20BP325A0ANNNNC0 is a PowerFlex 700 drive, catalog code b=P: 540 V DC input (Y), pre-charge.
The three digits after the voltage letter are the output current in amps - here 325 A. Rockwell does not publish a power rating for this catalog number on its product page, so this page states the current rating only.
Quick answer. 20BP325A0ANNNNC0 is a PowerFlex 700 drive, 540 V DC, normal duty, frame 5-8 range for this voltage class, A - IP 20, NEMA/UL Type 1, with conformal coating.
Catalog number |
20BP325A0ANNNNC0 |
Voltage rating (b) |
P - 540 V DC input (Y), pre-charge |
Output current rating (c) |
325 A |
Frame size |
Frame 5-8 range for this voltage class |
Enclosure (d) |
A - IP 20, NEMA/UL Type 1, with conformal coating |
HIM (e) |
0 - Blank cover |
Documentation (f) |
A - Manual included |
Brake IGBT (g) |
N - No brake IGBT |
Internal braking resistor (h) |
N - No internal braking resistor |
Emission class (i) |
N - No CE filter, no CM choke |
Comm slot (j) |
N - None |
Control and I/O (k) |
C - Vector control, 24 V DC I/O |
Feedback (l) |
0 - No feedback |
Rating code |
325 - read as the output current in amps |
Source |
20B-TD001 p.6-7 catalog explanation; rating and frame from the Rockwell product page |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 20B-TD001 (Sept 2023) (module specifications) and 20B-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The string is 20B (drive), P (voltage), 325 (output current in amps), then nine option positions d to l.
Here: d=A, e=0, f=A, g=N, h=N, i=N, j=N, k=C, l=0.
Two more positions m and n exist for future use and special firmware; they are omitted on most orders.
Enclosure (d): IP 20, NEMA/UL Type 1, with conformal coating.
HIM (e): Blank cover. Remote HIM codes J and K mount on a panel door and need the stand-alone IP 54 enclosure.
Brake IGBT (g): No brake IGBT. Internal braking resistor (h): No internal braking resistor; Rockwell does not offer the internal resistor on frame 3 and larger.
Emission (i): No CE filter fitted. Comm slot (j): None. Control and I/O (k): Vector control, 24 V DC I/O. Feedback (l): No feedback.
A 540 V DC input PowerFlex 700 takes its power from a common DC bus instead of a three-phase rectifier.
Pre-charge is in the catalog code (the Y in position b), so the drive expects the DC bus to be brought up by the line-side pre-charge circuit rather than by the drive itself.
This is the difference an engineer checks first: a 20BP is not a drop-in replacement for a 20BD fed from 480 V AC.
Nameplate catalog number, all 16 characters, against this page.
Whether the frame 5 or 6 enclosure is present; open/flange (d=F) and stand-alone (d=G) drives are the same chassis in different packaging.
Encoder board presence (l=1) and the brake IGBT (g=Y), because both are separate hardware, not parameters.
For 20BP325A0ANNNNC0 the positions, voltage classes and option codes are transcribed from 20B-TD001 (September 2023), Catalog Number Explanation, pages 6 and 7, and cross-checked against 20B-UM001 page P-5.
Current, power and frame figures for 20BP325A0ANNNNC0 are taken from the product page for this catalog number; where that page carries no power rating, none is shown here.
What is 20BP325A0ANNNNC0?
PowerFlex 700 drive, 540 V DC input (Y), pre-charge, 325 A output.
What is the output current of 20BP325A0ANNNNC0?
325 A.
What does the P code mean?
540 V DC input (Y), pre-charge.
Does 20BP325A0ANNNNC0 have a communication option?
None.
What enclosure is 20BP325A0ANNNNC0?
IP 20, NEMA/UL Type 1, with conformal coating.
Related catalog numbers in the same rating code as 20BP325A0ANNNNC0. Same A power stage, different option string - the enclosure, HIM, communication and safety positions are what change between them.
