Product Details:
Payment & Shipping Terms:
|
This page documents catalog number 20BR365U0ANNNND0, a PowerFlex 700 drive in the 650 V DC input class. The class and option definitions come from the drive family's published catalog number explanation; where the string carries a character the published option set does not cover, this page says so instead of assigning a meaning.
| Specification | Value |
|---|---|
| Catalog number | 20BR365U0ANNNND0 |
| Family | 20B - PowerFlex 700 |
| Input class | R - 650 V DC, precharge Y |
| Rating code | 365 - 365 A |
| Enclosure-position character | U - outside the documented enclosure set A, F, G so not read as an enclosure code |
| Brake field | N - no brake IGBT |
| Final option characters | NNNND0, not decoded on this page |
| AC class at the same bus level | 480 V AC three-phase, by the 1.35 arithmetic labelled on this page |
| Availability basis | No availability statement is made here for this string |
Three hundred and sixty-five amps at 650 V DC is a section size where the panel, not the drive, becomes the engineering subject, and this string also carries a character in the enclosure position that the published option set does not cover. The string reads 20B for PowerFlex 700, R for the 650 V DC class, 365 for the output current, U in the enclosure position, then 0 and a run of N characters ending in D0.
The enclosure set that the family documents is A for IP20 and NEMA/UL Type 1, F for open and flange mounting, and G for stand-alone and wall mounting. A U in that position is outside that set, so this page does not read it as an enclosure code; reporting it as one of the three would be an invention, and the correct statement is that the published catalog explanation does not resolve this string into named fields at that position.
The class letter is unambiguous and it is the one that matters for the bus. R is 650 V DC with precharge Y, the same voltage as J but with the charging path, and the family's split between the two is exactly the split that decides whether a drive can be dropped onto a live bus or needs the charging function built into the panel.
Precharge covers the drive's own DC link, not the installation. At 365 A the link capacitance is large enough that the inrush is a serious event even with an internal limiter, and a multi-section bus still needs a defined energisation order and protection coordinated against the total connected power rather than against one drive.
The AC equivalent of this class is arithmetic and it is labelled as such here: three-phase rectification gives a bus of roughly 1.35 times the line voltage, so 480 V corresponds to about 648 V and the 650 V DC class is the direct-current counterpart of the 480 V AC class. Retrofits are usually described in AC terms in the existing drawings, so the correspondence is the first step of a like-for-like comparison.
The brake field reads N in this string, and the family's rule makes that a definite statement rather than a guess: N means no brake IGBT, and the brake is optional on frames 4 to 6. A section at this current without a brake returns its regenerative energy to the bus, which is a system decision and not a defect.
The rating code reads as 365 A output under the family's convention for the three characters after the voltage letter. That convention is consistent across the AC and DC classes, which is what makes the reading safe independently of the class letter.
Terminal documentation is the part of the published data that carries most weight at this size. The family publishes wire ranges and torque values frame by frame and lists input power, DC+, DC-, BR1, BR2, PE and the motor connections as one group on the larger frames, so the DC terminals that carry the bus continuously have a specified range and a specified torque, and both are maintenance items.
The drive documentation also publishes input protection device tables separately for the 540 V DC and 650 V DC inputs, organised by frame. On a drive of this size the protection coordination is the difference between a fault that clears and a fault that takes the bus with it, and the table for the 650 V class is the one that applies.
The final characters are not decoded. A run of N values followed by D0 is a pattern that this page does not resolve into named fields, and the only honest statement about it is that it is unresolved rather than that it means nothing.
No lifecycle statement and no price is implied, and no availability claim is made for this string beyond what the published tables actually state.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Codes documented alongside this one are 20BR156A0AYNANC0, 20BR535U0ANNNND1, 20BF142A0ANNANC0, and this drive is listed at 20BR365U0ANNNND0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BR365U0ANNNND0 is R: 650 V DC input (Y), pre-charge, frames 5-8 in the catalog explanation, with 365 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.