Product Details:
Payment & Shipping Terms:
|
20AC015A3AYNAEC1 is a PowerFlex 70 in the 400 V class at the 15.4 A rating: 7.5 kW, 10 Hp, frame C.
Its build differs from the plain 20AC015A0AYNANC0 in EtherNet/IP, encoder feedback. The power stage is the same across the family, so the differences are in the option slots only.
Quick answer. 20AC015A3AYNAEC1 is a PowerFlex 70 drive, 400 V AC class, 15.4 A normal duty (7.5 kW / 10 Hp), frame C, A - Panel mount, IP 20, NEMA/UL Type 1.
| 20AC015C0AYNANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYYANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYYAEC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNANC1 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNAEG0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNAEC1 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNAEC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNADG1 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYYANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYNANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYNAEC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYNADG0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015F0AYNANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015C3AYYANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015C3AYNANC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNADC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A3AYNACC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYNANC1 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYNADC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
| 20AC015A0AYNACC0 | 15.4 A / 7.5 kW, frame C | IN STOCK |
Catalog number |
20AC015A3AYNAEC1 |
Voltage class |
400 V AC, 3-phase, 6-pulse |
Normal duty output current |
15.4 A |
Normal duty motor rating |
7.5 kW / 10 Hp |
Frame size |
C |
Enclosure (d) |
A - Panel mount, IP 20, NEMA/UL Type 1 |
HIM (e) |
3 - Full numeric LCD |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
Y - Brake IGBT fitted |
Internal brake resistor (h) |
N - No internal brake resistor |
Emission class (i) |
A - Filtered |
Comm slot (j) |
E - EtherNet/IP |
Control and I/O (k) |
C - Enhanced control, no safe-off |
Feedback (l) |
1 - 5V/12V encoder with enhanced control |
Source |
20A-UM001 p.10 catalog explanation |
Attribute values above for 20AC015A3AYNAEC1 are reproduced from the manufacturer's product data. For the authoritative technical record see the PowerFlex 70 User Manual, publication 20A-UM001, and the PowerFlex 70 Technical Data, publication 20A-TD001; mounting and wiring are in the Installation Instructions, publication 20A-IN009. Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20A (drive), C (400 V AC 3-phase), 015 (rating), then nine option positions d to l.
Here: d=A, e=3, f=A, g=Y, h=N, i=A, j=E, k=C, l=1.
Rockwell prints each position as its own table on page 10 of 20A-UM001; decoding by eye is where most used-drive listings go wrong.
Enclosure (d) decides the mounting: Panel mount, IP 20, NEMA/UL Type 1.
HIM (e): Full numeric LCD. The LCD keypad is removable, so a used drive can arrive with a blank cover.
Brake IGBT (g): Brake IGBT fitted; internal brake resistor (h): No internal brake resistor. On 20AC015A3AYNAEC1 the two characters are read together, because both are needed before a holding brake can be wired straight to the drive.
Comm slot (j): EtherNet/IP. Control and I/O (k): Enhanced control, no safe-off. Feedback (l): 5V/12V encoder with enhanced control.
Normal duty 15.4 A, 7.5 kW / 10 Hp on frame C.
Frame sets the heatsink, fan and terminal spacing, so a frame change is also a panel-space change.
What to verify before buying used Nameplate catalog number, full 16 characters, against this page - one letter of 20AC015A3AYNAEC1 changes the enclosure or the network option.
Safe-off builds (k=G) carry a second terminal pair; a standard-control drive does not.
Encoder interface (l=1) is a separate board; it is not CE EMC certified when fitted.
Every code above is transcribed from the Catalog Number Explanation, page 10 of Rockwell publication 20A-UM001.
No field on this page is inferred from a distributor listing; positions Rockwell leaves blank are not published and are not shown as data.
What is 20AC015A3AYNAEC1?
PowerFlex 70, 400 V, 15.4 A / 7.5 kW, frame C, panel mount.
What is the output current of 20AC015A3AYNAEC1?
15.4 A normal duty at 400 V.
Which frame is 20AC015A3AYNAEC1?
Frame C, 7.5 kW / 10 Hp normal duty.
Does 20AC015A3AYNAEC1 have a network slot?
EtherNet/IP.
What enclosure is 20AC015A3AYNAEC1?
Panel mount, IP 20, NEMA/UL Type 1.
Related catalog numbers in the same rating code. Same 15.4 A A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20AC015C0AYNANC0 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYYANC0 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYYAEC0 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYNANC1 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYNANC0 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYNAEG0 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYNAEC0 (15.4 A / 7.5 kW, frame C) · 20AC015A3AYNADG1 (15.4 A / 7.5 kW, frame C) · 20AC015A0AYYANC0 (15.4 A / 7.5 kW, frame C)
20AC015A3AYNAEC1 is a PowerFlex 70 adjustable frequency drive in the 400V class. The catalog number reads 20A for the family, C for the 400V three-phase rating, 015 for the output current code, and the trailing positions for HIM, filter, brake and feedback options.
| Attribute | Value |
| Catalog number | 20AC015A3AYNAEC1 |
| Family | PowerFlex 70, bulletin 20A |
| Voltage class | 400V AC, three-phase, six-pulse |
| Current code | 015 |
| Frame | C |
| Normal duty | 7.5 kW (10 Hp) |
| Heavy duty | 5.5 kW (7.5 Hp) |
| Input current | 15.1 A |
| Input kVA | 10.4 kVA |
| Output current | 15.4 / 17.2 / 23.1 A (cont. / 60 s / 3 s) |
| Dual element time delay fuse | 20...30 A dual element, 20...60 A non-time delay |
| Circuit breaker | 60 A max |
| Motor circuit protector | 20 A max |
| 140M / 140MT protector | 140M-C2E-C16 / 140M-D8E-C16 / 140M-F8E-C16 |
| Minimum enclosure | 3,441 in3 minimum enclosure |
The normal duty and heavy duty columns above are the same hardware at two thermal ratings, and the output current row gives the continuous, 60 second and 3 second values that a drive selection is actually checked against. A load that needs 130 percent for a minute is checked against the 60 second value, not against the continuous value.
The PowerFlex 70 line is split by voltage code rather than by frame: 20AB is 240V, 20AC is 400V, 20AD is 480V and 20AE is 600V, all three-phase six-pulse. A 400V drive and a 480V drive of the same frame are not interchangeable on a 480V supply, and the 400V code exists because the European supply is 380...480V with its own current ladder.
Two duty classes share one frame in this range: normal duty and heavy duty are published against the same hardware, with heavy duty one step below normal duty in kW. Sizing a conveyor on normal duty and then adding a high inertia load is the usual reason a 22 kW drive is found running at 18.5 kW.
The option string after the rating is where the order actually lives: HIM, internal EMC filter, internal dynamic brake resistor, feedback and enclosure options are each a position in the catalog number, and the same 15 A rating can be ordered with or without an internal filter. Reading the position is the only way to know what is inside the box.
For this rating the published branch protection starts at a 20...30 A dual element fuse and a 60 A circuit breaker, with the 140M or 140MT protector listed where the frame supports one. Use the published row rather than a computed value, and confirm the enclosure layout against the 3,441 in3 figure before the panel is designed.
The 400V current codes run 1P3, 2P1, 3P5, 5P0, 8P7, 011, 015, 022, 030, 037, 043, 060 and 072, which are current values rather than a copy of the 480V list. Match the code to the supply first, then check the motor current against the continuous output, then read the option positions for the filter, brake and HIM that the panel actually needs.
Related models, options and spare parts for this range are listed in the Allen-Bradley PowerFlex drives and motors category.