logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1768-CNB / 1768CNB

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1768-CNB / 1768CNB

China Allen Bradley PLC 1768-CNB / 1768CNB supplier
Allen Bradley PLC 1768-CNB / 1768CNB supplier Allen Bradley PLC 1768-CNB / 1768CNB supplier Allen Bradley PLC 1768-CNB / 1768CNB supplier Allen Bradley PLC 1768-CNB / 1768CNB supplier Allen Bradley PLC 1768-CNB / 1768CNB supplier

Large Image :  Allen Bradley PLC 1768-CNB / 1768CNB

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1768-CNB / 1768CNB

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $526.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1768-CNB technical data PDF download 1768-CNB / 1768CNB CompactLogix ControlNet Bridge

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC Module

The 1768-CNB is the nonredundant ControlNet bridge for the 1768 backplane: 5 Mbps, 48 Logix connections, 99 nodes, 1 A at 5.2V DC and 5.14 W dissipated.

It is the module for a machine that has to join an existing ControlNet trunk rather than be born on Ethernet — a line where the drives, the remote racks and the older panel all sit on coax.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1768-CNB (PDF)
 Application
 ControlNet bridge, nonredundant media, for 1768-L4x controllers
 Cat Num
 1768-CNB
 Brand Name
 Rockwell
 ControlNet communication rate
 5 Mbps
 Logix communication connections
 48
 Number of nodes, max
 99
 Current draw @ 5.2V DC
 1 A
 Current draw @ 24V DC
 0 mA
 Power dissipation
 5.14 W
 Thermal dissipation
 17.5 BTU/hr
 Isolation voltage
 30V, functional, ControlNet to backplane
 Ports
 1 ControlNet BNC, 1 ControlNet RJ45
 Cable
 Quad shield RG6 coaxial
 Weight, approx
 0.260 kg
 Dimensions (H * W * D)
 132 * 56.7 * 105.1 mm
 Slot width
 1

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1768-CNB ControlNet bridge module, factory packaging 1768-CNB module front view with BNC and RJ45 ports 1768-CNB label detail showing catalog number

ControlNet capacity

48 Logix connections. A third of what the EtherNet/IP bridge offers, which is the number to plan against when a controller has to talk to several ControlNet racks and drives. 99 nodes maximum. The ControlNet node limit for the segment, independent of the connection count. 5 Mbps determinism. ControlNet's scheduled and unscheduled traffic keeps I/O updates and controller interlocking ahead of program uploads and messaging.

Nonredundant versus redundant

1768-CNB: one BNC. Single media — one trunk connection, and the media itself has no second path. 1768-CNBR: two BNC. Redundant media, with channel A and channel B on separate trunks; Rockwell recommends channel A for nonredundant media while both channels are active. Both carry one RJ45. The RJ45 is the programming port for a 1786-CP cable, not a second network.

Power and thermal

1 A at 5.2V DC, 0 mA at 24V DC. The highest 5.2V draw of the 1768 communication modules, against 834 mA for the ENBT. 5.14 W dissipation, 17.5 BTU/hr. BOTH figures are published, which makes the enclosure calculation straightforward: 17.5 BTU/hr per module at full load. Slot 1, 1.16 N·m screws. 132 * 56.7 * 105.1 mm and 0.260 kg, on DIN rail or a panel.

Cabling and installation

Quad shield RG6 coax. The cable specification for the trunk; taps and terminators come from the 1786 family (1786-TPR or -TPS taps, 1786-XT terminators). 30V functional isolation. ControlNet to backplane, type tested at 500V AC for 60 s — functional, not a hazardous-area barrier. Wire category 2 on the communication port. Use it when separating the coax from power conductors in the panel.

Certification and environment

T4A temperature code. Class I Division 2 Groups A, B, C, D, CE to EN 61326-1 and EN 61131-2, C-Tick and KC. CI conformance. ControlNet International conformance tested, which is what a ControlNet segment owner will ask for. 0...60 °C, 5 g vibration, 30 g shock. 6 kV contact and 8 kV air ESD immunity; open-style enclosure.

FAQ — 1768-CNB

How many nodes does a 1768-CNB support?

99 nodes on the ControlNet segment, with 48 Logix connections available for I/O, tags and messaging.

What is the difference between 1768-CNB and 1768-CNBR?

The CNB is nonredundant with one BNC port; the CNBR has two BNC ports for redundant media and weighs 0.293 kg instead of 0.260 kg.

What current does the 1768-CNB draw?

1 A at 5.2V DC and 0 mA at 24V DC, with 5.14 W of dissipation and 17.5 BTU/hr of thermal load.

Which cable does ControlNet use on the 1768-CNB?

Quad shield RG6 coaxial cable, with 1786 taps and 1786-XT terminators for the segment.

Is the 1768-CNB isolated?

30V continuous functional insulation, ControlNet to backplane, type tested at 500V AC for 60 s.

Can the 1768-CNB be used with a 1768-L43S?

Yes. ControlNet is a standard-network option on the 1768 safety controllers; CIP Safety over ControlNet is the safety path.


