20BP260A0AYNANC0 is a PowerFlex 700 drive, catalog code b=P: 540 V DC input (Y), pre-charge.
The three digits after the voltage letter are the output current in amps - here 260 A. Published ratings: 132 HP normal duty, 110 HP heavy duty, frame 6.
Quick answer. 20BP260A0AYNANC0 is a PowerFlex 700 drive, 540 V DC, normal duty, frame 6, A - IP 20, NEMA/UL Type 1, with conformal coating.
Catalog number |
20BP260A0AYNANC0 |
Voltage rating (b) |
P - 540 V DC input (Y), pre-charge |
Output current rating (c) |
260 A |
Normal duty rating |
132 HP |
Heavy duty rating |
110 HP |
Frame size |
6 |
Enclosure (d) |
A - IP 20, NEMA/UL Type 1, with conformal coating |
HIM (e) |
0 - Blank cover |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
Y - Brake IGBT fitted |
Internal braking resistor (h) |
N - No internal braking resistor |
Emission class (i) |
A - CE filter fitted, CM choke fitted |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Vector control, 24 V DC I/O |
Feedback (l) |
0 - No feedback |
Rating code |
260 - read as the output current in amps |
Source |
20B-TD001 p.6-7 catalog explanation; rating and frame from the Rockwell product page |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 20B-TD001 (Sept 2023) (module specifications) and 20B-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20B (drive), P (voltage), 260 (output current in amps), then nine option positions d to l.
Here: d=A, e=0, f=A, g=Y, h=N, i=A, j=N, k=C, l=0.
Two more positions m and n exist for future use and special firmware; they are omitted on most orders.
Enclosure (d): IP 20, NEMA/UL Type 1, with conformal coating.
HIM (e): Blank cover. Remote HIM codes J and K mount on a panel door and need the stand-alone IP 54 enclosure.
Brake IGBT (g): Brake IGBT fitted. Internal braking resistor (h): No internal braking resistor; Rockwell does not offer the internal resistor on frame 3 and larger.
Emission (i): CE filter fitted, CM choke fitted. Comm slot (j): None. Control and I/O (k): Vector control, 24 V DC I/O. Feedback (l): No feedback.
A 540 V DC input PowerFlex 700 takes its power from a common DC bus instead of a three-phase rectifier.
Pre-charge is in the catalog code (the Y in position b), so the drive expects the DC bus to be brought up by the line-side pre-charge circuit rather than by the drive itself.
This is the difference an engineer checks first: a 20BP is not a drop-in replacement for a 20BD fed from 480 V AC.
Nameplate catalog number, all 16 characters, against this page.
Whether the frame 5 or 6 enclosure is present; open/flange (d=F) and stand-alone (d=G) drives are the same chassis in different packaging.
Encoder board presence (l=1) and the brake IGBT (g=Y), because both are separate hardware, not parameters.
For 20BP260A0AYNANC0 the positions, voltage classes and option codes are transcribed from 20B-TD001 (September 2023), Catalog Number Explanation, pages 6 and 7, and cross-checked against 20B-UM001 page P-5.
Current, power and frame figures for 20BP260A0AYNANC0 are taken from the product page for this catalog number; where that page carries no power rating, none is shown here.
What is 20BP260A0AYNANC0?
PowerFlex 700 drive, 540 V DC input (Y), pre-charge, 260 A output.
What is the output current of 20BP260A0AYNANC0?
260 A.
What does the P code mean?
540 V DC input (Y), pre-charge.
Does 20BP260A0AYNANC0 have a communication option?
None.
What enclosure is 20BP260A0AYNANC0?
IP 20, NEMA/UL Type 1, with conformal coating.
Related catalog numbers in the same rating code as 20BP260A0AYNANC0. Same A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20BP260A0ANNANC0 (260 A, 540 V DC) · 20BP205A3ANNANC0 (205 A, 540 V DC) · 20BP205A0ANNANC0 (205 A, 540 V DC) · 20BP170A0AYNANC0 (170 A, 540 V DC) · 20BP170A0ANNANC1 (170 A, 540 V DC) · 20BP170A0ANNANC0 (170 A, 540 V DC) · 20BP140A3ANNANC0 (140 A, 540 V DC) · 20BP730N0NNNNNC0 (730 A, 540 V DC) · 20BP535U0ANNNNC0 (535 A, 540 V DC)
20BP260A0AYNANC0
This page documents catalog number 20BP260A0AYNANC0, a PowerFlex 700 DC input drive with the 540 V DC precharge build, as published by Rockwell Automation in publication 20B-TD001 and the product data for this catalog number. Every value below comes from those documents; nothing is inferred.
