Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 20BW098A0AYNANC0, a PowerFlex 700 drive in the 932 V DC input class. The decode and the class definitions come from the drive family's published catalog number explanation and voltage table; the option region is interpreted only where the family publishes a rule for it.
| Specification | Value |
|---|---|
| Catalog number | 20BW098A0AYNANC0 |
| Family (first three characters) | 20B - PowerFlex 700 |
| Input class | W - 932 V DC, precharge Y |
| Rating code | 098 - 098 A |
| Enclosure field | A - IP20, NEMA/UL Type 1 |
| Brake field as ordered | N - no brake IGBT |
| Brake field | Y fitted / N not fitted; standard on frames 0-3, optional on frames 4-6 |
| Highest DC class on this platform | 932 V DC, once above 810 V DC |
| AC class at the same bus level | 690 V AC three-phase, by the 1.35 arithmetic labelled on this page |
| Published rating block for this class | ND and HD horsepower and kW per frame, in the DC input block, 932 V column |
| Not quoted on this page | kW and frame pairing for this string, because only the 932 V column can supply it |
This page documents the braked twin of the other 98 A listing in the 932 V DC class. The two strings are identical up to the brake field, where this one carries Y and the other carries N, and that single character is the whole difference a panel designer has to care about.
The family publishes Y and N against brake IGBT directly, with the brake standard on frames 0 to 3 and optional on frames 4 to 6, so Y here means the brake is fitted. On a common bus that is the difference between a section that can dissipate its regenerative energy into a resistor and one that returns it to the bus for another section to absorb.
Precharge comes from the class letter rather than from the option block. W is listed with precharge Y in the published voltage table, so this drive limits its own inrush when the bus is energised. That is a property of the class, shared with the unbraked twin, and it should not be confused with the brake when a spare is chosen.
The class is the highest DC level in the family, and the AC correspondence is arithmetic labelled as such: three-phase rectification gives about 1.35 times the line voltage, so 690 V yields roughly 931 V and the 932 V DC class corresponds to the 690 V AC class. The correspondence is what allows a retrofit drawing written in AC terms to be matched to a DC-fed section without re-deriving the bus level.
The rating code reads as 098, which is 98 amps under the family's three-character convention for normal-duty amps. Reading the code is independent of both the class letter and the option block, and that independence is why a string should be decoded field by field.
Where the published DC block gives horsepower and kW per frame for each DC voltage, no kW is quoted here for this string. At 98 A a kW figure is usually what a buyer asks for first, so the correct answer is that the 932 V column of the published block is where it comes from, not a figure derived from an adjacent class.
The enclosure field A is IP20 and NEMA/UL Type 1, with F and G covering open and flange mounting and stand-alone wall mounting. On a bus-fed section the cabinet carries the bus and the protection, so the enclosure code describes the drive rather than the installation.
A braked section at this rating is often specified where the machine stops hard and the bus cannot absorb the returned energy fast enough. That is an application decision, and the drive records it in one character; a panel that assumes the brake is present because the rating matches has assumed the one thing the string exists to state.
Terminal documentation applies as for the class: the larger frames publish wire ranges and torques per frame and list input power, DC+, DC-, BR1, BR2, PE and the motor connections as one group. The BR terminals are the brake resistor connections, and they are only useful when the brake IGBT is actually fitted, which is the reason the field is read before the resistor is ordered.
The remaining option characters carry communication slot, control type, feedback and documentation and are not decoded on this page. Two strings this close together are the strongest argument for quoting the full number rather than the rating.
No lifecycle statement and no price is implied. Class and precharge definitions, the brake rule, the rating-code convention, the enclosure field and the terminal grouping are quoted from the drive family's published documentation; the bus arithmetic is labelled as arithmetic.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Codes documented alongside this one are 20BW052A0ANNANC0, 20BW098A0ANNANC0, 20BW142A0ANNANC0, 20BF119A0ANNANC0, and this drive is listed at 20BW098A0AYNANC0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: 20BW098A0AYNANC0 decodes to voltage code W, which 20B-TD001 defines as 932 V DC input (Y), pre-charge, built on frames 5-6. The rating field reads 098 A.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.