20BP535U0ANNNNC0 is a PowerFlex 700 drive, catalog code b=P: 540 V DC input (Y), pre-charge.
The three digits after the voltage letter are the output current in amps - here 535 A. Rockwell does not publish a power rating for this catalog number on its product page, so this page states the current rating only.
Quick answer. 20BP535U0ANNNNC0 is a PowerFlex 700 drive, 540 V DC, normal duty, frame 5-8 range for this voltage class, U - Chassis, no enclosure in the catalog number.
Catalog number |
20BP535U0ANNNNC0 |
Voltage rating (b) |
P - 540 V DC input (Y), pre-charge |
Output current rating (c) |
535 A |
Frame size |
Frame 5-8 range for this voltage class |
Enclosure (d) |
U - Chassis, no enclosure in the catalog number |
HIM (e) |
0 - Blank cover |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
N - No brake IGBT |
Internal braking resistor (h) |
N - No internal braking resistor |
Emission class (i) |
N - No CE filter, no CM choke |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Vector control, 24 V DC I/O |
Feedback (l) |
0 - No feedback |
Rating code |
535 - read as the output current in amps |
Source |
20B-TD001 p.6-7 catalog explanation; rating and frame from the Rockwell product page |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 20B-TD001 (Sept 2023) (module specifications) and 20B-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20B (drive), P (voltage), 535 (output current in amps), then nine option positions d to l.
Here: d=U, e=0, f=A, g=N, h=N, i=N, j=N, k=C, l=0.
Two more positions m and n exist for future use and special firmware; they are omitted on most orders.
Enclosure (d): no enclosure code - the drive ships as a chassis unit.
HIM (e): Blank cover. Remote HIM codes J and K mount on a panel door and need the stand-alone IP 54 enclosure.
Brake IGBT (g): No brake IGBT. Internal braking resistor (h): No internal braking resistor; Rockwell does not offer the internal resistor on frame 3 and larger.
Emission (i): No CE filter fitted. Comm slot (j): None. Control and I/O (k): Vector control, 24 V DC I/O. Feedback (l): No feedback.
A 540 V DC input PowerFlex 700 takes its power from a common DC bus instead of a three-phase rectifier.
Pre-charge is in the catalog code (the Y in position b), so the drive expects the DC bus to be brought up by the line-side pre-charge circuit rather than by the drive itself.
This is the difference an engineer checks first: a 20BP is not a drop-in replacement for a 20BD fed from 480 V AC.
Nameplate catalog number, all 16 characters, against this page.
Whether the frame 5 or 6 enclosure is present; open/flange (d=F) and stand-alone (d=G) drives are the same chassis in different packaging.
Encoder board presence (l=1) and the brake IGBT (g=Y), because both are separate hardware, not parameters.
For 20BP535U0ANNNNC0 the positions, voltage classes and option codes are transcribed from 20B-TD001 (September 2023), Catalog Number Explanation, pages 6 and 7, and cross-checked against 20B-UM001 page P-5.
Current, power and frame figures for 20BP535U0ANNNNC0 are taken from the product page for this catalog number; where that page carries no power rating, none is shown here.
What is 20BP535U0ANNNNC0?
PowerFlex 700 drive, 540 V DC input (Y), pre-charge, 535 A output.
What is the output current of 20BP535U0ANNNNC0?
535 A.
What does the P code mean?
540 V DC input (Y), pre-charge.
Does 20BP535U0ANNNNC0 have a communication option?
None.
What enclosure is 20BP535U0ANNNNC0?
No enclosure code - chassis unit.
Related catalog numbers in the same rating code as 20BP535U0ANNNNC0. Same A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20BP260A0AYNANC0 (260 A, 540 V DC) · 20BP260A0ANNANC0 (260 A, 540 V DC) · 20BP205A3ANNANC0 (205 A, 540 V DC) · 20BP205A0ANNANC0 (205 A, 540 V DC) · 20BP170A0AYNANC0 (170 A, 540 V DC) · 20BP170A0ANNANC1 (170 A, 540 V DC) · 20BP170A0ANNANC0 (170 A, 540 V DC) · 20BP140A3ANNANC0 (140 A, 540 V DC) · 20BP730N0NNNNNC0 (730 A, 540 V DC)
20BP535U0ANNNNC0
This page documents catalog number 20BP535U0ANNNNC0, a PowerFlex 700 DC input drive built on frame 8 with the 540 V DC precharge arrangement, as published by Rockwell Automation in 20B-IN014 and 20B-TD001. Every value below comes from those publications; nothing is inferred.
