Product Details:
Payment & Shipping Terms:
|
This page documents the 1606-XLS480F-3, a member of the Bulletin 1606 switched-mode power supply range (1606-XLS Performance Power Supply): 48 V output at 10 A, 480 W, with 3 AC 380...480 V input. The selection and specification figures below are quoted from Rockwell publication 1606-TD002, which prints them per catalog number or per model row.
| Attribute | Published value |
| Catalog number | 1606-XLS480F-3 |
| Product family | 1606-XLS Performance Power Supply |
| Output voltage, nominal | 48 V |
| Output current, nominal | 10 A |
| Output power | 480 W |
| Input, AC | 3 AC 380...480 V |
| Input, DC | not printed for this string |
| Feature or limitation flag | three-phase input |
| Position | Value | Meaning |
| Prefix | 1606 | Bulletin number for switched-mode power supplies |
| Series letters | XLS | 1606-XLS Performance Power Supply |
| Digits | 480 | rated output power in watts |
| Voltage letter | F | 48...56 V |
| Trailing suffix | -3 | three-phase input |
The rule to carry into a bill of materials check is that the digits are watts and the letter after them is the output voltage, so two strings that differ only in the trailing characters share the power stage and differ in input window, terminal style or coating. A substitution across those characters is a mechanical or environmental decision rather than an electrical one, and the replacement category in the row above tells which kind of re-validation it needs.
| Series attribute | Published value |
| Series | 1606-XLS Performance Power Supply |
| Power range | 80...960 W |
| Overload / boost | 150 % for 5 s |
| Reserve current | 50 % additional current |
| Efficiency, typical | 90.0...95.3 % typical depending on model |
| Operating temperature | -25...+70 degC, derating above 60 degC |
| Terminals | spring terminals, screw terminals on the 960 W frame sizes |
| Mains versions | single-phase 100...240 V AC and three-phase 380...480 V AC versions |
The line exists for the reason printed against it: the line that carries power factor correction, DC OK relay contacts and the highest efficiency in the bulletin. Against this string that means the 10 A output is one point inside a 80...960 W range, and the reserve and boost figures belong to the whole line, so a load sized on the continuous rating plus the published reserve is a load the line is designed to carry rather than one it tolerates.
The rail load is the first number and it is 10 A; the second is the inrush the loads draw at switch-on, which the published reserve covers only for the time the line states; the third is the input current at the lowest point of the 3 AC 380...480 V window, which is what the branch device has to carry without tripping on a cold start. A supply sized on nominal mains current alone fails the third check in winter.
A supply is a branch-circuit load with its own protection and its own inrush. On 1606-XLS480F-3, choosing the breaker on the nominal input current is the mistake that shows up as a nuisance trip on a cold morning, when the input voltage is low and the bulk capacitors are empty.
Neighbouring numbers in the XLS series are 1606-XLS120E,1606-XLS120EA, 1606-XLS180B, 1606-XLS240-UPS. They differ in rated watts, output voltage or input frame rather than in construction, so the selection between them is made on load and on the mains available at the panel.
Terminals decide the wiring time more than the rating does. Spring terminals, screw terminals, push-in terminals and plug connectors all appear on this bulletin at the same power class. The terminal style is chosen by how the panel is wired and by whether the unit is expected to be swapped on site, and it is part of the catalog string rather than a build option added later. 1606-XLS480F-3 is the number described on this page.
Lifecycle status changes the spare, not the specification. A discontinued string keeps its published electrical figures; what changes is the path Rockwell prints for it: direct replacement, engineering replacement with different mounting or wiring, or no planned replacement. The replacement category is the amount of re-validation work a panel inherits, and it is the reason a bill of materials is read with the lifecycle column next to the rating. 1606-XLS480F-3 is the number described on this page.
Efficiency is a thermal number before it is an energy number. A 90 to 95 percent efficiency figure on a 480 W supply leaves 25 to 48 W of heat inside the enclosure, which is the difference between a sealed cabinet that holds temperature and one that needs forced ventilation. The efficiency band is published per series rather than per model, so the number to check is the one for the frame size that was ordered. 1606-XLS480F-3 is the number described on this page.
This string is a three-phase build. The 380...480 V AC frame exists where the load is too large for a single-phase branch, and the input terminals, the inrush and the branch protection are three-phase ones. A panel that carries this unit cannot be fed from a single-phase drop even though the output voltage is the same as a single-phase model of the same wattage.
The feature flag on this row reads: three-phase input. That flag is the field that separates this number from its neighbours of the same wattage and voltage, and it is the one to read first in a substitution, because a supply that differs only in its flag differs in mounting, terminals or output limitation rather than in power.
At 480 W this row sits in the high-power frames. Above roughly 480 W the terminals change to the larger screw or push-in sets and the unit needs the clearance a full-depth cabinet gives it, which is the mechanical difference a drawing has to show. A supply of this size also turns the enclosure thermal calculation into the deciding one, because the loss inside the cabinet is now tens of watts.
The comparison that matters before a substitute is ordered is not the watts figure. It is whether the output matches the rail, whether the continuous current covers the load schedule with the published reserve left as inrush, whether the input frame matches the mains at the site, whether the terminals fit the existing wiring, and what the lifecycle category says about re-validating the panel. Two strings that agree on watts can disagree on all five. 1606-XLS480F-3 is the number described on this page.
The published figures on this row are the ones a panel builder can be held to. They are also the ones that change when the string changes by a suffix, so a substitution made on the watts figure alone can move the terminals, the coating or the input frame without anyone noticing until the unit is on the bench. 1606-XLS480F-3 is the number described on this page.
What is 1606-XLS480F-3? 1606-XLS480F-3 is a 1606-XLS Performance Power Supply in the Bulletin 1606 range: 48 V output at 10 A, 480 W, with 3 AC 380...480 V input.
Is 1606-XLS480F-3 current? No lifecycle status is printed against this string in the source publication used for this page, so no availability claim is made here; the electrical figures are the ones the publication prints for the catalog number.
What decides the input protection for 1606-XLS480F-3? The input current at the lowest voltage of the 3 AC 380...480 V window, not the nominal mains figure, because that is where the branch current peaks and where a breaker chosen on nominal current trips on a cold start.
No price and no lead time is implied on this page. For 1606-XLS480F-3 the selection, series and lifecycle figures are quoted from Rockwell publication 1606-TD002 and the published catalog number explanation; a field the publication does not print for this string is marked as such rather than estimated from a neighbouring model.
Twelve of the 129 1606 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1606-XLS480F-3.
Group index: Allen Bradley Other PLC. 1606-XLS480F-3 is filed under that heading in the site's own product tree. Sibling codes of the same group are one click away from that page.