This page documents catalog number 440G-TZS21UPRH, a TLS-Z RFID guard locking switch with the GD2 actuator interface. It is a coded, non-contact interlock with guard locking rather than a tongue-operated switch, and the figures below are quoted from the TLSZR/L-GD2 guard locking switch installation instructions.
| Field | Value |
| Standards | IEC 60947-5-3, IEC 60947-5-1, IEC 61508, ISO 13849-1, ISO 14119 |
| Safety classification | Type 4 interlocking device per ISO 14119, RFID target with high level of coding, PLe Category 4 |
| Safety outputs | two PNP OSSD, 0.2 A maximum each, on at plus 24 V dc, safe state 0 V |
| Auxiliary output | 0.2 A maximum, function depends on variant |
| Assured locking distance | 13 mm (0.51 in.) maximum target distance, 5 mm (0.2 in.) maximum clearance between actuator base and switch when the door is closed |
| Locking force Fmax | plastic pins 1,950 N (488 lbf), steel bolts 2,600 N (585 lbf) |
| Locking force Fzh | plastic pins 1,500 N (337 lbf), steel bolts 2,000 N (450 lbf) |
| Supply | 24 V dc plus 10 percent minus 15 percent; 50 mA with the solenoid de-energized, 120 mA energized with 260 mA inrush |
| Solenoid duty cycle | 100 percent (the technical data sheet states 33 percent for Series F and later) |
| Response time | 75 ms for the first switch plus 25 ms for each additional switch in series, unlimited switches in series |
| Operating cycle | 1 Hz maximum; actuation speed 160 mm/s maximum and 100 mm/min minimum |
| Utilization category | DC-13, 24 V, 200 mA per IEC 60947-5-2 |
| Impulse withstand | 250 V, pollution degree 3, protection class 2, rated insulation 500 V |
| Mechanical life | 1 x 10^6 cycles |
| Temperature | minus 10 to plus 60 C, humidity 5 to 95 percent |
| Enclosure | NEMA 3, 4X, 12, 13 and IP66, IP67, IP69K |
| Connection | 8-pin M12 connector, one metre pigtail |
| Housing | UL approved glass-filled PBT, stainless steel actuator, glass-filled PBT target |
| Pin | Function |
| 1 | white, auxiliary output |
| 3 | green, lock command |
| 4 | yellow, Safety B+ OSSD input |
| 5 | gray, Safety A OSSD output |
| 6 | pink, Safety B OSSD output |
| 7 | blue, ground and 0 V |
| 8 | red, Safety A+ OSSD input |
This variant is the power-to-release version, and the cover with manual override key is published as intended for it: the override provides an auxiliary release when power is not available to achieve electrical interlocking. The override is a maintenance device rather than an operating control, and the keyed cover exists so that using it is a recorded act rather than a habit.
The auxiliary output on this catalog number reports lock status: it changes state when the lock is either locked or unlocked, independent of the OSSD state. On a power-to-release switch that is the bit that tells a controller the guard is free to be opened, and it is deliberately separate from the two safety outputs that carry the interlock function.
The OSSD test pulses are published because they constrain the receiving safety input: cross-short pulses of 0.1 ms every 11 s and short-circuit pulses of 0.5 ms every 11 s, with the instruction that the connected control system must tolerate them. A standard input with a 1 ms filter will not see them as a transition, and a fast edge-triggered input will, which is the failure mode a commissioning test is meant to expose.
Crosstalk between two TLS-Z switches has a published minimum spacing of 200 mm, and the same restriction applies to a 440G-LZ or a 440N-Z SensaGuard mounted nearby. The mechanism is magnetic rather than electrical: two inductive fields close together produce nuisance faults and false operation, so spacing is a layout decision made before drilling.
Operating the auxiliary release while the switch is powered and locked is published as driving the switch into a fault condition, shown by a blinking red indicator, and the reset is a power cycle rather than a command. That behaviour is why the release is behind a cover: an unplanned release does not quietly unlock the guard, it stops the switch until someone clears it.
| Parameter | Value |
| Catalog number | 440G-TZS21UPRH |
| Enclosure type rating | IP66, IP67, IP69K; IP69K requires appropriate IP-rated glands or cordset |
| Operating temperature | -20...+60 °C (-4...+140 °F) |
| Housing and actuator material | Housing UL-approved glass-filled PBT; actuator stainless steel |
| Weight | 400 g (0.88 lb) |
| Body length and hole spacing | 126 mm (4.96 in.) overall, 105 mm (4.13 in.) between mounting holes |
| Mounting bolts, max torque | 1.4 N·m (12.39 lb·in) |
| Lid screws, max torque | 1.2 N·m (10.62 lb·in) |
| Terminal screws, max torque | 1.02 N·m (9 lb·in) |
| Break contact force, min | 30 N (7 lbf) |
| Actuation speed | 100 mm (3.94 in.) per minute minimum, 160 mm (6.29 in.)/s maximum |
| Actuation frequency, max | 1 cycle/s |
| Operating radius, min | 160 mm (6.3 in.), 80 mm (3.15 in.) with the flexible actuator 440G-A27143 |
| Mechanical life | 1,000,000 operations |
Mounting rules come from 440G-IN022 and they are mechanical rather than electrical. The switch is not a mechanical stop, so guard stops and guides have to be fitted and the impact of a closing guard must not reach the head or the actuator. The mounting surface must be metal with a low-impedance connection to the machine earthing system, and the bolts that hold the body are therefore part of that path. Tightening figures are 1.4 N·m for the mounting bolts, 1.2 N·m for the lid screws and 1.02 N·m for the terminal screws, and over-torque on a glass-filled PBT housing distorts the body enough to shift the four-entry head out of alignment. For 440G-TZS21UPRH the figures above apply as printed.
Two maintenance intervals are printed, and both are part of the warranty terms. Weekly: operate and check the switching circuit, look for abuse or tampering, inspect the casing for damage and replace a damaged unit. At least every six months: isolate all power, remove the lid, check every terminal for tightness, clean out accumulated fine dirt, inspect the actuator, the cam assembly and the contacts for wear or oxidation, refit the covers at the specified torques, reinstate the power, check operation and reapply tamper-evident varnish to the screws. Repair is not offered in that document; a malfunctioning or damaged switch is replaced before the machine may run again. For 440G-TZS21UPRH the figures above apply as printed.
IP69K is a claim about the gland as much as about the housing. 440G-IN022 annotates the rating with the condition that appropriate IP-rated glands or a suitable cordset are used, so a switch wired through an ordinary cable entry should be read as an IP66/IP67 device in service. The sealed housing needs no cabinet of its own; a washdown or corrosive atmosphere can still justify one, but that is a plant decision rather than a product limitation. On 440G-TZS21UPRH the gland fitted at installation is what decides whether the claim holds.
The figures above are family values from 440G-IN022. For 440G-TZS21UPRH the attributes that do change with the catalog number are the contact set, the solenoid voltage and the entry and actuator combination, and those are stated in the tables earlier on this page.
What this page does not claim matters as much as what it does. It does not state a risk assessment outcome or a required performance level, because those belong to the machine rather than to the catalog number; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The safety, electrical and environmental figures are quoted from the TLSZR/L-GD2 guard locking switch installation instructions, and a figure absent from this page is absent from the publication for this catalog number.