This page documents the 1606-XLP60EQT, a member of the Bulletin 1606 switched-mode power supply range (1606-XLP Compact Power Supply): 24 V output at 2.5 A, 60 W, with AC 100...240 V input. The selection and specification figures below are quoted from Rockwell publication 1606-TD002, which prints them per catalog number or per model row.
| Attribute | Published value |
| Catalog number | 1606-XLP60EQT |
| Product family | 1606-XLP Compact Power Supply |
| Output voltage, nominal | 24 V |
| Output current, nominal | 2.5 A |
| Output power | 60 W |
| Input, AC | AC 100...240 V |
| Input, DC | DC 110...300 V |
| Feature or limitation flag | -40 degC operation |
| Position | Value | Meaning |
| Prefix | 1606 | Bulletin number for switched-mode power supplies |
| Series letters | XLP | 1606-XLP Compact Power Supply |
| Digits | 60 | rated output power in watts |
| Voltage letter | E | 24...28 V |
| Trailing suffix | QT | a suffix not in the published table; read the printed description |
The rule to carry into a bill of materials check is that the digits are watts and the letter after them is the output voltage, so two strings that differ only in the trailing characters share the power stage and differ in input window, terminal style or coating. A substitution across those characters is a mechanical or environmental decision rather than an electrical one, and the replacement category in the row above tells which kind of re-validation it needs.
| Series attribute | Published value |
| Series | 1606-XLP Compact Power Supply |
| Power range | 15...100 W |
| Overload / boost | none - the compact line runs without a power boost stage |
| Reserve current | no published reserve current |
| Efficiency, typical | 77.2...91.0 % typical depending on model |
| Operating temperature | -10...+70 degC, with -40 degC starting variants |
| Terminals | screw and spring terminals, plug connectors on the -XLP50EZ |
| Mains versions | single-phase 100...240 V AC and two-phase 380...480 V AC versions |
The line exists for the reason printed against it: the narrow 22.5...73 mm housings for shallow enclosures and small loads. Against this string that means the 2.5 A output is one point inside a 15...100 W range, and the reserve and boost figures belong to the whole line, so a load sized on the continuous rating plus the published reserve is a load the line is designed to carry rather than one it tolerates.
The rail load is the first number and it is 2.5 A; the second is the inrush the loads draw at switch-on, which the published reserve covers only for the time the line states; the third is the input current at the lowest point of the AC 100...240 V window, which is what the branch device has to carry without tripping on a cold start. A supply sized on nominal mains current alone fails the third check in winter.
A supply is a branch-circuit load with its own protection and its own inrush. On 1606-XLP60EQT, choosing the breaker on the nominal input current is the mistake that shows up as a nuisance trip on a cold morning, when the input voltage is low and the bulk capacitors are empty.
Neighbouring numbers in the XLP series are 1606-XLP100E,1606-XLP100E-2, 1606-XLP100F, 1606-XLP15A. They differ in rated watts, output voltage or input frame rather than in construction, so the selection between them is made on load and on the mains available at the panel.
The boost stage is what makes a supply survive a start-up. The family quotes its overload behaviour as a boost figure - 150 percent for 5 s on the performance line, 120 percent on the essential line - and that is the allowance a contactor coil, a capacitor bank or a motor starter draws when the 24 V rail is already loaded. A supply chosen on continuous watts alone and started against a bank of coils is a supply that trips on the first cold start, and the boost figure is the number that decides it. 1606-XLP60EQT is the number described on this page.
Redundancy modules are a separate product, not a feature. Decoupling diodes and MOSFET redundancy modules sit beside the supply, not inside it: two supplies in parallel without a module share current badly and fail as one. The module is selected by the load current and by whether the two feeds come from the same or from different sources, which is why the module string carries its own current rating. 1606-XLP60EQT is the number described on this page.
Terminals decide the wiring time more than the rating does. Spring terminals, screw terminals, push-in terminals and plug connectors all appear on this bulletin at the same power class. The terminal style is chosen by how the panel is wired and by whether the unit is expected to be swapped on site, and it is part of the catalog string rather than a build option added later. 1606-XLP60EQT is the number described on this page.
This string publishes a DC input window as well as an AC one. DC 110...300 V is the DC figure for this row, which is what a battery-backed or rail-fed panel is sized against. A DC feed does not carry the same inrush as an AC feed into a rectifier, and the branch device is selected from the DC current rather than from the AC current.
The feature flag on this row reads: -40 degC operation. That flag is the field that separates this number from its neighbours of the same wattage and voltage, and it is the one to read first in a substitution, because a supply that differs only in its flag differs in mounting, terminals or output limitation rather than in power.
The comparison that matters before a substitute is ordered is not the watts figure. It is whether the output matches the rail, whether the continuous current covers the load schedule with the published reserve left as inrush, whether the input frame matches the mains at the site, whether the terminals fit the existing wiring, and what the lifecycle category says about re-validating the panel. Two strings that agree on watts can disagree on all five. 1606-XLP60EQT is the number described on this page.
Read this row against the panel it will feed rather than against the catalogue page: the output is what the rail needs, the reserve is what the inrush may borrow, the efficiency is what the cabinet must dissipate, and the input window is what the site must supply. A number that satisfies the first three and fails the fourth is a unit that is correct on paper and unusable on a low-line branch. 1606-XLP60EQT is the number described on this page.
What is 1606-XLP60EQT? 1606-XLP60EQT is a 1606-XLP Compact Power Supply in the Bulletin 1606 range: 24 V output at 2.5 A, 60 W, with AC 100...240 V input.
Is 1606-XLP60EQT current? No lifecycle status is printed against this string in the source publication used for this page, so no availability claim is made here; the electrical figures are the ones the publication prints for the catalog number.
What decides the input protection for 1606-XLP60EQT? The input current at the lowest voltage of the AC 100...240 V window, not the nominal mains figure, because that is where the branch current peaks and where a breaker chosen on nominal current trips on a cold start.
No price and no lead time is implied on this page. For 1606-XLP60EQT the selection, series and lifecycle figures are quoted from Rockwell publication 1606-TD002 and the published catalog number explanation; a field the publication does not print for this string is marked as such rather than estimated from a neighbouring model.
This page links twelve of the 129 1606 records on this site; the closest rating codes come first. This page is 1606-XLP60EQT.
For the surrounding range, open the Allen Bradley Other PLC catalogue index — 1606-XLP60EQT is listed there beside the rest of the other-PLC group. It is the entry point used when a project list is assembled group by group.