Product Details:
Payment & Shipping Terms:
|
20AB028C0AYNANC0 is a PowerFlex 70 in the 240 V class at the 28 A rating: 7.5 kW, 10 Hp, frame D.
Its build differs from the plain 20AB028A0AYNANC0 in wall/machine mount. The power stage is the same across the family, so the differences are in the option slots only.
Quick answer. 20AB028C0AYNANC0 is a PowerFlex 70 drive, 240 V AC, 3-phase, 6-pulse, 28 A normal duty (7.5 kW / 10 Hp), frame D, C - Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use.
| 20AB9P6C3AYNANC0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB9P6A0AYNNNC0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB9P6A0AYNANG0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB6P8A0AYNNNC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB6P8A0AYNANC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB4P2A3NYNNEG1 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A3NYNNDG1 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A3AYNNNC0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A0AYNNNG0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A0AYNNNC0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A0AYNANC0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB2P2A0AYNNNC0 | 2.2 A / 0.37 kW, frame A | IN STOCK |
| 20AB070A0AYNANC0 | 70 A / 18.5 kW, frame E | IN STOCK |
| 20AB054C0NYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB054A3AYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB054A0AYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB042A3AYNANC0 | 42 A / 11 kW, frame D | IN STOCK |
| 20AB042A0AYNANC0 | 42 A / 11 kW, frame D | IN STOCK |
| 20AB028C0AYNANC0 | 28 A / 7.5 kW, frame D | IN STOCK |
| 20AB028A3AYNANC0 | 28 A / 7.5 kW, frame D | IN STOCK |
| 20AB022C3AYNANC0 | 22 A / 5.5 kW, frame C | IN STOCK |
| 20AB022A3AYNANC0 | 22 A / 5.5 kW, frame C | IN STOCK |
| 20AB022A0AYNANC0 | 22 A / 5.5 kW, frame C | IN STOCK |
| 20AB9P6A3AYNACG0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB9P6A0AYNANC0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB6P8C3AYNANC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB6P8A0AYNNEC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB2P2A3AYNNNC0 | 2.2 A / 0.37 kW, frame A | IN STOCK |
| 20AB2P2A0AYNANC0 | 2.2 A / 0.37 kW, frame A | IN STOCK |
| 20AB054A3NYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB042C0AYNANC0 | 42 A / 11 kW, frame D | IN STOCK |
| 20AB028A0AYNANC0 | 28 A / 7.5 kW, frame D | IN STOCK |
Catalog number |
20AB028C0AYNANC0 |
Voltage class |
240 V AC, 3-phase, 6-pulse |
Normal duty output current |
28 A |
Normal duty motor rating |
7.5 kW / 10 Hp |
Frame size |
D |
Enclosure (d) |
C - Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use |
HIM (e) |
0 - Blank cover |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
Y - Brake IGBT fitted |
Internal brake resistor (h) |
N - No internal brake resistor |
Emission class (i) |
A - Filtered |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Enhanced control, no safe-off |
Feedback (l) |
0 - No feedback, enhanced control |
Source |
20A-UM001 p.10 catalog explanation |
Attribute values above for 20AB028C0AYNANC0 are reproduced from the manufacturer's product data. For the authoritative technical record see the PowerFlex 70 User Manual, publication 20A-UM001, and the PowerFlex 70 Technical Data, publication 20A-TD001; mounting and wiring are in the Installation Instructions, publication 20A-IN009. Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20A (drive), B (240 V AC 3-phase), 028 (rating), then nine option positions d to l.
Here: d=C, e=0, f=A, g=Y, h=N, i=A, j=N, k=C, l=0.
Rockwell prints each position as its own table on page 10 of 20A-UM001; decoding by eye is where most used-drive listings go wrong.
Enclosure (d) decides the mounting: Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use.
HIM (e): Blank cover. The LCD keypad is removable, so a used drive can arrive with a blank cover.
Brake IGBT (g): Brake IGBT fitted; internal brake resistor (h): No internal brake resistor. On 20AB028C0AYNANC0 the two characters are read together, because both are needed before a holding brake can be wired straight to the drive.
Comm slot (j): None. Control and I/O (k): Enhanced control, no safe-off. Feedback (l): No feedback, enhanced control.
Normal duty 28 A, 7.5 kW / 10 Hp on frame D.
Frame sets the heatsink, fan and terminal spacing, so a frame change is also a panel-space change.
What to verify before buying used Nameplate catalog number, full 16 characters, against this page - one letter of 20AB028C0AYNANC0 changes the enclosure or the network option.
Safe-off builds (k=G) carry a second terminal pair; a standard-control drive does not.
Encoder interface (l=1) is a separate board; it is not CE EMC certified when fitted.