20BP260A0AYNANC0 (260 A, 540 V DC) · 20BP260A0ANNANC0 (260 A, 540 V DC) · 20BP205A3ANNANC0 (205 A, 540 V DC) · 20BP205A0ANNANC0 (205 A, 540 V DC) · 20BP170A0AYNANC0 (170 A, 540 V DC) · 20BP170A0ANNANC1 (170 A, 540 V DC) · 20BP170A0ANNANC0 (170 A, 540 V DC) · 20BP140A3ANNANC0 (140 A, 540 V DC) · 20BP730N0NNNNNC0 (730 A, 540 V DC) · 20BP535U0ANNNNC0 (535 A, 540 V DC)
20BP325A0ANNNNC0
This page documents catalog number 20BP325A0ANNNNC0, a PowerFlex 700 DC input drive built on frame 7 with the 540 V DC precharge arrangement, as published by Rockwell Automation in 20B-IN014 and 20B-TD001. Every value below comes from those publications; nothing is inferred.
| Specification | Value |
|---|---|
| Output current, normal duty | 325 A |
| Normal duty rating | 180 kW at 4 kHz, 40 °C |
| Heavy duty rating | 180 kW, 325 A continuous |
| DC input rating | 381 A, 206 kW at 180 kW output |
| Output current, 1 min | 358 A |
| Output current, 3 s | 488 A |
| Semiconductor fuse | 630 A, catalog number 170M6610 |
| Frame | 7 |
| Input voltage rating | 540 V DC, with internal precharge |
| Voltage code in catalog number | P = 540 V DC |
| Input | DC bus, no AC rectifier stage, DC+ and DC- terminals |
| Output phases | 3 |
| Precharge interlock | Auxiliary contact on the disconnector to a digital input, parameter 361...366 set to option 30 precharge enable, and to TB1 on the precharge board |
| Precharge board jumpers | JMP1: 1-2 = 24 V DC input, 2-3 = 120 V AC input. JMP2: 1-2 = interlock, 2-3 = bypass (default). JMP3: 1-2 = do not use, 2-3 = bypass |
| Disconnector rule | Not to be used between the drive input and a common DC bus without an external precharge device |
| Control voltage code | C = vector control with 24 V DC I/O |
| Lifecycle | Bulletin announced discontinued 2023-11-30, replacement category Engineering Replacement |
The catalog number is a readable specification once each position is decoded against the bulletin catalog explanation. For this unit the positions read as follows:
| Specification | Value |
|---|---|
| Position in catalog number | Published meaning |
| Enclosure code A | IP20, NEMA/UL Type 1, with conformal coating |
| HIM code 0 | blank cover, no keypad |
| Documentation code A | manual supplied |
| Brake code N | no brake IGBT |
| Resistor code N | no drive mounted brake resistor |
| Emission code N | no internal CE filter |
| Communication code N | no communication module |
| Control code C | vector control with 24 V DC I/O |
| Feedback code 0 | no encoder feedback |
The DC+ and DC- terminals are the only power connection to the bus, which means the drive's protection against a bus fault is the fuse and the overcurrent trip, in that order. Nothing upstream in the drive limits the current coming out of a shared capacitor bank. That is why the instructions insist on the fuse by catalog number rather than by amp rating, and why the panel drawing should show it as part of the drive branch.
The DC+ and DC- terminals are the only power connection to the bus, which means the drive's protection against a bus fault is the fuse and the overcurrent trip, in that order. Nothing upstream in the drive limits the current coming out of a shared capacitor bank. That is why the instructions insist on the fuse by catalog number rather than by amp rating, and why the panel drawing should show it as part of the drive branch.
Frames 7 through 9 carry an internal precharge board, and frame 10 does not; the instructions treat the two cases separately. Where the board is present, the interlock contact goes to TB1 and the drive is expected to see the disconnector state on a digital input. Where the board is absent, precharge capability has to be provided by the system, which means an external charging path and its own interlock. Mixing the two procedures is how a drive gets energised through a path nobody verified.
Only values that appear in 20B-IN014 or 20B-TD001 are printed here. The heavy duty row, the DC input current, the fuse catalog number and the one minute and three second output columns are taken from the frames 7...10 installation instructions rather than transferred from another frame or another voltage class. Where a figure is not published for this catalog number the table says so instead of carrying a substitute; enclosure position letters are quoted as printed in the catalog number, and the IP class for these frames is stated in the frames 7...10 instructions rather than in the seed catalog explanation.
Frames 7 through 10 are the part of this range where the installation instructions, not the catalog explanation, become the working document. At these ratings the drive is a cabinet-mounted power structure with a precharge board, a TB1 terminal strip and jumper blocks that have to be set for the site's control voltage before the first energisation. A drive ordered from a suffix string arrives with the factory default jumper positions, and the default is not always the one the panel was designed around.