| Specification | Value |
|---|---|
| Output current, normal duty | 535 A |
| Normal duty rating | 300 kW at 2 kHz, 40 °C |
| Heavy duty rating | 280 kW, 481 A continuous |
| DC input rating | 627 A, 338 kW at 300 kW output |
| Output current, 1 min | 589 A |
| Output current, 3 s | 803 A |
| Semiconductor fuse | 1000 A, catalog number 170M6614 |
| Frame | 8 |
| Input voltage rating | 540 V DC, with internal precharge |
| Voltage code in catalog number | P = 540 V DC |
| Input | DC bus, no AC rectifier stage, DC+ and DC- terminals |
| Output phases | 3 |
| Precharge interlock | Auxiliary contact on the disconnector to a digital input, parameter 361...366 set to option 30 precharge enable, and to TB1 on the precharge board |
| Precharge board jumpers | JMP1: 1-2 = 24 V DC input, 2-3 = 120 V AC input. JMP2: 1-2 = interlock, 2-3 = bypass (default). JMP3: 1-2 = do not use, 2-3 = bypass |
| Disconnector rule | Not to be used between the drive input and a common DC bus without an external precharge device |
| Control voltage code | C = vector control with 24 V DC I/O |
| Lifecycle | Bulletin announced discontinued 2023-11-30, replacement category Engineering Replacement |
The catalog number is a readable specification once each position is decoded against the bulletin catalog explanation. For this unit the positions read as follows:
| Specification | Value |
|---|---|
| Position in catalog number | Published meaning |
| Enclosure position | letter U, as printed in the catalog number |
| HIM code 0 | blank cover, no keypad |
| Documentation code A | manual supplied |
| Brake code N | no brake IGBT |
| Resistor code N | no drive mounted brake resistor |
| Emission code N | no internal CE filter |
| Communication code N | no communication module |
| Control code C | vector control with 24 V DC I/O |
| Feedback code 0 | no encoder feedback |
Every row of this table is a site decision, not a catalog curiosity. The fuse catalog number has to be bought as a semiconductor fuse of that family, the switching frequency and ambient go together, and the precharge interlock is a wiring item that has to exist before the disconnector is closed. A drive that arrives with factory jumper positions and factory defaults is a drive that has not yet been configured for the panel it was bought for.
Every row of this table is a site decision, not a catalog curiosity. The fuse catalog number has to be bought as a semiconductor fuse of that family, the switching frequency and ambient go together, and the precharge interlock is a wiring item that has to exist before the disconnector is closed. A drive that arrives with factory jumper positions and factory defaults is a drive that has not yet been configured for the panel it was bought for.
The DC+ and DC- terminals are the only power connection to the bus, which means the drive's protection against a bus fault is the fuse and the overcurrent trip, in that order. Nothing upstream in the drive limits the current coming out of a shared capacitor bank. That is why the instructions insist on the fuse by catalog number rather than by amp rating, and why the panel drawing should show it as part of the drive branch.
Only values that appear in 20B-IN014 or 20B-TD001 are printed here. The heavy duty row, the DC input current, the fuse catalog number and the one minute and three second output columns are taken from the frames 7...10 installation instructions rather than transferred from another frame or another voltage class. Where a figure is not published for this catalog number the table says so instead of carrying a substitute; enclosure position letters are quoted as printed in the catalog number, and the IP class for these frames is stated in the frames 7...10 instructions rather than in the seed catalog explanation.
The fuse figures in this range are semiconductor fuses with published catalog numbers, not generic ampere ratings. That matters because the fuse has to protect the module before the module's own overcurrent trip acts, and a substitute of the same amp rating from a different family does not carry the same clearing characteristic. The instructions list the fuse by catalog number alongside the DC input current, which is the only honest way to specify it for a retrofit.
