This page documents catalog number 440G-TZS21UPLH, a TLS-Z RFID guard locking switch with the GD2 actuator interface. It is a coded, non-contact interlock with guard locking rather than a tongue-operated switch, and the figures below are quoted from the TLSZR/L-GD2 guard locking switch installation instructions.
| Field | Value |
| Standards | IEC 60947-5-3, IEC 60947-5-1, IEC 61508, ISO 13849-1, ISO 14119 |
| Safety classification | Type 4 interlocking device per ISO 14119, RFID target with high level of coding, PLe Category 4 |
| Safety outputs | two PNP OSSD, 0.2 A maximum each, on at plus 24 V dc, safe state 0 V |
| Auxiliary output | 0.2 A maximum, function depends on variant |
| Assured locking distance | 13 mm (0.51 in.) maximum target distance, 5 mm (0.2 in.) maximum clearance between actuator base and switch when the door is closed |
| Locking force Fmax | plastic pins 1,950 N (488 lbf), steel bolts 2,600 N (585 lbf) |
| Locking force Fzh | plastic pins 1,500 N (337 lbf), steel bolts 2,000 N (450 lbf) |
| Supply | 24 V dc plus 10 percent minus 15 percent; 50 mA with the solenoid de-energized, 120 mA energized with 260 mA inrush |
| Solenoid duty cycle | 100 percent (the technical data sheet states 33 percent for Series F and later) |
| Response time | 75 ms for the first switch plus 25 ms for each additional switch in series, unlimited switches in series |
| Operating cycle | 1 Hz maximum; actuation speed 160 mm/s maximum and 100 mm/min minimum |
| Utilization category | DC-13, 24 V, 200 mA per IEC 60947-5-2 |
| Impulse withstand | 250 V, pollution degree 3, protection class 2, rated insulation 500 V |
| Mechanical life | 1 x 10^6 cycles |
| Temperature | minus 10 to plus 60 C, humidity 5 to 95 percent |
| Enclosure | NEMA 3, 4X, 12, 13 and IP66, IP67, IP69K |
| Connection | 8-pin M12 connector, one metre pigtail |
| Housing | UL approved glass-filled PBT, stainless steel actuator, glass-filled PBT target |
| Pin | Function |
| 1 | white, auxiliary output |
| 3 | green, lock command |
| 4 | yellow, Safety B+ OSSD input |
| 5 | gray, Safety A OSSD output |
| 6 | pink, Safety B OSSD output |
| 7 | blue, ground and 0 V |
| 8 | red, Safety A+ OSSD input |
This variant is the power-to-lock version, and the publication carries an explicit conditional warning about it: it must only be used after a risk assessment has shown that a power-to-release principle is not required. The distinction matters because a power failure on power-to-lock leaves the guard locked rather than released, which is the opposite of what a person trapped inside expects.
The auxiliary output on this catalog number reports lock status rather than door position: it changes state when the lock is either locked or unlocked, independent of the OSSD state. That is the signal a line controller uses to confirm the lock engaged before a cycle starts, and it is not a substitute for the door position reported by the UTRH and UTLH variants.
The OSSD test pulses are published because they constrain the receiving safety input: cross-short pulses of 0.1 ms every 11 s and short-circuit pulses of 0.5 ms every 11 s, with the instruction that the connected control system must tolerate them. A standard input with a 1 ms filter will not see them as a transition, and a fast edge-triggered input will, which is the failure mode a commissioning test is meant to expose.
Crosstalk between two TLS-Z switches has a published minimum spacing of 200 mm, and the same restriction applies to a 440G-LZ or a 440N-Z SensaGuard mounted nearby. The mechanism is magnetic rather than electrical: two inductive fields close together produce nuisance faults and false operation, so spacing is a layout decision made before drilling.
