This page documents catalog number 20BR125A3ANNANC0, a PowerFlex 700 drive in the 650 V DC input class at 125 A. The decode and the class definitions come from the drive family's published catalog number explanation and voltage table; the option region is interpreted only where the family publishes a rule for it.
| Specification | Value |
|---|---|
| Catalog number | 20BR125A3ANNANC0 |
| Family (first three characters) | 20B - PowerFlex 700 |
| Input class (fourth character) | R - 650 V DC |
| Precharge as published for this class | R is listed with precharge Y |
| AC class this bus level corresponds to | 480 V AC three-phase, by the 1.35 factor stated as arithmetic on this page |
| Rating code | 125 - 125 A |
| Enclosure field | A - IP20, NEMA/UL Type 1 |
| Brake field, per the family rule | Y fitted / N not fitted; standard on frames 0-3, optional on frames 4-6 |
| Frame character in this string | 3 |
| Published rating block for this class | ND and HD horsepower and kW per frame, in the DC input block, 650 V DC column |
| Not quoted on this page | kW and frame pairing for this string, because only the 650 V DC column of that block can supply it |
This is a 650 V DC entry, and the letter that produces it is the one that most often gets read as an AC class by mistake. The string reads 20B for PowerFlex 700, R for the 650 V DC input, 125 for the output current in amps, A for the enclosure field and 3 in the frame position that follows it.
The family publishes two entries at 650 V DC, J without precharge and R with precharge, in the same way it publishes H and P at 540 V DC. So the difference between a 650 V DC drive that can limit its own inrush and one that cannot is a single letter, and a spare order that keeps the voltage and the current but changes that letter changes the charging behaviour of the panel.
The class voltage is worth relating back to the AC world, and the relation is arithmetic rather than a published claim: a three-phase supply rectifies to a bus of roughly 1.35 times its line voltage, so 480 V produces about 648 V and the 650 V DC class is the direct-current counterpart of the 480 V AC class. That is the sentence an engineer needs when a common-bus retrofit has to keep the existing 480 V-fed drive ratings and shared bus.
The rating code reads as output current, which is the family's convention: three characters for the ND amps, with P in place of the decimal point for fractional values. 125 therefore reads as 125 A, and the reading does not change with the voltage class.
The frame character is visible in the string and the terminal data is published per frame, so the mechanical consequences of this rating are documented even where the kW row is not quoted on this page. The larger frames list input power, DC+, DC-, BR1, BR2, PE and motor connections on one terminal group with a specified wire range and torque, and those figures are what an installer actually works to.
Precharge on the R entry also means an internal path for charging the DC link, but it does not mean the panel can be designed without thinking about the bus. A precharged drive limits its own inrush; it does not decide the sequence in which the sections are energised, and a common-bus panel with several precharged drives still needs a defined energisation order if the upstream protection is to be coordinated.
The enclosure field A is IP20 and NEMA/UL Type 1 as the family defines it, with the F and G codes covering open and flange mounting and stand-alone wall mounting. A panel-mounted drive on a DC bus leaves the bus bars, the charging arrangement and the coordination to the cabinet, which is a larger scope than the drive's own specification.
The brake field is decodable from the family's published table, where Y and N map to brake IGBT fitted or not, standard on frames 0 to 3 and optional on frames 4 to 6. On a common bus a fitted brake IGBT is the difference between a section that can dump regeneration into a resistor and one that returns it to the bus.
The other option characters carry communication slot, control type and documentation, and they are not interpreted here. A string this long has more than one field whose position depends on the total length, and the only safe statement about an unread field is that it is unread.
The practical consequence of the R letter for a maintenance store is that the register should record it. Two 650 V DC drives of the same current differ only in precharge, and a store holding the number without the letter will order the wrong charging behaviour and discover it when the panel is energised.
No lifecycle statement and no price is implied. The class and precharge definitions, the rating-code convention, the enclosure field, the brake rule and the terminal grouping are quoted from the drive family's published documentation; the bus arithmetic is labelled as arithmetic.
The other drives, reactors and drive spares in this range are collected in the Drives & Motors category. Codes documented alongside this one are 20BN260A0AYNANC0, 20BR156A0ANNANC0, 20BR248A0AYNANC0, and this drive is listed at 20BR125A3ANNANC0.
The fourth character of a 20B catalog number is the voltage code, and there are twelve of them: five AC classes and seven DC-bus classes. They are not interchangeable, they do not share frame ranges, and the DC codes additionally split on whether a pre-charge circuit is built in. This table is the complete code list from the 20B-TD001 catalog explanation, with the frame range each class is built on.
| Code | Voltage rating | Frames built on | Where the class is used |
| B | 240 V AC, 3-phase, 50/60 Hz | 0-6 | 208...240 V supply, the North American low-voltage class |
| C | 400 V AC, 3-phase, 50/60 Hz | 0-6 | 380...415 V supply, the European standard class |
| D | 480 V AC, 3-phase, 50/60 Hz | 0-6 | 440...480 V supply, the widest rating ladder of the series |
| E | 600 V AC, 3-phase, 50/60 Hz | 0-6 | 575...600 V supply, Canada and heavy industry |
| F | 690 V AC, 3-phase, 50/60 Hz | 5-6 | 690 V supply, and only on the larger frames |
| H | 540 V DC input, pre-charge | 5-6 | fed from a 540 V DC bus, pre-charge circuit built in |
| J | 650 V DC input | 5-6 | 650 V DC common DC bus, no pre-charge letter |
| N | 325 V DC input (Y), pre-charge | 5-6 | 325 V DC bus, common-bus configuration |
| P | 540 V DC input (Y), pre-charge | 5-8 | 540 V DC common bus, the widest DC frame range |
| R | 650 V DC input (Y), pre-charge | 5-8 | 650 V DC common bus, frames 5 through 8 |
| T | 810 V DC input (Y), pre-charge | 5-6 | 810 V DC bus for 600 V class front ends |
| W | 932 V DC input (Y), pre-charge | 5-6 | 932 V DC bus for 690 V class front ends |
Where this page sits: The fourth character of 20BR125A3ANNANC0 is R: 650 V DC input (Y), pre-charge, frames 5-8 in the catalog explanation, with 125 A in the rating field.
What is missing here is the ladder itself: the rating tables that turn these codes into amp, power and frame steps are printed per voltage class in 20B-TD001, and only the 240, 400 and 480 V classes were transcribed for this site. For 600 V, 690 V and the DC-bus classes the neighbouring current steps are therefore not listed, and none is inferred from another class.
Catalog prefix first: 20B is the PowerFlex 700 prefix and 20A is the PowerFlex 70 prefix. A page filed under a "PowerFlex 70 drives" group while carrying a 20B number is a filing error at the prefix level - the two are different product lines with different frame ranges, not variants of one another. The catalog number on the page decides, not the group label.
Source: 20B-TD001 PowerFlex 700 catalog number explanation (voltage, rating and frame codes) and the 20B-TD001 rating tables. Values are quoted as printed; no figure on this page is calculated or extrapolated.