Switching frequency on the larger frames is 2 kHz, and 4 kHz on frame 7. That figure is not a preference: it is the value the published ratings were established at, together with the ambient temperature printed in the same row. Choosing a higher switching frequency to reduce audible noise moves the drive outside the derating table, and the amp code that looked adequate on paper then has to be re-checked against the derating curves before the order is placed.
The published ambient for these rows is 40 degrees C, and it is printed in the same table as the switching frequency because the two together define the rating. A cabinet that reaches 45 degrees C in summer is outside the row the drive was selected from, and the answer is not a bigger drive but either more airflow or a lower switching frequency. Neither adjustment is obvious from a nameplate, which is why both figures belong on the page rather than in an appendix.
Precharge resistors and contactors are wear items on a common-bus drive. Every energisation charges a capacitor bank through the precharge path, so the number of starts over a decade is not a trivial count. A maintenance schedule that records precharge operations, rather than only running hours, predicts the failure before the board does, and the jumper settings are part of that record because a board left in bypass charges the bus through the wrong path.
The rule that a disconnect switch must not sit between the drive input and a common DC bus without an external precharge device is written into the instructions for a reason. The bus is shared, so a disconnector on one inverter branch is not a local isolator: it separates a capacitor bank from a supply that other inverters are still charging. Anyone who treats it as a maintenance isolator and opens it under load is opening a DC circuit that has no natural current zero.
These catalog numbers belong to a bulletin that was announced as discontinued with an engineering replacement category. Engineering replacement means the successor is a different design, so the precharge board, the TB1 wiring and the jumper settings of the old unit have no direct equivalent in the new one; the changeover is a re-engineering task with a commissioning window, not a like-for-like exchange during a weekend shutdown.
The one minute and three second columns describe what the output stage will hold during a load step. At these ratings the three second figure is several hundred amps above continuous, which is what carries a heavy conveyor through a start. The motor, the cable and the protector all have to tolerate that current for the same duration, so the drive's overload row is a system constraint rather than a drive-only specification.
The precharge board on frames 7 through 9 carries three jumper blocks. JMP1 selects the auxiliary control supply, 24 V DC on positions 1-2 and 120 V AC on positions 2-3. JMP2 selects interlock or bypass on the precharge contactor path, with bypass as the factory default. JMP3 must be left on positions 1-2 and is marked do not use; the bypass setting on 2-3 exists for test benches. Reading those three blocks before closing a disconnector is cheaper than replacing a precharge resistor.
DC input current is not the same as output current, and on a common-bus drive the difference is the point. The input row states the current the drive draws from the bus at its rated output, while the output row states what it delivers to the motor, including the one minute and three second overload columns. A panel that sizes its DC bus bars from the output rating alone will run the bus at a higher current than the drawing shows during acceleration.
Where a site runs several inverters from one rectifier, the DC bus bars, the discharge path and the precharge interlock are the three drawings that maintenance actually needs. The drive's own catalog number says nothing about the other two, but it does say what the drive expects: a precharge enable signal on a digital input, a contact on TB1, and an auxiliary contact on the disconnector. Those expectations are the interface to the rest of the bus.
The DC bus is a hazard that outlives the command to stop. Capacitors hold charge after the disconnector opens, and on a shared bus they can be held up by another drive still running. Instructions that require a proven discharge path and an interlock are not paperwork: they are the difference between a maintenance window and an incident. Publishing the interlock requirement on the product page puts it in front of the person who specifies the panel, not only the person who reads the manual afterwards.
The fuse figures in this range are semiconductor fuses with published catalog numbers, not generic ampere ratings. That matters because the fuse has to protect the module before the module's own overcurrent trip acts, and a substitute of the same amp rating from a different family does not carry the same clearing characteristic. The instructions list the fuse by catalog number alongside the DC input current, which is the only honest way to specify it for a retrofit.
Common-bus arrangements pay off where several motors work against each other: one axis regenerating while another accelerates, with the energy circulating on the bus instead of being dissipated. The cost is that the bus becomes a single point of failure with several owners. A drive page that publishes the DC input current, the fuse catalog number and the precharge interlock requirement gives the panel designer the three facts needed to make that shared asset safe rather than merely functional.
Catalog numbers, options and spare parts for the same PowerFlex 700 range are listed in the Drives & Motors category. This drive itself can be checked against the shop listing at 20BP325A0ANNNNC0.
This part sits in the Allen-Bradley PowerFlex drives and motors category, with the other models and spare parts listed alongside it.