| Specification | Value |
|---|---|
| Output current, normal duty | 260 A |
| Normal duty rating | 132 kW |
| Heavy duty rating | 110 kW |
| Frame | 6 |
| Input voltage rating | 540 V DC, with internal precharge |
| Voltage code in catalog number | P = 540 V DC |
| Input phases | DC bus, no AC rectifier stage |
| Output phases | 3 |
| Output voltage range | 0 V to rated motor voltage |
| Intermittent overload | 110% for up to 1 min, 150% for up to 3 s |
| Instantaneous overcurrent trip | 220...300% of rated current, rating dependent |
| Current limit setting range | 20...160% of rated output current |
| Efficiency | 97.5% at rated amps, nominal line volts |
| Power ride-through | 15 ms at full load |
| Short circuit rating | 200,000 A symmetrical |
| Drive to motor power ratio | Not greater than 2:1, not less than 1:2 |
| Analog inputs / outputs | 2 / 2 |
| Digital inputs / outputs | 6 / 3 |
| Enclosure | IP20, NEMA/UL Type 1, with conformal coating |
| Ambient temperature | 0...50 °C (frames 5...6, most ratings, top label in place) |
| Altitude | 1000 m (3300 ft) without derating |
| Sound level | Frame 6: 72 dB @ 300 CFM fan velocity |
| Height, standalone IP54 build | 1828.8 mm |
| Width, standalone IP54 build | 711.3 mm |
| Depth, standalone IP54 build | 487.8 mm |
| Weight, drive and packaging | 229.07 kg (standalone IP54 build) |
| Power terminal capacity, frame 6 | Per terminal label inside the drive; brake and PE terminals 6.0 N·m (52 lb·in) |
The catalog number is a readable specification once each position is decoded against the bulletin catalog explanation. For this unit the positions read as follows:
| Specification | Value |
|---|---|
| Position in catalog number | Published meaning |
| Enclosure code A | IP20, NEMA/UL Type 1, with conformal coating |
| HIM code 0 | blank cover, no keypad |
| Documentation code A | manual supplied |
| Brake code Y | brake IGBT installed |
| Resistor code N | no drive mounted brake resistor |
| Emission code A | CE filter and common mode choke fitted |
| Communication code N | no communication module |
| Control code C | vector control with 24 V DC I/O |
| Feedback code 0 | no encoder feedback |
The frame number decides the mechanical work. A frame 5 unit and a frame 6 unit differ in height, width, depth, terminal capacity and airflow, so a replacement that moves up a frame changes the mounting plate, the duct length and the cabinet vent free area. That is why the frame is listed next to the amp code on this page rather than buried in a dimension drawing.
The frame number decides the mechanical work. A frame 5 unit and a frame 6 unit differ in height, width, depth, terminal capacity and airflow, so a replacement that moves up a frame changes the mounting plate, the duct length and the cabinet vent free area. That is why the frame is listed next to the amp code on this page rather than buried in a dimension drawing.
Precharge is built in on this build, which means the unit expects to be connected to a live bus through its own charging path before the main contactor closes. Where the panel is wired with a single disconnector to the bus, the auxiliary contact that proves precharge complete is a wiring item, not a parameter: the control sequence has to be told the bus is up, and a drive that closes onto a partly charged bus draws the current step that the precharge circuit exists to prevent.
Only values that appear in 20B-TD001, 20B-IN014 or the Rockwell Automation product data for this catalog number are printed here. Where a figure is not published for this amp code, the table does not carry a substitute: the heavy duty kW row is present only for the codes whose product data states it, and DC input current, radiated emissions class and enclosure dimensions for the AC build are not adopted from other frames or other voltage classes. A missing row means the document is silent, not that the value is zero.
A 540 V DC input drive is a common-bus inverter, not an AC drive with a rectifier in front of it. That single sentence decides most of what an engineer has to check before ordering one: there is no incoming three-phase bridge, no internal AC choke on the supply side, and no line-side fusing inside the package, because the DC bus it sits on is already conditioned by whatever feeds it. The frame, the DC terminal size and the precharge arrangement are therefore the first three items on the drawing, and the option string behind the catalog number decides whether anything else is fitted.
Power ride-through of 15 milliseconds at full load is the number that decides whether a short dip stops the line. Fifteen milliseconds is about one cycle of a 60 Hz supply, which is enough to ride through a contactor chatter or a breaker transfer but nowhere near enough for a two-second sag. Where the site suffers longer disturbances, the answer is not a bigger drive but a DC bus with stored energy or a controlled stop sequence that uses the motor as a brake; the drive's own ride-through figure only tells you how long it can hold the output before it faults.
The CE EMC filter position tells you what the drive was built to meet, and it matters most when the drive is one of several on a shared bus. A filtered build carries common-mode chokes and capacitors intended for the second environment; an unfiltered build assumes the EMC work is done elsewhere in the panel. Retrofitting a filter into an unfiltered frame is not a bolt-on job, because the filter is part of the internal layout, and a project that specifies the wrong build usually discovers it at the site acceptance test rather than at the quotation stage.
