Product Details:
Payment & Shipping Terms:
|
This page documents the 1606-XLDC92D, a member of the Bulletin 1606 switched-mode power supply range: 24 V output at 3.8 A, 92 W, with an unprinted input window. The selection and specification figures below are quoted from Rockwell publication 1606-TD002, which prints them per catalog number or per model row.
| Attribute | Published value |
| Catalog number | 1606-XLDC92D |
| Product family | Bulletin 1606 switched-mode power supply |
| Output voltage, nominal | 24 V |
| Output current, nominal | 3.8 A |
| Output power | 92 W |
| Input, AC | not printed for this string |
| Input, DC | DC 24 V |
| Feature or limitation flag | DC-DC converter, NEC Class 2 |
| Series attribute | Published value |
| Series | 1606-XL Power Supply (legacy line) |
| Power range | 60...960 W |
| Overload / boost | not published for this line in the current technical data |
| Reserve current | not published for this line in the current technical data |
| Efficiency, typical | not published for this line in the current technical data |
| Operating temperature | not published for this line in the current technical data |
| Terminals | screw terminals |
| Mains versions | single-phase 100...240 V AC and three-phase 380...480 V AC versions |
The line exists for the reason printed against it: the first generation of Bulletin 1606 that the XLE and XLS lines replaced part by part. Against this string that means the 3.8 A output is one point inside a 60...960 W range, and the reserve and boost figures belong to the whole line, so a load sized on the continuous rating plus the published reserve is a load the line is designed to carry rather than one it tolerates.
Sizing from this row means three numbers that are rarely written down together: the continuous rail load against 3.8 A, the inrush allowance taken from the published reserve of the line, and the heat the unit leaves in the enclosure. The third one is the one that decides whether the cabinet needs a fan, and it follows from the efficiency band for this frame rather than from the watts figure alone. The input current at the lowest point of the published window is the fourth, and it is the one the branch device is sized against.
A supply is a branch-circuit load with its own protection and its own inrush. On 1606-XLDC92D, choosing the breaker on the nominal input current is the mistake that shows up as a nuisance trip on a cold morning, when the input voltage is low and the bulk capacitors are empty.
Neighbouring numbers to 1606-XLDC92D in the XL series are 1606-XLB120E, 1606-XLB240E, 1606-XLB36EH. They differ in rated watts, output voltage or input frame rather than in construction, so the selection between them is made on load and on the mains available at the panel.
Dc input is a separate application, not an ac fallback. The DC-input members of this bulletin take 110...300 V DC or a battery-range window, and they exist for rail, vehicle and battery-backed panels. A DC input is not an AC supply with a rectifier bolted on the front: the input window, the inrush and the branch protection all change, and the string carries the DC figure explicitly.
The boost stage is what makes a supply survive a start-up. The family quotes its overload behaviour as a boost figure - 150 percent for 5 s on the performance line, 120 percent on the essential line - and that is the allowance a contactor coil, a capacitor bank or a motor starter draws when the 24 V rail is already loaded. A supply chosen on continuous watts alone and started against a bank of coils is a supply that trips on the first cold start, and the boost figure is the number that decides it.
Redundancy modules are a separate product, not a feature. Decoupling diodes and MOSFET redundancy modules sit beside the supply, not inside it: two supplies in parallel without a module share current badly and fail as one. The module is selected by the load current and by whether the two feeds come from the same or from different sources, which is why the module string carries its own current rating.
This string publishes a DC input window as well as an AC one. DC 24 V is the DC figure for this row, which is what a battery-backed or rail-fed panel is sized against. A DC feed does not carry the same inrush as an AC feed into a rectifier, and the branch device is selected from the DC current rather than from the AC current.
The feature flag on this row reads: DC-DC converter, NEC Class 2. That flag is the field that separates this number from its neighbours of the same wattage and voltage, and it is the one to read first in a substitution, because a supply that differs only in its flag differs in mounting, terminals or output limitation rather than in power.
The Class 2 marking is a wiring permission, not a rating. A Class 2 limited-power output may be wired with the smaller cable classes and without the same separation rules as a general-purpose circuit, which is why a compact supply carries the marking for sensor and low-power circuits. The limit is an output limit rather than a supply limit, so a Class 2 string does not become a general-purpose supply by loading it harder.
The comparison that matters before a substitute is ordered is not the watts figure. It is whether the output matches the rail, whether the continuous current covers the load schedule with the published reserve left as inrush, whether the input frame matches the mains at the site, whether the terminals fit the existing wiring, and what the lifecycle category says about re-validating the panel. Two strings that agree on watts can disagree on all five.
What this string fixes is narrower than it looks: the power stage, the output voltage and the input window. What the trailing characters add is mechanical and environmental, and what the lifecycle row adds is how much of the panel survives a replacement. Keeping those three groups apart is how a bill of materials stays readable after the first revision.
What is 1606-XLDC92D? 1606-XLDC92D is a switched-mode power supply in the Bulletin 1606 range: 24 V output at 3.8 A, 92 W, with an input window printed in the selection table.
Is 1606-XLDC92D current? No lifecycle status is printed against this string in the source publication used for this page, so no availability claim is made here; the electrical figures are the ones the publication prints for the catalog number.
What decides the input protection for 1606-XLDC92D? The input current at the lowest voltage of the printed window, not the nominal mains figure, because that is where the branch current peaks and where a breaker chosen on nominal current trips on a cold start.
This number is an accessory or a legacy-line member rather than a stand-alone supply row: DC-DC converter, NEC Class 2. Its own catalog string therefore carries the family and the function rather than an output rating, and it is selected by the supply it is paired with - the current rating of that supply, the rail it serves and the mounting it needs - instead of by a watts figure. That is why the selection row above marks the electrical fields the publication does not print for this catalog number.
No price and no lead time is implied on this page. For 1606-XLDC92D the selection, series and lifecycle figures are quoted from Rockwell publication 1606-TD002 and the published catalog number explanation; a field the publication does not print for this string is marked as such rather than estimated from a neighbouring model.
Twelve of the 129 1606 records this shop lists, chosen by code proximity so that the nearest options are one click away. This page is 1606-XLDC92D.