Data sources. Technical values on this page come from Rockwell publication 1769-TD007 (CompactLogix Communication Modules Specifications, publication 1769-TD007D-EN-P, May 2014), current Rockwell Automation documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

1768-CNB: CompactLogix ControlNet bridge module

1768-CNB is a module for the 1768 CompactLogix backplane, documented here from the Rockwell controller manual and the integrated motion specification so that the electrical, network and timing limits sit on one page.

SpecificationValue
Catalog number1768-CNB, with the 1768-CNBR as the redundant media variant
FunctionBridges ControlNet links, routes messages to devices on other networks, monitors and controls remote I/O
Connected messaging64 connections per module, including five controllers with a rack optimized connection and five with a rack optimized listen-only connection
Backplane position1768 slots are numbered right to left from the controller in slot 0
Related EtherNet/IP modules1768-ENBT and 1768-EWEB, up to two per controller
Power5V rail from the controller, 24V rail distributed by the controller
Typical network peersControlLogix with 1756-CNB, 1734 POINT I/O with 1734-ACNR, PowerFlex drives with 20-COMM-C or 22-COMM-C, PanelView Plus with a ControlNet adapter
Source1768-UM001 CompactLogix controller user manual, ControlNet section

A bridge module is a data mover with a hard connection budget. Sixty four connections, five rack optimized producers and five listen-only consumers, is the published ceiling, and a network design that assumes a bridge can absorb one more chassis because the coax looks quiet will fail at the configuration stage rather than in service.

Its place in a machine is usually the link to a legacy ControlNet segment: drives that predate EtherNet/IP, older remote I/O, and a PanelView that still speaks ControlNet. Adding it to a 1768 backplane is cheaper than replacing that segment, and the connection count is the price of keeping it.

The engineering question for a module in this backplane is always the same three: which rail it draws from, how it is addressed or connected, and what its published limit is. The table answers those from the Rockwell documents, and the notes below carry what the figures mean on a running machine.

A ControlNet bridge in this backplane exists to move produced and consumed data between a local controller and remote chassis, and its connection count is the practical limit. Sixty four connections with five rack optimized producers and five listen-only consumers is a number a network design has to stay inside, and it is published per module rather than per network.

Current draw at 24V is zero on this module because it runs from the 5V rail, and that matters to the power budget arithmetic: the module consumes from one rail only, so adding a second motion module changes the 5V calculation and leaves the 24V calculation untouched.

One power supply per backplane, and it does not feed the modules directly. It delivers 24V DC to the controller, and the controller converts that to the 5V and 24V rails that the communication and motion modules and the 1769 I/O actually use, so the power budget belongs to the controller rather than to the supply alone.

Two EtherNet/IP modules can be fitted per controller, which is enough for a device level ring or for separating a plant network from a machine network. Beyond two, the architecture has to change, either to a larger controller or to a gateway, and that is a design decision rather than a purchasing one.

The environmental envelope is stated with the IEC test numbers behind it, from operating cold to thermal shock. That is what allows a cabinet in an unheated building to be signed off against a standard rather than against an opinion, and it is why the storage range is quoted separately from the operating range.

The distinction between the two supply catalog numbers is an input question, not an output question: one accepts a wide AC range and a narrow DC range, the other accepts a single 24V DC range. Choosing between them is a decision about the panel, because a DC input supply inherits whatever the plant battery system does during a mains dip.

A SERCOS interface module is a deterministic motion bus, and its cycle time is a function of the data rate and the axis count. Half a millisecond with two drives at four megabits, one millisecond with four, and half a millisecond with four at eight megabits: those three numbers are the whole timing envelope, and a machine with a fast cam profile lives or dies on them.

Certification for a module in a control backplane includes the hazardous location listing, and the file numbers are the evidence a panel inspector asks for. Having them on the page saves the argument that starts when the certificate has to be found at commissioning.

There is no distance rating between the 1768 modules and the supply, which is a statement about the backplane rather than about wiring. Ribbon cable extension of a 1769 I/O bank has a published distance limit; the 1768 modules bolted to the same backplane do not, and confusing the two leads to an unfounded worry or a real mistake depending on which family is being extended.

Axis capacity is bound to the controller, not to the module. One module in a 1768-L43 gives four real axes, two feedback axes and six virtual axes; two modules in a 1768-L45 give eight, four and six. The virtual axes are not free hardware, they are a programming convenience, and a project that counts them as real axes will run out of capacity.

A motion module has one slot width, so the physical cost of adding an axis pair is a centimetre of DIN rail plus the fiber. What does not scale linearly is the engineering: the cam tables, the registration and the safety of the axis group all have to be rethought when the axis count doubles.

The PWR indicator is a diagnostic sequence, not a lamp. Steady red means the supply cannot produce valid 24V, and the documented procedure is to strip the system back, prove the supply alone, then add modules in groups until the fault reappears. Following that order is faster than swapping parts at random.

The fiber between the module and the drives is plastic optical fiber in three jacket variants, chosen for the routing rather than for the data rate. Non-jacketed cable suits a short run inside a cabinet, a standard PVC jacket suits general routing, and a nylon jacket is the option for abrasion and for tight bends, and all three are ordered by length.

Count connections before the chassis is added, keep the bridge for the legacy segment it serves, and remember the two EtherNet/IP module limit per controller.

This part sits in the Allen-Bradley CompactLogix 1769 controllers category, with the other models and spare parts listed alongside it.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)