Ambient temperature on frames 5 and 6 is quoted as 0 to 50 degrees C for most ratings with the top label in place, and the wording matters: the label is part of the thermal design and removing it changes the rating rather than merely voiding a warranty. Altitude is quoted to 1000 m without derating, so a site above that figure has to apply the published derating curve before the amp code is chosen. Neither of these limits appears on the motor nameplate, which is why they are missed.
The instantaneous overcurrent trip sits above the intermittent rows, at 220 to 300 percent of rated current depending on the rating itself. That band is not a fault level, it is a protection threshold: a short circuit or a flashover in the motor leads pushes the output stage past it in microseconds and the drive shuts down before the module is destroyed. What matters on site is that the threshold moves with the rating, so a replacement drive of a different amp code does not protect the same way, and the motor circuit protector upstream has to be coordinated with the new figure rather than the old one.
Vector control with 24 V DC I/O is the standard configuration in this range, and the position that carries it also decides what the terminal strip looks like. Twenty-four volt control is what most cabinets in Europe and North America already distribute, so a drive wired for it shares the same supply as the safety relay and the pilot devices; a 115 V AC control build exists for plants that still run that voltage, and mixing the two inside one panel means two control supplies, two fuse groups and a labelling exercise that nobody wants during a shutdown.
A replacement schedule is built from three facts that are easy to keep and hard to reconstruct: the catalog string as printed on the label, the power code inside it, and the frame the unit was built on. The suffix letters describe what is fitted, so two drives with the same amp code but different letters are not interchangeable without reading the panel drawing. Recording the full string, rather than the shortened number used in conversation, is what makes a purchase order unambiguous and what lets a spare be ordered years later without a site visit.
Precharge is the part of a common-bus installation that damages hardware when it is treated as an afterthought. A DC bus carries a large capacitor bank across every inverter connected to it, so closing a disconnector onto an uncharged bus produces a current step limited only by wiring resistance. Drives built with an internal precharge circuit ramp that capacitor bank up before the main contactor closes; drives built without one need an external precharge path, an interlock that proves the bus is up, and a control sequence that will not permit the contactor to close early. The difference between the two build styles is a catalog position, and it is worth reading that position rather than assuming.
DC bus terminals change the wiring rules. The input terminals on these units accept DC+ and DC- alongside a brake resistor pair and a protective earth, and the conductor sizes quoted per frame are terminal block capacity, not a recommendation. A common-bus installation also has to decide what happens to the bus when one inverter trips: a drive that faults and stops drawing current leaves the bus charged, and a maintenance person who opens a disconnector without a proven discharge path is the real hazard in the system, not the drive.
An encoder feedback option changes the control architecture rather than just adding a connector. With feedback the drive can close a speed or position loop and hold torque at low speed, which is what a lift, a winder or a positioning axis needs; without it the drive runs open loop on a calculated slip model, which is adequate for fans and pumps and wrong for anything that has to hold a load at zero speed. The encoder supply on this option is 12 V at 250 mA with a differential receiver rated to 250 kHz, so the encoder chosen has to match that interface rather than the other way round.
The difference between a drive that lasts fifteen years and one that fails in three is often the fan and the filter, not the power stage. Fan velocity is published, filter builds are published, and both are serviceable items with a replacement interval; a maintenance schedule that ignores them turns a thermal margin into a thermal failure at the worst possible moment. Publishing the airflow figure with the sound level is the manufacturer's way of saying the cooling is specified, and a panel builder who reads it can size the cabinet vents instead of guessing.
A published efficiency of 97.5 percent at rated amps and nominal line volts sounds like a marketing number until it is turned into heat. Three percent of a 132 kW rating is roughly four kilowatts of loss inside an enclosure that also holds contactors, a PLC and a 24 V supply. That heat has to leave through the cabinet surface or through forced ventilation, and the fan velocity quoted with the sound level figure is the clue: at 200 CFM on frame 5 and 300 CFM on frame 6 the airflow is specified, not optional, and a cabinet built without that airflow will run the drive into its ambient limit on a warm afternoon.
A blank cover instead of a keypad is a deliberate choice, not a stripped unit. In a networked installation the parameters live in the controller and are downloaded on start-up, so a local operator interface adds a place where somebody can change a value that the program will overwrite at the next power cycle. Where commissioning, troubleshooting or local speed control is part of the job, the full numeric keypad version exists in the same catalog string, and the only difference between the two is one character after the enclosure code.
Catalog numbers, options and spare parts for the same PowerFlex 700 range are listed in the Drives & Motors category. This drive itself can be checked against the shop listing at 20BP260A0AYNANC0.
The Allen-Bradley PowerFlex drives and motors category groups the other catalog numbers, options and spare parts in the same range.