Product Details:
Payment & Shipping Terms:
|
20AB022C3AYNANC0 is a PowerFlex 70 in the 240 V class at the 22 A rating: 5.5 kW, 7.5 Hp, frame C.
Its build differs from the plain 20AB022A0AYNANC0 in wall/machine mount. The power stage is the same across the family, so the differences are in the option slots only.
Quick answer. 20AB022C3AYNANC0 is a PowerFlex 70 drive, 240 V AC, 3-phase, 6-pulse, 22 A normal duty (5.5 kW / 7.5 Hp), frame C, C - Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use.
| 20AB9P6C3AYNANC0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB9P6A0AYNNNC0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB9P6A0AYNANG0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB6P8A0AYNNNC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB6P8A0AYNANC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB4P2A3NYNNEG1 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A3NYNNDG1 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A3AYNNNC0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A0AYNNNG0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A0AYNNNC0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB4P2A0AYNANC0 | 4.2 A / 0.75 kW, frame A | IN STOCK |
| 20AB2P2A0AYNNNC0 | 2.2 A / 0.37 kW, frame A | IN STOCK |
| 20AB070A0AYNANC0 | 70 A / 18.5 kW, frame E | IN STOCK |
| 20AB054C0NYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB054A3AYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB054A0AYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB042A3AYNANC0 | 42 A / 11 kW, frame D | IN STOCK |
| 20AB042A0AYNANC0 | 42 A / 11 kW, frame D | IN STOCK |
| 20AB028C0AYNANC0 | 28 A / 7.5 kW, frame D | IN STOCK |
| 20AB028A3AYNANC0 | 28 A / 7.5 kW, frame D | IN STOCK |
| 20AB022C3AYNANC0 | 22 A / 5.5 kW, frame C | IN STOCK |
| 20AB022A3AYNANC0 | 22 A / 5.5 kW, frame C | IN STOCK |
| 20AB022A0AYNANC0 | 22 A / 5.5 kW, frame C | IN STOCK |
| 20AB9P6A3AYNACG0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB9P6A0AYNANC0 | 9.6 A / 2.2 kW, frame B | IN STOCK |
| 20AB6P8C3AYNANC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB6P8A0AYNNEC0 | 6.8 A / 1.5 kW, frame B | IN STOCK |
| 20AB2P2A3AYNNNC0 | 2.2 A / 0.37 kW, frame A | IN STOCK |
| 20AB2P2A0AYNANC0 | 2.2 A / 0.37 kW, frame A | IN STOCK |
| 20AB054A3NYNANC0 | 54 A / 15 kW, frame E | IN STOCK |
| 20AB042C0AYNANC0 | 42 A / 11 kW, frame D | IN STOCK |
| 20AB028A0AYNANC0 | 28 A / 7.5 kW, frame D | IN STOCK |
Catalog number |
20AB022C3AYNANC0 |
Voltage class |
240 V AC, 3-phase, 6-pulse |
Normal duty output current |
22 A |
Normal duty motor rating |
5.5 kW / 7.5 Hp |
Frame size |
C |
Enclosure (d) |
C - Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use |
HIM (e) |
3 - Full numeric LCD |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
Y - Brake IGBT fitted |
Internal brake resistor (h) |
N - No internal brake resistor |
Emission class (i) |
A - Filtered |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Enhanced control, no safe-off |
Feedback (l) |
0 - No feedback, enhanced control |
Source |
20A-UM001 p.10 catalog explanation |
Attribute values above for 20AB022C3AYNANC0 are reproduced from the manufacturer's product data. For the authoritative technical record see the PowerFlex 70 User Manual, publication 20A-UM001, and the PowerFlex 70 Technical Data, publication 20A-TD001; mounting and wiring are in the Installation Instructions, publication 20A-IN009. Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20A (drive), B (240 V AC 3-phase), 022 (rating), then nine option positions d to l.
Here: d=C, e=3, f=A, g=Y, h=N, i=A, j=N, k=C, l=0.
Rockwell prints each position as its own table on page 10 of 20A-UM001; decoding by eye is where most used-drive listings go wrong.
Enclosure (d) decides the mounting: Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use.
HIM (e): Full numeric LCD. The LCD keypad is removable, so a used drive can arrive with a blank cover.
Brake IGBT (g): Brake IGBT fitted; internal brake resistor (h): No internal brake resistor. On 20AB022C3AYNANC0 the two characters are read together, because both are needed before a holding brake can be wired straight to the drive.
Comm slot (j): None. Control and I/O (k): Enhanced control, no safe-off. Feedback (l): No feedback, enhanced control.
Normal duty 22 A, 5.5 kW / 7.5 Hp on frame C.
Frame sets the heatsink, fan and terminal spacing, so a frame change is also a panel-space change.
