This page documents the 1606-XLS180B, a member of the Bulletin 1606 switched-mode power supply range (1606-XLS Performance Power Supply): 12 V output at 15 A, 180 W, with AC 100...240 V input. The selection and specification figures below are quoted from Rockwell publication 1606-TD002, which prints them per catalog number or per model row.
| Attribute | Published value |
| Catalog number | 1606-XLS180B |
| Product family | 1606-XLS Performance Power Supply |
| Output voltage, nominal | 12 V |
| Output current, nominal | 15 A |
| Output power | 180 W |
| Input, AC | AC 100...240 V |
| Input, DC | DC 110...150 V |
| Feature or limitation flag | none printed |
| Position | Value | Meaning |
| Prefix | 1606 | Bulletin number for switched-mode power supplies |
| Series letters | XLS | 1606-XLS Performance Power Supply |
| Digits | 180 | rated output power in watts |
| Voltage letter | B | 12 V |
The rule to carry into a bill of materials check is that the digits are watts and the letter after them is the output voltage, so two strings that differ only in the trailing characters share the power stage and differ in input window, terminal style or coating. A substitution across those characters is a mechanical or environmental decision rather than an electrical one, and the replacement category in the row above tells which kind of re-validation it needs.
| Series attribute | Published value |
| Series | 1606-XLS Performance Power Supply |
| Power range | 80...960 W |
| Overload / boost | 150 % for 5 s |
| Reserve current | 50 % additional current |
| Efficiency, typical | 90.0...95.3 % typical depending on model |
| Operating temperature | -25...+70 degC, derating above 60 degC |
| Terminals | spring terminals, screw terminals on the 960 W frame sizes |
| Mains versions | single-phase 100...240 V AC and three-phase 380...480 V AC versions |
The line exists for the reason printed against it: the line that carries power factor correction, DC OK relay contacts and the highest efficiency in the bulletin. Against this string that means the 15 A output is one point inside a 80...960 W range, and the reserve and boost figures belong to the whole line, so a load sized on the continuous rating plus the published reserve is a load the line is designed to carry rather than one it tolerates.
Three calculations follow from the row above. The output load is the sum of everything on the rail against 15 A, with the published reserve as the allowance for inrush rather than as continuous capacity. The heat inside the enclosure is the output power divided by the efficiency figure for this frame, and it is what a sealed cabinet has to dissipate. The input protection is sized from the input current at the lowest voltage of the AC 100...240 V window, not at nominal mains, because that is where the current is highest.
A supply is a branch-circuit load with its own protection and its own inrush. On 1606-XLS180B, choosing the breaker on the nominal input current is the mistake that shows up as a nuisance trip on a cold morning, when the input voltage is low and the bulk capacitors are empty.
Neighbouring numbers in the XLS series are 1606-XLS120E,1606-XLS120EA, 1606-XLS240-UPS, 1606-XLS240-UPSC. They differ in rated watts, output voltage or input frame rather than in construction, so the selection between them is made on load and on the mains available at the panel.
Single-phase, two-phase and three-phase are different products. The same 24 V output appears on single-phase 100...240 V AC frames and on three-phase 380...480 V AC frames. They are not interchangeable on a panel: the three-phase units exist where the load is too large for a single-phase branch, and each frame carries its own terminal layout and its own derating curve. 1606-XLS180B is the number described on this page.
The -3 and regional suffixes are input variants. A trailing numeric suffix on this bulletin marks an input or regional variant rather than a different output: 380...480 V AC three-phase builds and regional mains builds read the same output current from a different input window. Substituting one for the other across a project is an input-side change, and the output side of the panel does not have to be re-validated. 1606-XLS180B is the number described on this page.
Dc input is a separate application, not an ac fallback. The DC-input members of this bulletin take 110...300 V DC or a battery-range window, and they exist for rail, vehicle and battery-backed panels. A DC input is not an AC supply with a rectifier bolted on the front: the input window, the inrush and the branch protection all change, and the string carries the DC figure explicitly. 1606-XLS180B is the number described on this page.
This string publishes a DC input window as well as an AC one. DC 110...150 V is the DC figure for this row, which is what a battery-backed or rail-fed panel is sized against. A DC feed does not carry the same inrush as an AC feed into a rectifier, and the branch device is selected from the DC current rather than from the AC current.
The comparison that matters before a substitute is ordered is not the watts figure. It is whether the output matches the rail, whether the continuous current covers the load schedule with the published reserve left as inrush, whether the input frame matches the mains at the site, whether the terminals fit the existing wiring, and what the lifecycle category says about re-validating the panel. Two strings that agree on watts can disagree on all five. 1606-XLS180B is the number described on this page.
The published figures on this row are the ones a panel builder can be held to. They are also the ones that change when the string changes by a suffix, so a substitution made on the watts figure alone can move the terminals, the coating or the input frame without anyone noticing until the unit is on the bench. 1606-XLS180B is the number described on this page.
What is 1606-XLS180B? 1606-XLS180B is a 1606-XLS Performance Power Supply in the Bulletin 1606 range: 12 V output at 15 A, 180 W, with AC 100...240 V input.
Is 1606-XLS180B current? No lifecycle status is printed against this string in the source publication used for this page, so no availability claim is made here; the electrical figures are the ones the publication prints for the catalog number.
What decides the input protection for 1606-XLS180B? The input current at the lowest voltage of the AC 100...240 V window, not the nominal mains figure, because that is where the branch current peaks and where a breaker chosen on nominal current trips on a cold start.
No price and no lead time is implied on this page. For 1606-XLS180B the selection, series and lifecycle figures are quoted from Rockwell publication 1606-TD002 and the published catalog number explanation; a field the publication does not print for this string is marked as such rather than estimated from a neighbouring model.
Twelve of the 129 1606 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1606-XLS180B.
Group index: Allen Bradley Other PLC. 1606-XLS180B is filed under that heading in the site's own product tree.