The RFID target has to be taught before use, because this is not done at the factory. Up to eight targets can be learned consecutively, which is the published provision for a damaged or lost target, and learning a new target makes the switch stop recognising the old one. Leaving the lock command open while the first target is taught is part of the published sequence for this variant.
| Parameter | Value |
| Catalog number | 440G-TZS21UPLH |
| Enclosure type rating | IP66, IP67, IP69K; IP69K requires appropriate IP-rated glands or cordset |
| Operating temperature | -20...+60 °C (-4...+140 °F) |
| Housing and actuator material | Housing UL-approved glass-filled PBT; actuator stainless steel |
| Weight | 400 g (0.88 lb) |
| Body length and hole spacing | 126 mm (4.96 in.) overall, 105 mm (4.13 in.) between mounting holes |
| Mounting bolts, max torque | 1.4 N·m (12.39 lb·in) |
| Lid screws, max torque | 1.2 N·m (10.62 lb·in) |
| Terminal screws, max torque | 1.02 N·m (9 lb·in) |
| Break contact force, min | 30 N (7 lbf) |
| Actuation speed | 100 mm (3.94 in.) per minute minimum, 160 mm (6.29 in.)/s maximum |
| Actuation frequency, max | 1 cycle/s |
| Operating radius, min | 160 mm (6.3 in.), 80 mm (3.15 in.) with the flexible actuator 440G-A27143 |
| Mechanical life | 1,000,000 operations |
The unit is not a mechanical stop. Publication 440G-IN022 requires guard stops and guides to be fitted, so the weight of the guard and the impact of closing it are carried by the door hardware and never by the actuator or the head. The switch also has to sit on a metal surface that provides a low-impedance connection to the machine earthing system, which makes the mounting bolts part of the earth path rather than a convenience. The maxima are 1.4 N·m for the mounting bolts, 1.2 N·m for the lid screws and 1.02 N·m for the terminal screws; a screw driven past its figure distorts the glass-filled PBT housing and moves the head alignment the actuator depends on. For 440G-TZS21UPLH the figures above apply as printed.
Maintenance is prescribed at two frequencies. Weekly, the switching circuit is operated and checked, the casing is inspected for signs of abuse or tampering, and a damaged unit is replaced rather than repaired. At least every six months the power is isolated, the lid removed, every terminal checked for tightness, fine dirt cleaned out, the actuator, cam assembly and contacts inspected for wear or oxidation, the covers refitted at the specified torques, the power reinstated, operation rechecked and the tamper-evident varnish reapplied to the screws. The same publication states that any malfunction or damage means the switch is replaced before the machine is allowed to run. For 440G-TZS21UPLH the figures above apply as printed.
IP69K is a claim about the gland as much as about the housing. 440G-IN022 annotates the rating with the condition that appropriate IP-rated glands or a suitable cordset are used, so a switch wired through an ordinary cable entry should be read as an IP66/IP67 device in service. The sealed housing needs no cabinet of its own; a washdown or corrosive atmosphere can still justify one, but that is a plant decision rather than a product limitation. On 440G-TZS21UPLH the gland fitted at installation is what decides whether the claim holds.
The figures above are family values from 440G-IN022. For 440G-TZS21UPLH the attributes that do change with the catalog number are the contact set, the solenoid voltage and the entry and actuator combination, and those are stated in the tables earlier on this page.
The keyswitch position is part of the install step, not a label: the base is rotated until the number printed for the module class lines up with the notch, and a module pressed onto a base set for another class is the failure that produces a module which powers up and never appears on the network. This entry is for 440G-TZS21UPLH.
What this page does not claim matters as much as what it does. It does not state a risk assessment outcome or a required performance level, because those belong to the machine rather than to the catalog number; only what the source publication states is printed here.
No lifecycle statement and no price is implied. The safety, electrical and environmental figures are quoted from the TLSZR/L-GD2 guard locking switch installation instructions, and a figure absent from this page is absent from the publication for this catalog number.
Twelve of the 86 440G records carried on this site, ordered by how close their codes sit to this one. This page is 440G-TZS21UPLH.
This listing is filed in the Allen Bradley Other PLC group on plc-vip.com; the group index is Allen Bradley Other PLC catalogue index, and the 440G-TZS21UPLH page is one entry in it.