What to verify before buying used Nameplate catalog number, full 16 characters, against this page - one letter of 20AB022C3AYNANC0 changes the enclosure or the network option.
Safe-off builds (k=G) carry a second terminal pair; a standard-control drive does not.
Encoder interface (l=1) is a separate board; it is not CE EMC certified when fitted.
Every code above is transcribed from the Catalog Number Explanation, page 10 of Rockwell publication 20A-UM001.
No field on this page is inferred from a distributor listing; positions Rockwell leaves blank are not published and are not shown as data.
What is 20AB022C3AYNANC0?
PowerFlex 70, 240 V, 22 A / 5.5 kW, frame C, wall/machine mount.
What is the output current of 20AB022C3AYNANC0?
22 A normal duty at 240 V.
Which frame is 20AB022C3AYNANC0?
Frame C, 5.5 kW / 7.5 Hp normal duty.
Does 20AB022C3AYNANC0 have a network slot?
None.
What enclosure is 20AB022C3AYNANC0?
Wall/machine mount, IP 66, NEMA/UL Type 4X/12, indoor use.
Related catalog numbers in the same rating code. Same 22 A A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20AB9P6C3AYNANC0 (9.6 A / 2.2 kW, frame B) · 20AB9P6A0AYNNNC0 (9.6 A / 2.2 kW, frame B) · 20AB9P6A0AYNANG0 (9.6 A / 2.2 kW, frame B) · 20AB6P8A0AYNNNC0 (6.8 A / 1.5 kW, frame B) · 20AB6P8A0AYNANC0 (6.8 A / 1.5 kW, frame B) · 20AB4P2A3NYNNEG1 (4.2 A / 0.75 kW, frame A) · 20AB4P2A3NYNNDG1 (4.2 A / 0.75 kW, frame A) · 20AB4P2A3AYNNNC0 (4.2 A / 0.75 kW, frame A) · 20AB4P2A0AYNNNG0 (4.2 A / 0.75 kW, frame A) · 20AB4P2A0AYNNNC0 (4.2 A / 0.75 kW, frame A)
This page is a 240 V class PowerFlex drive record with a full option string printed, and this site carries the 400 V class beside it. The first table compares the same family across the two voltage classes; the second reads the option positions that decide what the panel must add.
| Row | 240 V class, 20AB022C3AYNANC0 | 400 V class, 20AC037A0AYNANC0 |
| Rating code | 022 | 037 |
| Continuous output current | 22 A | 37 A |
| Motor rating | 5.5 kW / 7.5 Hp | 18.5 kW / 25 Hp |
| Frame size | C | D |
| Amperes per kW as printed | 4.0 A per kW | 2.0 A per kW |
| Option position | Code on this page | What it fixes for the panel |
| g and h, braking | g = Y brake IGBT fitted, h = N no internal brake resistor | dynamic braking is possible, but the resistor is external and ordered separately |
| d, enclosure | C - wall or machine mount, IP 66, NEMA/UL Type 4X/12, indoor use | a washdown-rated housing |
| i, emissions | A - filtered | the integral EMC filter is fitted |
| j, k and l | N comm slot, C enhanced control with no safe-off, 0 no feedback | a stand-alone drive: no network option, no safe-off, no encoder feedback |
The option string on this page is short and readable: no communication slot, enhanced control without safe-off, no feedback, filtered, IP 66 wall or machine mount, brake IGBT fitted with no internal resistor, full numeric LCD and the manual included. That combination describes a stand-alone drive in a washdown housing that can brake a load if an external resistor is bought, and it cannot be networked or made safe-off without a different string rather than an add-on card.
Two option rows are worth reading before a purchase rather than after: a brake IGBT with no internal resistor means the drive can brake but the resistor is a separate line on the order, and an enhanced control without safe-off means the safe-off function is unavailable on this code rather than unlockable. Both are printed plainly, and both are the kind of row a quote skips when it is written from the kW figure alone.
What this record does not settle: the output voltage range, the input current, the heat dissipation in watts, an enclosure dimension, a weight, the HP rating at 50 Hz against 60 Hz, a filter part number, and any lifecycle field.
The current per kilowatt is the number that decides cable and breaker sizing, and between the two voltage classes on this site it doubles: 4.0 A per kW on the 240 V drive against 2.0 A per kW on the 400 V one. A 5.5 kW 240 V machine therefore draws what an 11 kW 400 V machine draws, which is why the panel for the smaller motor needs the heavier wire.
Source: the fifteen published rows of 20AB022C3AYNANC0 from 20A-UM001 page 10, and the published rating rows of the 400 V class records on this site for the second column of the comparison. The amperes per kW figure is the printed current divided by the printed kW on each record.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley PowerFlex drives and motors category.