermal design. Fifty millimetres on every side is the published figure, and a controller bolted tight against a wireway will run hotter than the specification assumes, which shortens the life of the internal supply long before any I/O fails.

A MicroLogix controller is a complete package: power supply, processor, embedded I/O and communication ports in one housing that mounts on a DIN rail or a panel. Nothing here is a card in a chassis, so the specification table reads differently from an I/O module page: input power, embedded point count, communication ports and enclosure dimensions all matter at once.

The 24V user supply, where it exists, is for input devices only. Feeding output circuits from it is the mistake that destroys the internal supply, and the manuals state the restriction explicitly because the temptation is real when a panel has spare milliamps.

These controllers expand to the right through an expansion bus, and the expansion modules are the 1762 family rather than a second controller. Power budgeting therefore happens across the whole assembly, and the expansion cable and the end cap belong on the order with the first module.

The AC input version is chosen when the machine already switches 120V control circuits. It removes the need for a separate 24V sensor supply, but it also means every field device carries line voltage, so the wiring practice around the terminal block is the same as for a 120V relay panel.

Communication is built in rather than added: an Ethernet port for programming and messaging, plus serial ports that cover RS-232 and RS-485 without an external converter. On a retrofit this removes the gateway that used to sit in the panel, and it also removes the point of failure that gateway represented.

Operating temperature for this generation is quoted down to minus twenty degrees C, which is unusual for an AC powered device and relevant for outdoor cabinets and unheated shelters. The storage range is wider still, so a controller that has sat in a cold store can be energised without a warm-up ritual.

Relay outputs are the reason these controllers survive in mixed panels. A relay contact does not care whether the load is 24V DC, 120V AC or a small contactor coil, and the published pilot duty ratings are what a panel builder uses to decide whether a starter can be driven directly or needs an interposing relay.

The memory module is a removable program store, so a replacement controller can be commissioned without a laptop. It is a service part rather than an expansion part, and the procedure is to power down, transfer the module, and confirm the program and the recipe data before returning the machine to production.

Terminal torque is specified because a loose terminal block screw fails intermittently for months. The published value is the target for the rated screw, and a torque screwdriver is cheaper than the downtime caused by a high resistance joint that only shows up under load.

Relay life is quoted mechanically and electrically, and the two numbers are far apart. Twenty million mechanical operations is a mechanical endurance figure; the electrical life depends on the load, the inrush and the arc, which is why contactor coils and incandescent lamps shorten the life of the same contact.

Plan the 0 to 10V channels at drawing stage, provide shunts or conditioners where the transmitter is a current loop, and keep analog shields terminated at the panel rather than at the controller.

Related models, options and spare parts for this range are listed in the Allen-Bradley MicroLogix 1400 1766 controllers category.