Common-bus arrangements pay off where several motors work against each other: one axis regenerating while another accelerates, with the energy circulating on the bus instead of being dissipated. The cost is that the bus becomes a single point of failure with several owners. A drive page that publishes the DC input current, the fuse catalog number and the precharge interlock requirement gives the panel designer the three facts needed to make that shared asset safe rather than merely functional.
A spare for a frame 7 through 10 unit is a capital item, and the decision to hold one is usually taken after the first unplanned stop. The information needed to place that order years later is the full catalog string, the fuse catalog number and the jumper settings as found on site. Two of those three live in the installation instructions, which is why a page that quotes them from the publication is worth more than one that repeats a sales description.
Where the drive is fed through a disconnector from a common DC bus, the instructions are explicit: an auxiliary contact on the disconnector must be wired to a digital input, and the corresponding parameter between 361 and 366 must be set to option 30, precharge enable. The same auxiliary contact also goes to TB1 on the precharge board so the board knows the disconnector state. Skipping either half leaves the drive able to close onto an uncharged bus, which is the failure the interlock exists to prevent.
A drive this size is usually ordered as a spare against an existing line rather than as new equipment, and the suffix letters decide whether the spare can be dropped in. A unit with the manual and the filtered build is not the same physical object as one supplied without a manual and without the filter, even though the power code, the frame and the DC input current are identical. Recording only the amp code is how a spare arrives that fits the mounting but not the panel drawing.
Terminal capacity and torque on the larger frames are stated per frame rather than per amp code, because the power structure is the same across several ratings. Tightening a DC terminal to a torque taken from a smaller frame is a common field error: the terminal accepts the conductor, the joint is under-torqued, and the failure appears months later as a hot spot rather than as an immediate fault.
Frames 7 through 10 are the part of this range where the installation instructions, not the catalog explanation, become the working document. At these ratings the drive is a cabinet-mounted power structure with a precharge board, a TB1 terminal strip and jumper blocks that have to be set for the site's control voltage before the first energisation. A drive ordered from a suffix string arrives with the factory default jumper positions, and the default is not always the one the panel was designed around.
Switching frequency on the larger frames is 2 kHz, and 4 kHz on frame 7. That figure is not a preference: it is the value the published ratings were established at, together with the ambient temperature printed in the same row. Choosing a higher switching frequency to reduce audible noise moves the drive outside the derating table, and the amp code that looked adequate on paper then has to be re-checked against the derating curves before the order is placed.
The published ambient for these rows is 40 degrees C, and it is printed in the same table as the switching frequency because the two together define the rating. A cabinet that reaches 45 degrees C in summer is outside the row the drive was selected from, and the answer is not a bigger drive but either more airflow or a lower switching frequency. Neither adjustment is obvious from a nameplate, which is why both figures belong on the page rather than in an appendix.
Precharge resistors and contactors are wear items on a common-bus drive. Every energisation charges a capacitor bank through the precharge path, so the number of starts over a decade is not a trivial count. A maintenance schedule that records precharge operations, rather than only running hours, predicts the failure before the board does, and the jumper settings are part of that record because a board left in bypass charges the bus through the wrong path.
The rule that a disconnect switch must not sit between the drive input and a common DC bus without an external precharge device is written into the instructions for a reason. The bus is shared, so a disconnector on one inverter branch is not a local isolator: it separates a capacitor bank from a supply that other inverters are still charging. Anyone who treats it as a maintenance isolator and opens it under load is opening a DC circuit that has no natural current zero.
These catalog numbers belong to a bulletin that was announced as discontinued with an engineering replacement category. Engineering replacement means the successor is a different design, so the precharge board, the TB1 wiring and the jumper settings of the old unit have no direct equivalent in the new one; the changeover is a re-engineering task with a commissioning window, not a like-for-like exchange during a weekend shutdown.
The one minute and three second columns describe what the output stage will hold during a load step. At these ratings the three second figure is several hundred amps above continuous, which is what carries a heavy conveyor through a start. The motor, the cable and the protector all have to tolerate that current for the same duration, so the drive's overload row is a system constraint rather than a drive-only specification.
Catalog numbers, options and spare parts for the same PowerFlex 700 range are listed in the Drives & Motors category. This drive itself can be checked against the shop listing at 20BP535U0ANNNNC0.