Every code above is transcribed from the Catalog Number Explanation, page 10 of Rockwell publication 20A-UM001.
No field on this page is inferred from a distributor listing; positions Rockwell leaves blank are not published and are not shown as data.
What is 20AB028C0AYNANC0?
PowerFlex 70, 240 V, 28 A / 7.5 kW, frame D, wall/machine mount.
What is the output current of 20AB028C0AYNANC0?
28 A normal duty at 240 V.
Which frame is 20AB028C0AYNANC0?
Frame D, 7.5 kW / 10 Hp normal duty.
Does 20AB028C0AYNANC0 have a network slot?
None.
What enclosure is 20AB028C0AYNANC0?
Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use.
Related catalog numbers in the same rating code. Same 28 A A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20AB9P6C3AYNANC0 (9.6 A / 2.2 kW, frame B) · 20AB9P6A0AYNNNC0 (9.6 A / 2.2 kW, frame B) · 20AB9P6A0AYNANG0 (9.6 A / 2.2 kW, frame B) · 20AB6P8A0AYNNNC0 (6.8 A / 1.5 kW, frame B) · 20AB6P8A0AYNANC0 (6.8 A / 1.5 kW, frame B) · 20AB4P2A3NYNNEG1 (4.2 A / 0.75 kW, frame A) · 20AB4P2A3NYNNDG1 (4.2 A / 0.75 kW, frame A) · 20AB4P2A3AYNNNC0 (4.2 A / 0.75 kW, frame A) · 20AB4P2A0AYNNNG0 (4.2 A / 0.75 kW, frame A) · 20AB4P2A0AYNNNC0 (4.2 A / 0.75 kW, frame A)
The PowerFlex 70 is a thirteen-rating 400 V ladder and a ten-rating 240 V ladder, and the frames are lettered A to E rather than numbered. That is the first thing to fix when reading a 20A page next to a 20B page: the two product lines do not share a frame scheme, so a frame D 70 is not a frame 4 anything. Within one ladder, though, the rating code is simply the output current written into the catalog number, and consecutive codes often stay in one cabinet.
| Rating code | Output current | kW | HP | Frame |
| 2P2 | 2.2 A | 0.37 kW | 0.5 HP | Frame A |
| 4P2 | 4.2 A | 0.75 kW | 1.0 HP | Frame A |
| 6P8 | 6.8 A | 1.5 kW | 2.0 HP | Frame B |
| 9P6 | 9.6 A | 2.2 kW | 3.0 HP | Frame B |
| 015 | 15.3 A | 4.0 kW | 5.0 HP | Frame C |
| 022 | 22 A | 5.5 kW | 7.5 HP | Frame C |
| 028 | 28 A | 7.5 kW | 10 HP | Frame D |
| 042 | 42 A | 11 kW | 15 HP | Frame D |
| 054 | 54 A | 15 kW | 20 HP | Frame E |
| 070 | 70 A | 18.5 kW | 25 HP | Frame E |
Where this page sits: 20AB028C0AYNANC0 carries rating code 028. The rating field 028 reads 28 A, 7.5 kW and 10 HP on a frame D chassis; 028 and 042 share frame D, two rating codes in one cabinet.
What the suffix adds: Suffix read on this catalog: wall/machine mount, IP 66 NEMA/UL Type 4X/12, head position 0 (blank cover), and the CE filter is fitted inside the drive, so nothing has to be added at the cabinet entry to meet the emission class. For braking, no internal braking resistor is fitted, so any braking duty has to be sized as an external resistor.
| PowerFlex 70 (this series) | PowerFlex 700 | |
| Prefix and product | 20A = PowerFlex 70 | 20B = PowerFlex 700 |
| Frame naming | letters A to E | numbers 0 to 10 |
| 400 V ladder | 13 rating codes, 1.3 to 72 A | 30 rating codes, 1.3 to 875 A |
| 400 V top rating | 72 A / 37 kW on frame E | 875 A / 500 kW on frame 10 |
| 240 V top rating | 70 A / 18.5 kW on frame E | 260 A / 100 HP on frame 6 |
The table is the normal-duty ladder from the 50 Hz rating rows of 20A-TD001. The heavy-duty column and the 60 Hz rows are printed separately, and a 70 selected for constant torque has to be read from the heavy-duty column, which sits lower than the figure here. Enclosure dimensions per frame are in 20A-UM001 and are deliberately not reproduced, since mounting drawings change between frames.
Source: 20A-TD001 rating tables (240 V and 400 V classes) and 20A-UM001 p.10 catalog number explanation. Values are quoted as printed in the Rockwell tables.
Related models, options and spare parts for this range are listed in the Allen-Bradley PowerFlex drives and motors category.